INIM TRIPLICATE PHOTOELECTRIC BEAM DETECTOR

INIM TRIPLICATE PHOTOELECTRIC BEAM DETECTOR

GENERAL VIEW

  1. Wire entry
  2. Connection terminal board
  3. LED indicators
  4. Beam alignment-level indicator
  5. Lens
  6. Horizontal adjustment trimmer
  7. Vertical adjustment screw
  8. Mount screw location
  9. Cover screw
  10. Bracket-mount screw location
  11. Tamper protection
  12. Response time adjustment
  13. Voltage-tester entry
  • Power (verde) si accende quando la barriera è alimentata.
  • Power (green) is ON when the beam is powered.

  • ALARM (rosso) si accende in caso di segnale di allarme.
  • LEVEL (verde) aumenta la luminosità in base al numero di LED di alineamento accesi.
  • ILED 1-8 indicano il livello dell’allineamento delle barriere.

  • ALARM (red) is ON when the beam senses alarm conditions.
  • LEVEL (green) becomes brighter as more alignment indicator LEDs go ON.
  • LEDs 1-8 8 is ON indicate the level of the beam alignment.

TECHNICAL SPECIFICATIONS

BD-T100                       BD-T200
Supply voltage 12 to 24 Vdc
Nominal voltage 13.8 Vdc
Current draw (max.) 80 mA 100 mA
Operating Temperature -25 to +55 °C
Environmental humidity 5 to 95 %
Outdoor range 100 200
Indoor range 300 600
Beam characteristics Pulse infrared triplicate beams
Response time 50 to 700 msec (selectable)
Alarm time 2 sec (± 1) nominal
Alarm Relay output N.C. or N.O., 30 Vdc, 500 mA max.
Tamper output N.C., 24 Vdc, 500 mA max.
Installation method Pole mount
Alignment angles Horizontal 180° (± 90°), vertical 20° (± 10°)
IP grade IP54
Weight 1500 g (receiver + transmitter)
Casing Black PC resin

INSTALLATION

  1. Remove the screw and detach the cover from the backplate.
  2. Pull the wire through the wire entry.
  3. Mount the detector.
    3-a. Break off the wire-entry knockout and pull the wires through.
    3-. Break off the bracket-mount knockouts
    3-C. Using the brackets mount the detector to the pole
  4. Connect the wires to the terminals.
  5. Adjust the beam alignment.
  6. Replace the cover
Cavo

Sezione (mm²) Section (mm²)

Cable

Diametro (mm) Diameter (mm)

Lunghezza cavi (mm)

DC 12V

Wiring distance (mm)

DC 24V

0.5 0.8 300 600
0.75 1.0 400 800
1.25 1.2 700 1400
2.0 1.6 1000 2000

 

Terminale

Terminal

Transmitter                Receiver
1 Alimentazione + Power supply + Non usato Free
2 Alimentazione – Power supply – Alimentazione + Power supply +
3 Non usato Free Alimentazione – Power supply –
4 Non usato Free Non usato Free
5 Non usato Free Allarme – Comune Alarm – Common
6 Non usato Free Allarme – Norm chiuso Alarm – Norm closed
7 Non usato Free Allarme – Norm aperto Alarm – Norm open
8 Non usato Free Non usato Free
9 Antisabotaggio Tamper Antisabotaggio Tamper
10 Antisabotaggio Tamper Antisabotaggio Tamper

INSTALLATION RECOMMENDATIONS

INIM TRIPLICATE PHOTOELECTRIC BEAM DETECTOR-7

In placements where obstacles (such as trees or even full clothes-lines) are situated between the receiver and the transmitter.

INIM TRIPLICATE PHOTOELECTRIC BEAM DETECTOR-8

In places where the installation base is unstable.

INIM TRIPLICATE PHOTOELECTRIC BEAM DETECTOR-9

In places where sunlight or car headlights shine directly onto the detector.

Distanza di copertura (m)

Protection distance (m)

Dispersione (m)

Dispersion (m)

50 1.5
75 2.3
100 3.0
125 3.8
150 4.5
175 5.4
200 6.0
250 7.5

In case of using many groups of detectors when long-distance protection to avoid the mutual disturbance of light beams.

