10783331 Multifunction With Active Energy Count
Multimetering
They measure and display simultaneously more quantities
Energy counting
They quantify the energy consumption
Communication
They communicate the measurements carried at a distance
Interface different ways of communication
Measuring and Monitoring
They measure and report specific involved conditions
The technical documentation for the product is available on www.imeitaly.com website in the “Technical documentation” area, type in the field “Technical note code NT879.
Waring Diagrams
F: 0,5A gG
NOTE
The wiring diagrams show the device complete with pulse output and RS485 interface.
In case of version without these features, the corresponding terminals must not be considered.
ATTENTION!
Aux. supply must be connected to terminals 20 and 21
Mounting instructions
Mounting of this equipment must be carried out just by skil-led personnel.
Please make sure that the data on the label (measuring voltage,
measuring current, extra supply voltage, frequency) correspond to the network on which the meter must be connected. In the wiring scrupulously respect the wiring diagram; an error in connection unavoidably leads to wrong measure-ments or damages to the meter.
When the meter is connected, conclude the mounting with the configuration as described in the user’s manual.
Programming
Menu is divided on two levels, protected by two different numerical passwords. Programming is carried out by front 3-key touch screen keyboardMoves the cursor
In the pages with choice among the fixed values, it scrolls the loadable values
Increases the loaded value
In the pages with choice among the fixed values, it scrolls the loadable values
Confirms
During programming by keeping pressed keys you return to the previous page by keeping pressed keys
you leave the programming menu, without save nothing
Level 1
Password = 1000
1.0 Password
1.1 Customized display page
1.2 Connection
1.3 Current delay time and average power
1.4 Display lighting
1.5 Run hour meter count start
1.6 RS485 ModBus RTU/TCP or BACNET communication
1.7 Relay output function: Energy pulses, Alarm, State of relay switching (remote-controlled)
Level 2
Password = 2001
2.0 Password
2.1 External CT and VT ratio
Programmable Parameters
Level 1
Password = 1000
1.1 Customized display page
Possibility to load a customized display page on which you can choose which quantities the three display lines must show.
If the user loads a customized page, this will become the standard display when the meter is switched on (as alternative the one showing the line voltages).
The selectable displays for the customized page are mentioned in the tables page 7.
1.2 Connection
The meter can be used for single phase or three phase 3- and 4-wire network.
The selectable connections are:
Symbol | Line | Load | Coils | Wiring | Connection |
1N1E | Sigle-phase | – | 1 | S 1000/251 | |
3-1E | 3-phase 3 wires | Balanced | 1 | S 1000/447 | |
3N1 E | 3-phase 4 wires | Balanced | 1 | S 1000/448 | |
3-2E | 3-phase 3 wires | Unbalanced | 2 | S 1000/166 | Aron L1 – L3 |
3-3E | 3-phase 3 wires | Unbalanced | 3 | S 1000/446 | |
3N3E | 3-phase 4 wires | Unbalanced | 3 | S 1000/164 |
1.3 Current delay time and average power
Selectable delay time: 5, 8, 10, 15, 20, 30, 60 minutes
The selected time is valid both for the current and the average power
1.4 Display lighting
The 4 selectable levels (0-35-70-100%) show the display lighting percentage
1.5 Run hour meter count start
Select the quantity which starts the run hour meter count: voltage or power.
Voltage: count start with phase voltage > 20V
Power: total active power, programmable value 0,5…50%Pn (rated power)
1.6 RS485 communication (where provided)
According to the models, this meter can be without communication or equipped with
RS485 ModBus RTU/TCP or RS485 BACNET communication
1.6a RS485 ModBus RTU/TCP communication
Address number: 1…255
Parity bit: none – even – odd
Waiting time before answer: 3…100ms
Transmission speed: 4800-9600-19200-38400 bit/s
ModBus message word format’: Big Endian – Little Endian – Swap
Just for 32-bit quantities
1.6b RS485 BACNET communication
Address number: 0…127
Transmission speed: 9600-19200-38400-76800 bit/s
Parity bit: none – even – odd
Network address: 0…4000
Just for 32-bit quantities
1.7 Relay output function: energy pulses, alarm, state of relay switching
The output relay (terminals 15-29) can be used as energy pulse repeater, as alarm relay or for remote-controlled state of relay switching (function available just for models with communication).
