HMW15 Surface Mount High Bay HF Motion Sensor
User ManualHYTRONIK HMW15 Surface Mount High Bay HF Motion SensorHYTRONIK HMW15 Surface Mount High Bay HF Motion Sensor - fig

HMW15 Surface Mount High Bay HF Motion Sensor

Surface Mount High Bay HF Motion SensorTCL HH42CV1 Link Hub - icon 11
HMW15
Tri-level Control for Independent DALI

Mechanical Structure

HYTRONIK HMW15 Surface Mount High Bay HF Motion Sensor - Mechanical Structure

Installation:

For more details, please refer to user manual.

  1. Direct junction “J” box mountingHYTRONIK HMW15 Surface Mount High Bay HF Motion Sensor - Mechanical Structure1
  2. Surface mount assemblyHYTRONIK HMW15 Surface Mount High Bay HF Motion Sensor - Mechanical Structure2

Note: We recommend the mounting distance between sensor to sensor should be more than 2m to prevent sensors from false-triggering.

Technical Data

Input Characteristics

Model No. HMW15
Operating voltage 120 ~ 277VAC   50/60Hz
Stand-by power <1W
Switched power Max. 20pcs devices, 40mA
Warming-up 20s

Safety and EMC

EMC standard (EMC) EN55015, EN61000
Safety standard (LVD) EN60669-1,  EN60669-2-1
Radio Equipment (RED) EN300440, EN301489-1,
EN62479
Certification Semco, CB, CE , EMC, RED, RCM

Sensor Data

Model No. HMW15
Sensor principle High Frequency (microwave)
Operation frequency 5.8GHz +/- 75MHz
Transmission power <0.2mW
Detection range Max. ( O x H) 12m x 12m
Detection angle 360°

Environment

Operation temperature Ta: -20°C ~ +50°C
IP rating IP42

HYTRONIK HMW15 Surface Mount High Bay HF Motion Sensor - icon1

Functions and Features

  1. Tri-level Control (Corridor Function)
    Hydronic builds this function inside the motion sensor to achieve tri-level control, for some areas which require a light change notice before switch-off. The sensor offers 3 levels of light: 100%–>dimmed light (natural light is insufficient) –>off; and 2 periods of selectable waiting time: motion hold-time and stand-by period; Selectable daylight threshold and freedom of detection area.
  2. Intelligent Photocell (daylight detection prior to motion detection)
    The built-in photocell will also automatically turn off the light when the ambient natural light exceeds the programmed lux level for more than 5min, regardless of whether motion is detected or not. This feature can be disabled if it is  required that the fixture stays at dimmed level during absence.HYTRONIK HMW15 Surface Mount High Bay HF Motion Sensor - Photocell
    With sufficient natural light, the light does not switch on when presence is detected.HYTRONIK HMW15 Surface Mount High Bay HF Motion Sensor - Photocell1
    With insufficient natural light, the sensor switches on the light automatically when presence is detected.HYTRONIK HMW15 Surface Mount High Bay HF Motion Sensor - Photocell2The sensor switches off the light when natural light is sufficient, even with presence.
    Note: if the stand-by time is preset at “+∞”, the fixture never switches off but stays at preset dimming level even when natural light is sufficient.
  3. Manual Override
    With the help of push-switch, this sensor can be over-ridden by the end-user to manually switch on/off the light, or adjust the brightness by push-switch, which makes the product more user-friendly and offers more options to fit  some extra-ordinary demands:
    * Short Push (<1s): on/off function;
    On → Off: the light turns off immediately and cannot be triggered ON by motion until the expiration of pre-set hold-time. After this period, the sensor goes back to normal sensor mode.
    Off → On: the light turns on and goes to sensor mode, no matter if ambient Lux level exceeds the daylight threshold or not.
    * Long Push (>1s): adjust the hold-time brightness level between10% and 100%.
    Note: if end-user do not want this manual override function, just leave the “push” terminal unconnected to any wire.
  4. Semi-auto Mode (Absence Detection)
    It is easy to forget to switch off the light, in office, corridor, even at home. And in many other cases, people do not want to have a sensor to switch on the light automatically, for example, when people just quickly pass-by, there is no  need to have the light on. The solution is to apply this “absence detector”: motion sensor is employed, but only activated on the manual press of the push-switch, the light keeps being ON in the presence, and dims down in the absence, then switches off in the long absence.
    Note: end-user can choose either function 3 or function 4 for application. Default function is manual override.
  5. Semi-auto Mode (Absence Detection)
    It is easy to forget to switch off the light, in office, corridor, even at home. And in many other cases, people do not want to have a sensor to switch on the light automatically, for example, when people just quickly pass-by, there is no  need to have the light on. The solution is to apply this “absence detector”: motion sensor is employed, but only activated on the manual press of the push-switch, the light keeps being ON in the presence, and dims down in the  absence, then switches off in the long absence. Note: end-user can choose either function or function for application. Default function is manual override.

Settings (Remote Control HRC-11)

HYTRONIK HMW15 Surface Mount High Bay HF Motion Sensor - icon3 Permanent ON/OFF function
Press button “ON/OFF” to select permanent ON or permanent OFF mode.
* Press button “AUTO”, “RESET” to quit this mode.
The mode will change to AUTO Mode after power failure.

HYTRONIK HMW15 Surface Mount High Bay HF Motion Sensor - icon4 Reset Settings
Press button “RESET”, all settings go back to rotary switch settings.

HYTRONIK HMW15 Surface Mount High Bay HF Motion Sensor - icon5 Shift Button
Press button “Shift”, the LED on the top left corner is on to indicate mode selection. All values / settings in RED are valid for 20 seconds.

