HMW15

Product introduction HMW15

HMW15 IP42 High Bay DALI Sensor Hytronik


File Info : application/pdf, 5 Pages, 1.27MB

PDF preview unavailable. Download the PDF instead.

HMW15-1
11 43.5 64.7 69.1
29 50.2

Surface Mount High Bay HF Motion Sensor HF HMW15
Tri-level Control for Independent DALI
Mechanical Structure

C - Surface box B - Facia Cover

Infrared receiver HF Sensor module

Photocell LED indicator

56

109

38.6

Rotary switch preset

A - Control Board

Installation:
For more details, please refer to user manual.
1 Direct junction "J" box mounting

2 Surface mount assembly

Note:We recommend the mounting distance between sensor to sensor should be more than 2m to prevent sensors from false-triggering.

Technical Data
Input Characteristics Model No.
Operating voltage Stand-by power Switched power Warming-up

HMW15 120 ~ 277VAC 50/60Hz
<1W Max. 20pcs devices, 40mA
20s

Sensor Data
Model No. Sensor principle Operation frequency Transmission power Detection range Detection angle

HMW15 High Frequency (microwave)
5.8GHz +/- 75MHz <0.2mW
Max. ( O x H) 12m x 12m 360O

Safety and EMC EMC standard (EMC) Safety standard (LVD)
Radio Equipment (RED)
Certification

EN55015, EN61000 EN60669-1, EN60669-2-1
EN300440, EN301489-1, EN62479
Semko, CB, CE , EMC, RED, RCM

Environment Operation temperature IP rating

Ta: -20OC ~ +50OC IP42

RED

IP42

Subject to change without notice.

Edition: 26 Feb. 2020 Ver. A0 Page 1/5

Intelligent Photocell

Detection Pattern

0

6

One-Key

Rotary Switch

Commissioning

Programing

12

TX

TX 39
synchronization control

TX

Ambient daylight threshold

Functions and Features
1 Tri-level Control (Corridor Function) Hytronik builds this function inside the motion sensor to achieve tri-level control, for some areas which require a light change notice before switch-off. The sensor offers 3 levels of light: 100%-->dimmed light (natural light is insufficient) -->off; and 2 periods of selectable waiting time: motion hold-time and stand-by period; Selectable daylight threshold and freedom of detection area.

2 Intelligent Photocell (daylight detection prior to motion detection)
The built-in photocell will also automatically turn off the light when the ambient natural light exceeds the programmed lux level for more than 5min, regardless of whether motion is detected or not. This feature can be disabled if it is required that the fixture stays at dimmed level during absence.

With sufficient natural light, the light does not switch on when presence is detected.

With insufficient natural light, the sensor switches on the light automatically when presence is detected.

The sensor switches off the light when natural light is sufficient, even with presence.

Note: if the stand-by time is preset at "+", the fixture never switches off but stays at preset dimming level even when natural light is sufficient.

3 Manual Override
With the help of push-switch, this sensor can be over-ridden by the end-user to manually switch on/off the light, or adjust the brightness by push-switch, which makes the product more user-friendly and offers more options to fit some extra-ordinary demands:
* Short Push (<1s): on/off function; On ¹ Off: the light turns off immediately and cannot be triggered ON by motion until the expiration of pre-set hold-time. After this period, the sensor goes back to normal sensor mode. Off ¹ On: the light turns on and goes to sensor mode, no matter if ambient Lux level exceeds the daylight threshold or not.
* Long Push (>1s): adjust the hold-time brightness level between10% and 100%.
Note: if end-user do not want this manual override function, just leave the "push" terminal unconnected to any wire.

4 Semi-auto Mode (Absence Detection) It is easy to forget to switch off the light, in office, corridor, even at home. And in many other cases, people do not want to have a sensor to switch on the light automatically, for example, when people just quickly pass-by, there is no need to have the light on. The solution is to apply this "absence detector": motion sensor is employed, but only activated on the manual press of the push-switch, the light keeps being ON in the presence, and dims down in the absence, then switches off in the long absence.
Note: end-user can choose either function 3 or function 4 for application. Default function is manual override.

Subject to change without notice.

Edition: 26 Feb. 2020 Ver. A0 Page 2/5

5 Synchronisation Function
By connecting the DALI terminals in parallel (see wiring diagram), no matter which sensor detects motion, all HMW15 in the group will turn on the lights when surrounding natural light is below the daylight threshold. The detection area could be widely enlarged in this way.

Settings (Remote Control HRC-11)

ON/ OFF

Permanent ON/OFF function

Press button "ON/OFF" to select permanent ON or permanent OFF mode. * Press button "AUTO", "RESET" to quit this mode. The mode will change to AUTO Mode after power failure.

Reset Settings Press button "RESET", all settings go back to rotary switch settings.

Shift Button
Press button "Shift", the LED on the top left corner is on to indicate mode selection. All values / settings in RED are valid for 20 seconds.