1.7a Energy pulses
Quantity that can be coupled: active or reactive energy
Pulse weight: 1 pulse/10Wh(varh) – 100Wh(varh) – 1kWh(kvarh)-10 kWh(kvarh) -100kWh(kvarh) – 1MWh (Mvarh) – 10MWh (Mvarh)
Width of the pulse: 50-100-200-300-400-500 ms
1.7b Alarm
Quantity that can be coupled: phase voltage (L1-N, L2-N, L3-N), interlinked voltage (L1-L2, L2-L3, L3-L1), phase current (11, 12, 13),, three-phase active power, three-phase reactive power.
Intervention threshold: intervention point, decimal point, metering unit
Alarm type: min. or max.
Relay output contact: normally open (no) or normally closed (nC)
Hysteresis: 0…20%
Intervention delay: 0…99s
Reset delay: 0…995
1.7c Remote-controlled state of relay switching, bistable mode (rMtb)
Relay output contact: normally open (no) or normally closed (nC)
t on: delay elapsed between the activation remote command and the change in the state of relay of: delay elapsed between the reset remote command and the change in the state of relay t selectable values ton / t of: 0…99s
1.7d Remote-controlled state of relay switching, time mode (rMtt)
Relay output contact: normally open (no) or normally closed (nC)
t on: delay elapsed between the activation remote command and the change in the state of relay
t of: delay elapsed between the reset remote command and the change in the state of relay selectable values ton / t of: 0…995
Level 2
Password = 2001
2.1 External VT or CT ratio
Vt External primary/secondary VT ratio (ex. VT 600/100V Vt = 6)
Ct External primary/secondary CT ratío (ex. CT 800/5A Ct = 160)
External CT ratio (Ct): 1…9999 (max. primary current 50000/5A-10000/1A)
External VT ratio (Vt): 1,00…10,00 (max. primary voltage TV 1200V)
For voltage direct connection (with external voltage transformer) load Vt=1,00
By modifying the CT and/or VT ratios, the KWH meters are automatically reset
Phase sequence diagnostic
In the software of the device have added a specific functionality to detect and correct many problems concerning voltage and/or current connection.
This function can be activated through password and allows to display and modify the connec-
tion sequence provided that the following conditions are respected:
- The neutral wire (in a 4-wire network) is connected to the right terminal (normally number1).
- No crossings between cables connected to CTs (e.g. avoid that on phase 1 of the meter-terminals 1 and 3-are connected some way both to CT1 and CT2).
- The power factor is between 1 and 0,5- Inductive load – for each phase. See www.imeitaly.com “TECHNICAL SUPPORT”.
1.0 Password 1000
Pressing at the same time the keys , you display page:
Load password 1000 and confirms
1.1 Customized display page
Possibility to choose which quantities the three display lines must show. To customize the page, please select the quantity required for line 1 (among the ones shown in the Table 1)
Select the quantity required for ine 2 (among the ones shown in the Table 2)
Select the quantity required for line 3 (among the ones shown in the Table 3)
Note
The customized page will become the standard display when the meter is turned on. If you don’t want to display the customized page, you can directly go to point 1.2 Connection by pressing several times key until you display
1.2 Connection
Select the desired connection and scrupulously respect the linked wiring diagram.
The selectable wiring diagrams are:
Symbol | Line | Load | Coils | Wiring | Connection |
1N1E | Sig le-phase | 1 | S 1000/251 | ||
3-1E | 3-phase 3 wires | Balanced | 1 | S 1000/447 | |
3N1E | 3-phase 4 wires | Balanced | 1 | S 1000/448 | |
3-2E | 3-phase 3 wires | Unbalanced | 2 | S 1000/166 | Aron L1- L3 |
3-3E | 3-phase 3 wires | Unbalanced | 3 | S 1000/446 | |
3N3E | 3-phase 4 wires | Unbalanced | 3 | S 1000/164 |
1.3 Current delay time and average power
Selectable delay time: 5, 8, 10, 15, 20, 30, 60 minutes
The selected time is valid both for the current and the average power
1.4 Display lighting
The 4 selectable levels (0-35-70-100%)%) show the display lighting percentage1.5 Run hour meter count start
Select the quantity which starts the run hour meter count:
Voltage or Power.
1.5a Voltage count start
Voltage: count start with phase voltage > 20V
1.5b Power count start
Power: total active power, programmable value 0,5…50% Pn (rated power)
1.6 RS485 Communication
According to the models, this meter can be without communication or equipped with RS485 ModBus RTU/TCP or RS485 BACNET communication.