HYTRONIK HMW15 Surface Mount High Bay HF Motion Sensor - AUTO mode AUTO mode
Press button “AUTO” to initiate automatic mode. The sensor starts working and all settings remain as before the light is switched ON/OFF.HYTRONIK HMW15 Surface Mount High Bay HF Motion Sensor - (Remote Control

HYTRONIK HMW15 Surface Mount High Bay HF Motion Sensor - AUTO mode SEMI-AUTO mode

  1. Press button “Shift”, the red LED ashes for indication.
  2. Press button “SEMI-AUTO/AUTO” to initiate semi-auto mode. The fixture is manually turned on by pressing the push-switch, and goes off automatically in this mode. (Absence detection mode)

HYTRONIK HMW15 Surface Mount High Bay HF Motion Sensor - Power output Power output
Press the buttons to select light output at 80% (at initial 10,000 hours) or 100%.
Note: “Sensor off” and “Twilight” functions are disabled.

HYTRONIK HMW15 Surface Mount High Bay HF Motion Sensor - Scene programScene program – 1-key commissioning

  1. Press button “Start” to program.
  2. Select the buttons in “Detection range”, “Daylight threshold”, “Hold-time”, “Stand-by time”, “Stand-by dimming level” to set all parameters.
  3. Press button “Memory” to save all the settings programmed in the remote control.
  4. Press button “Apply” to set the settings to each sensor unit(s).
    For example, to set detection range 100%, daylight threshold Disable, hold-time 5min, stand-by time +∞, stand-by dimming level 30%, the steps should be:
    Press button “Start”, button ”100%”, “Disable”, “Shift”, “5min”, “Shift”, “+∞”, “30%”, “Memory”. By pointing to the sensor unit(s) and pressing “Apply”, all settings are passed on the sensor(s).

HYTRONIK HMW15 Surface Mount High Bay HF Motion Sensor - Brightness Brightness +/-
Press the buttons to adjust the light brightness during hold-time.
Detection range
Press buttons in zone “Detection range” to set detection range at 100% / 75% / 50% / 10%.
Daylight threshold
Press buttons in zone “ Daylight threshold” to set daylight sensor at 2Lux/ 10Lux / 50Lux / 100Lux / 300Lux / 500Lux / Disable.
Note: To set daylight sensor at 100Lux / 300Lux / 500Lux, press “Shift” button first.
Ambient daylight threshold

  1. Press button “Shift”, the red LED starts to fiat.
  2. Press button “Ambient”, the surrounding lux level is sampled and set as the new daylight threshold.

Hold-time
Press buttons in zone “hold-time” to set the hold-time at 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min.

Note:

  1. To set hold-time at 30s / 5min / 15min / 30min, press “Shift” button first.
  2. 2s is for testing purpose only, stand-by period and daylight sensor settings are disabled in this mode.
    *To exit from Test mode, press button “RESET” or any button in “Hold-time”.

Stand-by time (corridor function)
Press buttons in zone “stand-by time” to set the stand-by period at 0s / 10s / 1min / 5min / 10min / 30min / 1h / +∞.
Note: “0s” means on/off control; “+∞” means bi-level control, the fixture is 100% on when there is motion detected, and remains at the stand-by dimming level when no presence after motion hold-time.

Stand-by dimming level
Press the button in zone “stand-by dimming level” to set the stand-by dimming level at 10% / 20% / 30% / 50%.
Auto-configuration function
All buttons in this zone are disabled.
Dual tech & RF mode
All buttons are disabled.

HYTRONIK HMW15 Surface Mount High Bay HF Motion Sensor - Dual tech

Rotary Switch Preset

A rotary switch is built inside the sensor for scene selection / fast programming. Total 16 channels are available:

HYTRONIK HMW15 Surface Mount High Bay HF Motion Sensor - Rotary

Note: settings can also be changed by remote control HRC-11. The last action controls.

Channel Detection range Hold-time Daylight sensor Stand-by time Stand-by dim level
0 100% 5s Disable 10s 10%
1 100% 1min 2Lux 5min 10%
2 100% 5min 10Lux 10min 10%
3 100% 5min 30Lux 30min 10%
4 100% 5min 10Lux 0s Disable
5 100% 5min 30Lux +∞ 10%
6 100% 5min Disable +∞ 30%
7 100% 10min 2Lux 10min 10%
8 100% 10min 10Lux 30min 10%
9 100% 10min 30Lux +∞ 10%
A 100% 10min Disable +∞ 30%
B 75% 10min 30Lux +∞ 10%
C 50% 10min 10Lux +∞ 10%
D 100% 30min 50Lux +∞ 10%
E 100% 30min Disable +∞ 30%
F 100% 5s 2Lux 10s 10%

Detection Pattern

HYTRONIK HMW15 Surface Mount High Bay HF Motion Sensor - Detection Pattern

Additional Information / Documents

  1. Regarding precautions for microwave sensor installation and operation, please kindly refer to www.hytronik.com/download ->knowledge ->Microwave Sensors – Precautions for Product Installation and Operation
  2. Regarding Hydronic standard guarantee policy, please refer to www.hytronik.com/download ->knowledge ->Hydronic Standard Guarantee Policy

HYTRONIK - logo

HYTRONIK HMW15 Surface Mount High Bay HF Motion Sensor - icon

Subject to change without notice.
Edition: 26 Feb. 2020 Ver. A0

Documents / Resources

HYTRONIK HMW15 Surface Mount High Bay HF Motion Sensor [pdf] User Manual
HMW15, HMW15 Surface Mount High Bay HF Motion Sensor, Surface Mount High Bay HF Motion Sensor, High Bay HF Motion Sensor, HF Motion Sensor, Motion Sensor, Sensor

References