Siemens Climatix RT RTU Controller POL648.10/RTU
Quick Start Guide
Document No. A5W00153010
April 29, 2022
Pre-installation steps
- Download the Climatix Mobile App to be used for setup and commissioning.
- iOS: [QR code for iOS app]
- Android: [QR code for Android app]
- Ensure you have a Siemens WLAN stick for connectivity from the controller to the Climatix Mobile App.
Related Documentation
Document ID | Title | Description | QR Code |
---|---|---|---|
A6V12001603 | Climatix RT Rooftop Unit Controller Data Sheet | Functions, use, technical data, terminal concept, and dimensions for the POL648.10/RTU controller | [QR Code] |
A6V12250551 | Climatix RT RTU Controller POL648.10/RTU Installation Instructions | Mounting and wiring the Climatix controller | [QR Code] |
A5W00153010 | Climatix RT RTU Controller POL648.10/RTU Quick Start Guide | Pre-assigned I/O terminations for Climatix RT | [QR Code] |
A6V12053407 | Remote Monitoring and Intelligent Diagnostics for Roof Top Unit Controllers Start Up | Startup document for Climatix RTU solution and Climatix IC setup | [QR Code] |
A6V101099058_en | Climatix: Technical Limits | Technical limits of controller devices and integration |
Power supply
Diagram
Terminal T8
Supply AC 230 V
[Electrical diagram showing transformer with 230V AC input and 24V AC output, connected to terminals labeled 24V~ and 24V~]
Standard Configuration Wiring Diagram
[Diagram showing connections for a standard HVAC system including: Siemens Power Meter, 141-0518 Air Filter Status Switch, FAN STATUS, Variable Fan Speed Out, Damper Command, Damper Feedback, OAH, OAT & OAH Combo Sensor (QFR9530), Mixed Air Temperature Sensor, Discharge Air Temperature Sensor, Compressor 3 Run Status, Compressor 2 Run Status, Compressor 1 Run Status. The Climatix RT unit is shown with connections to QMX3.P74 Room Unit and Siemens VFD, with terminal labels PWR, COMMON, 24v PWR, G, W2, W1, RV, Y2, Y1.]
Heat Pump Configuration Wiring Diagram
[Diagram showing connections for a heat pump system including: Siemens Power Meter, 141-0518 Air Filter Status Switch, FAN STATUS, Variable Fan Speed Out, Damper Command, Damper Feedback, OAH, OAT & OAH Combo Sensor (QFR9530), Mixed Air Temperature Sensor, Discharge Air Temperature Sensor, Compressor 3 Run Status, Compressor 2 Run Status, Compressor 1 Run Status. The Climatix RT unit is shown with connections to QMX3.P74 Room Unit and Siemens VFD, with terminal labels PWR, COMMON, 24v PWR, G, W2, W1, RV, Y2, Y1.]
Input and Output Terminals
Auxiliary Inputs
- X9: Compressor 1 Run Status
- X10: Compressor 2 Run Status
- X11: Compressor 3 Run Status
Auxiliary Outputs
- X1: Discharge Air Temperature Sensor
- X2: Mixed Air Temperature Sensor
- X3: Outside Air Temperature Sensor
- X4: Outside Air Humidity Sensor
- X5: Damper Command
- X6: Damper Feedback
- X7: Not assigned
- X8: Not assigned
Digital Inputs
- DI1: Traditional Fan Speed Feedback
- DI2: Clog Filter Switch Status
- DI3: Not assigned
- DI4: Not assigned
Digital Outputs
- DO1: Compressor 1 Run Enable
- DO2: Compressor 2 Run Enable
- DO3: Compressor 3 Run Enable
- DO4: Heater Stage 1 Enable
- DO5: Heater Stage 1 Enable
- DO6: Traditional Fan Speed DO