1.6a RS485 ModBus RTU / TCP CommunicationTransmission speed: 4800-9600-19200-38400 bit/s
Parity bit: none – even – odd
Waiting time before answer: 3…99ms
ModBus message word format: Big Endian – Little Endian – Swap
1.6b RS485 BACNET Communication
Address: 0…127
Transmission speed: 9600-19200-38400- 76800 bit/s
Parity bit: none – even – odd
Indirizzo di rete: 0…4000
1.7 Relay output function:: energy pulses, alarm, state of relay switching (remote-controlled)
The output relay (terminals 15-29) can be used as energy pulses (see point 1.7a) repeater or as alarm relay (see point 1.7b) or as remote-controlled state of relay switching (see point 1.7c- point 1.7c).
1.7a Energy pulses
Quantity that can be coupled: active or reactive energy
Pulse weight: 1pulse/10Wh(varh) – 100Wh(varh) – 1kWh(kvarh) – kWh(kvarh)-100kWh(kvarh) – 1MWh (Mvarh) – 10MWh (Mvarh)
Width of the pulse: 50-100-200-300-400 – 500ms
1.7b Alarm
Alarm type: min. or max.
Quantity that can be coupled: phase voltage (L1-N, L2-N, L3-N)
interlinked voltage (L1-L2, L2-L3, L3-L1)
phase current (11, 12, 13)
frequency
3-phase active power
3-phase reactive power
Intervention threshold: intervention point, decimal point, metering unit
State relay: normally open (no) or normally closed (nC)
1.7c Remote-controlled state of relay switching, bistable mode (rMtb)
Relay output contact: normally open (no) or normally closed (nC)1.7d Remote-controlled state of relay switching, time mode (rMtt)
Relay output contact: normally open (no) or normally closed (nC)Programmed data confirmation
2.0 Password 2001
2.1 External CT ratio
Ct = external primary/secondary CT ratio (ex.: CT 800/5A Ct = 160) External CT ratio (Ct): 1…9999 (max. primary current 50000/5A – 10000/1A)
External VT ratio
Vt = external primary/secondary VT ratio (ex.: TV 600/100V Vt = 6) External VT ratio (Vt): 1,00… 10,00 (max. primary voltage TV 1200V)
For voltage direct connection (with external voltage transformer) load Vt=1,00
By modifying the CT and/or VT ratios, the KWH meters are automatically reset
Display
Display is divided into 3 menus, accessible with their relevant function keys:
The quantities and the display modes vary according to the selected connection (3-phase 3- or 4-wire line, single phase, etc. In the following pages you could find all the displayed measurements based on the selected connection.
Acting on the function keys it is possible to scroll the different available measurements:
![]() |
![]() |
![]() |
|
Phase voltage | Phase current and neutral current | Active, reactive, apparent, distorting 3-phase power | Total and partial, positive active energy |
Interlinked voltage | Current demand | Active, reactive, apparent phase power | Total and partial, positive reactive energy |
Interlinked voltage | Max. current demand | Active, reactive, apparent power | Total and partial, negative active energy |
Max. voltage value | Average currents | Max. demand active, reactive, apparent power | Total and partial, negative reactive energy |
Voltage harmonic distortion | Current harmonic distortion | Phase and 3-phase power factor | Configuration data* |
Voltage harmonic analysis | Current harmonic analysis | Phase angle voltages – Phase and 3-phase current | |
Voltage peak factor | Current peak factor | Frequency | |
Phase angle between the voltages | Phase angle between the currents | Run hour meter | |
Configuration data* | Configuration data* | Configuration data* |
*See configutation factory setting at page 20
Alarm Diplay
If the meter has been programmed for relay output = alarm function (see point 1.7), in case of alarm intervention, the display blinks in order to detect the anomaly.
Pressing any of the front keys, the display stops blinking.
When the alarm is intervened, press several times key, until you display the alarm. page.
Auxiliary Supply
Terminals 20 and 21
Auxliary suppy: direct or alternating current electrical supply which is necessary for proper working of the device.
Please verify that the available supply voltage meets the one shown on the data label of the meter (voltage value and any frequency).
Where a double voltage is shown (for instance 80…265Vac/80…265Vdc) the meter can be fed with alternating voltage 80…265Vac or direct voltage 100…300Vdc.
In case of direct voltage supply please respect the shown polarities 20+ and 21.
Factory setting
Password 1000
Customized page
1 Lin 1v voltage L1
2Lin2v voltage L2
3Lin3v voltage L3
Connection: 3n3E 4-wires 3-system line
Average time: 15m 15 minutes
Backlight: 35%
Run hour meter: U Voltage start
RS485
Address: 255
Speed: 9.600
Parity: none
Transmission delay: 15mses
Word: bend
Relay output: pulse
Pulse output
Energy: active
Pulse weight: 0,01kWh
Width of the pulse: 50ms
Password 2001
CT ratio: 0001
VT ratio: 01,00
Documents / Resources
![]() |