AUTO mode Press button "AUTO" to initiate automatic mode. The sensor starts working and all settings remain as before the light is switched ON/OFF.
SEMI-AUTO mode
1. Press button "Shift", the red LED flashes for indication. 2. Press button "SEMI-AUTO/AUTO" to initiate semi-auto mode. The fixture is manually turned on by pressing the push-switch, and goes off automatically in this mode. (Absence detection mode)
Power output Press the buttons to select light output at 80% (at initial 10,000 hours) or 100%. Note: "Sensor off" and "Twilight" functions are disabled.

& A

4h

h

4h

HRC-11

Scene program - 1-key commissioning
1. Press button "Start" to program. 2. Select the buttons in "Detection range", "Daylight threshold", "Hold-time", "Stand-by time", "Stand-by dimming le vel" to set all parameters. 3. Press button "Memory" to save all the settings programmed in the remote control. 4. Press button "Apply" to set the settings to each sensor unit(s).
For example, to set detection range 100%, daylight threshold Disable, hold-time 5min, stand-by time +, stand-by dimming level 30%, the steps should be: Press button "Start", button "100%", "Disable", "Shift", "5min", "Shift", "+", "30%", "Memory". By pointing to the sensor unit(s) and pressing "Apply", all settings are passed on the sensor(s).

Subject to change without notice.

Edition: 26 Feb. 2020 Ver. A0 Page 3/5

Brightness +/Press the buttons to adjust the light brightness during hold-time.
Detection range Press buttons in zone "Detection range" to set detection range at 100% / 75% / 50% / 10%.
Daylight threshold Press buttons in zone " Daylight threshold" to set daylight sensor at 2Lux/ 10Lux / 50Lux / 100Lux / 300Lux / 500Lux / Disable. Note: To set daylight sensor at 100Lux / 300Lux / 500Lux, press "Shift" button first.

Ambient daylight threshold
1. Press button "Shift", the red LED starts to flash. 2. Press button "Ambient", the surrounding lux level is sampled and set as the new daylight threshold.

Hold-time
Press buttons in zone "hold-time" to set the hold-time at 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min. Note: 1. To set hold-time at 30s / 5min / 15min / 30min, press "Shift" button first.
2. 2s is for testing purpose only, stand-by period and daylight sensor settings are disabled in this mode. *To exit from Test mode, press button "RESET" or any button in "Hold-time".

Stand-by time (corridor function)
Press buttons in zone "stand-by time" to set the stand-by period at 0s / 10s / 1min / 5min / 10min / 30min / 1h / +. Note: "0s" means on/off control; "+" means bi-level control, the fixture is 100% on when there is motion detected, and remains at the stand-by dimming level
when no presence after motion hold-time.

Stand-by dimming level Press the button in zone "stand-by dimming level" to set the stand-by dimming level at 10% / 20% / 30% / 50%.

Auto-configuration function All buttons in this zone are disabled.
Dual tech & RF mode All buttons are disabled.
L N

Wiring Diagram

SY SY P N L NC NC
HMW15 DALI
-+

L

N LED Driver LED+

DALI+ DALI_

LED _

SY SY P N L NC NC
HMW15 DALI
-+

L

N LED Driver LED+

DALI+ DALI _

LED _

NFUSFT UPUBM
NBYGPSNNq$4" 5B
 NFUSFT UPUBM
NBYGPSNNq$4" 5B


Subject to change without notice.

Edition: 26 Feb. 2020 Ver. A0 Page 4/5

Rotary Switch Preset
A rotary switch is built inside the sensor for scene selection / fast programming. Total 16 channels are available:
Rotary switch preset Note: settings can also be changed by remote control
HRC-11. The last action controls.

Channel
0 1 2 3 4 5 6 7 8 9 A B C D E F

Detection range 100%
100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 75% 50% 100% 100% 100%

Hold-time
5s 1min 5min 5min 5min 5min 5min 10min 10min 10min 10min 10min 10min 30min 30min 5s

Daylight sensor
Disable
2Lux 10Lux 30Lux 10Lux 30Lux Disable 2Lux 10Lux 30Lux Disable 30Lux 10Lux 50Lux Disable 2Lux

Stand-by time 10s
5min 10min 30min 0s + + 10min 30min + + + + + + 10s

Stand-by dim level
10%
10% 10% 10% Disable 10% 30% 10% 10% 10% 30% 10% 10% 10% 30% 10%

Ceiling mounted height(m)

Detection Pattern
0 6
10% 30% 50% 75%
12

Additional Information / Documents
1. Regarding precautions for microwave sensor installation and operation, please kindly refer to www.hytronik.com/download ->knowledge ->Microwave Sensors - Precautions for Product Installation and Operation
2. Regarding Hytronik standard guarantee policy, please refer to www.hytronik.com/download ->knowledge ->Hytronik Standard Guarantee Policy

Subject to change without notice.

Edition: 26 Feb. 2020 Ver. A0 Page 5/5

