T4M Thermostat
Programmable Modulating Thermostat
Quick Start Installation Guide
T4M Programmable Modulating Thermostat
Compatible with Open Term appliances only.
Not compatible with 230V boilers, zone valve applications or 230V electric heating.
Installation in 3 steps
Must be installed by a competent person.
To ensure your safety make sure the mains power is switched OFF before accessing wiring.
Open Term Boiler
To prevent a short circuit from a loose wire
- When using multi-core cables: Only remove enough outer insulation to allow secure fixing of the cores into the terminal block.
- When using single core cables: Secure them together with a cable tie as close as possible to the terminal block.
- Wire the Thermostat
Find a suitable wall location away from draughts, direct sunlight or other heat sources, and where cables can be run from the boiler to the thermostat.A) Separate the Wallplate from the thermostat, and using a screwdriver open the Wallplate terminal cover to connect wires.
B) Connect wires according to wiring diagrams and clip the cover closed.
- Power Up and Test
Power Up the Heating System and do a quick functional test on the thermostat to check that it switches the boiler. - Configure the System
Specific settings for the thermostat and heating system can be configured in the advanced menu.
Press and holdand then
buttons together until the display changes (approx. 3 seconds).
A) Press
and
buttons to navigate through the parameter list
B) Press
and
buttons to change a parameters
C) Press
button to save the change
(or press to cancel the change)
D) Press button to exit advanced menu and save any changes
Parameters
No | Description | Settings (default in bold) |
![]() |
Language | 1 = EN, 2 = NL, 3 = DE, 4 = FR, 5 = ES |
![]() |
Lower Temperature Limit | 5 – 21 (°C) |
![]() |
Upper Temperature Limit | 21 – 35 (°C) |
![]() |
Schedule options | 1 = 7 day (different schedule each day of the week) 2 = 5 + 2 day (weekday + weekend schedule) 3 = 1 day (same schedule every day) |
![]() |
Number of periods per day | 4 or 6 |
![]() |
Wired Remote Sensor | 0 = No Remote Sensor, 1 = Wired Remote Sensor |
![]() |
Fail Safe mode | 0 = Boiler off, 1 = Boiler 20% on / 80% off |
![]() |
Backlight | 0 = Off, 1 = On (only on demand) |
![]() |
Clock Format | 0 = 24 hr, 1 = AM/PM |
![]() |
Daylight Saving time change | 0 = Off, 1 = Auto |
![]() |
Temperature Display Offset | +/-1.5°C |
![]() |
Restore Schedule Defaults | 0, 1 = reset |
![]() |
Restore Factory Settings | 0, 1 = reset |
![]() |
Low load control | 0 = Off, 1 = On |
![]() |
Control setpoint | 5 – 99°C |
![]() |
Supply water temperature | 5 – 99°C |
![]() |
Return water temperature | 5 – 99°C |
![]() |
Max. supply water temperature | 5 – 99°C |
![]() |
Hot water temperature | 5 – 99°C |
![]() |
Hot water setpoint | 5 – 99°C |
![]() |
Actual power | 0 – 99% |
![]() |
Water pressure | 0.0 – 9.9 |
![]() |
OTC control | 0 = Off, 1 = On |
![]() |
OTC curve | 4 – 40 (16) |
![]() |
Room compensation | 0 = Off, 1 = On |
Troubleshooting
What’s happening? | What it could mean… | How to fix it… |
Thermostat display is blank | No power to heating system | Check heating system is powered |
Faulty wiring connection | Check wiring at thermostat and boiler terminals | |
Display =![]() ![]() ![]() |
Faulty temperature sensor | Replace thermostat or check wiring to remote temperature sensor if fitted |
Thermostat shows heat demand![]() but boiler doesn’t respond |
Boiler (water) already at temperature | Normal behavior – wait for water temperature to drop |
Faulty wiring connection | Check wiring at thermostat and boiler terminals |
Conforms to protection requirements of the following directives:
EMC: 2014/30/EU and LVD: 2014/35/EU
ErP: Class VI (+4%), (EU) 811/2013
WEEE Directive 2012/19/EC – Waste Electrical and Electronic Equipment directive
At the end of the product life dispose of the packaging and product in a corresponding recycling centre. Do not dispose of the unit with the usual domestic refuse. Do not burn the product.
Honeywell Control Systems Ltd.
Skimped Hill Lane,
Cracknell,
Berkshire
RG12 1EB
www.honeywelluk.com
Manufactured for and on behalf of the Environmental & Energy Solutions
Division of Honeywell Technologies Sàrl, ACS-E&ES, Z.A., La Pièce 16,
1180 Rolle, Switzerland by its Authorised Representative Honeywell Inc.
© 2016 Honeywell International Inc. | Printed in UK