INIM TRIPLICATE PHOTOELECTRIC BEAM DETECTOR-10

INIM TRIPLICATE PHOTOELECTRIC BEAM DETECTOR-11

INIM TRIPLICATE PHOTOELECTRIC BEAM DETECTOR-16

ALIGNMENT

Accurate beam alignment optimizes the sensing capacity of the detector and thus improves security and lowers the false-alarm rate, especially in difficult environments.
After mounting the devices, correct alignment is achieved through the lens positions.
It is attained by rotating the optical axis horizontally or vertically: adjustments can be made within a #90° horizontal angle and t10° vertical angle.

INIM TRIPLICATE PHOTOELECTRIC BEAM DETECTOR-12 INIM TRIPLICATE PHOTOELECTRIC BEAM DETECTOR-13

The alignment level can be gauged in two ways:

  • LEDs 1-8 light in accordance with the beam-alignment level; the more LEDs that light, the better the beam alignment level.

A good level is indicated by the activation of 5 LEDs.

  • Voltage measurement at LEVEL connectors:
    Insert the tester probes into the voltage-tester entries and measure the voltage.
    A good level is indicated by a voltage of at least 1.5V (maximum measurable voltage is 1.8V).

RESPONSE TIME SETTING

INIM TRIPLICATE PHOTOELECTRIC BEAM DETECTOR-14

Livello Level Tempo di risposta (msec) Response time (msec)
1 50
2 80
3 306
4 408
5 700

If the receiver does not receive a signal from the transmitter within the set Response time, the detector will trigger an alarm.
The interval can be set by means of the screw inside the “RESPONSE TIME” entry. 5 setings are available (refer to table).

INIM TRIPLICATE PHOTOELECTRIC BEAM DETECTOR-15

TROUBLESHOOTING

Trouble Possible cause Solution
The LEDs do not go ON Inade uate power supply. Check the power supply and wiring.
The alarm LED does not go ON even when the beams are violated. 1. The receiver is picking up beams from other sources.

2. The three beams are not violated simultaneously.

3. The response time is too short

1.  Remove the reflecting object or adjust the optical axis.

2.  Increase the response time.

In the event of beam violation, the alarm LED goes on but the detector does not trigger an alarm. 1. There is a short circuit.

2. The terminal wiring has not been completed correctly.

Check all wiring.
The alarm LED is always ON. 1. The optical axis is positioned incorrectly.

2. There are obstacles between the transmitter and receiver.

3. The detector cover or lens is dirty.

1.  Adjust the optical axis.

2.  Remove the obstacle.

3.  Clean the detector with a soft lint-free cloth.

Intermittent alarm. 1. Improper wiring.

2. Inade uate power-supply.

3. Moving obstacles between the transmitter and receiver.

4. Unstable mounting base.

5. The optical axis is not well positioned.

6. The response time is too short.

7. The lenses do not emit beams.

1.  Check wiring.

2.  Check the power supply.

3.  Remove the obstacles.

4.  Stabilize the base.

5.  Adjust the optical axis.

6.  Increase the response time.

7.  Change the detector placements.

WARNING

The device must be installed in accordance with the instructions herein.
Do not touch the sensor surface as this may cause degradation of its performance.
Ensure that the power supply is off before cleaning the detector with a soft lint-free cloth dampened with a small amount of alcohol.
This product reduces the risk of intrusions but cannot be considered a guarantee of absolute security. Take all necessary precautions when protecting your premises.
Once this product has been properly mounted and setup, carry out a walk test by creating motion in the protected area.

DECLARATION OF CONFORMITY
The declaration of conformity to the Directive 2004/108/CE may be consulted at
www.inim.biz/dc.html

via Fosso Antico, Centobuchi
63076 Monteprandone AP-Italy
tel +39 0735 705007
fax +39 0735 734912
info@inim.biz
www.inim.biz

Documents / Resources

INIM TRIPLICATE PHOTOELECTRIC BEAM DETECTOR [pdf] Installation Guide
TRIPLICATE PHOTOELECTRIC BEAM DETECTOR, TRIPLICATE PHOTOELECTRIC BEAM, PHOTOELECTRIC BEAM DETECTOR, DETECTOR, BD-T100, BD-T200, BEAM DETECTOR

References

Leave a comment

Your email address will not be published. Required fields are marked *