Haiwell-logo

Haiwell A04AI Series Card-type PLC Analog Module

Haiwell A04AI Series Card-type PLC Analog Module-fig1

Product Information

The Haiwell A Series Card-type PLC – Analog Module is a device that provides analog input and output capabilities to the host PLC.
The product has five different models – A04AI, A04AO, A04XA, A08AI, and A08A0. The product dimensions are 25*95*65 mm, and it requires a DC power supply of 24VDC -15%~+20%. The analog input (AI) specification includes voltage input and current input with an input range of 0V~+10V, 0V~+5V, 1V~+5V, 0~20mA, and 4~20mA. The
maximum allowed input is 13V for voltage input and 30mA for current input. The range of digital value is 0-32000 for all input types. The response time is 2.0ms/ch, and the resolution is 16 bits.

Product Usage Instructions

To use the Haiwell A Series Card-type PLC – Analog Module, follow the below instructions:

  1. Connect the module to the host PLC parallel port.
  2. Ensure that the power supply voltage is within the required range (24VDC -15%~+20%).
  3. Connect the analog input devices to the module’s analog input terminals.
  4. Configure the module’s analog input settings based on the input device specifications.
  5. Monitor the module’s communication status using the LINK indicator.
  6. If the LINK indicator shows abnormal status, refer to the user manual for troubleshooting steps.Refer to the user manual for detailed instructions on configuring and using the Haiwell A Series Card-type PLC – Analog Module.

Analog Module User Manual & Application Cases

Haiwell A04AI Series Card-type PLC Analog Module-fig2

Product Model List and Dimension

Model Power (24V) Dimension
A04AI DC24V~0.1A MAX  

 

25*95*65 mm

A04AO DC24V~0.1A MAX
A04XA DC24V~0.1A MAX
A08AI DC24V~0.1A MAX
A08A0 DC24V~0.15A MAX

Haiwell A04AI Series Card-type PLC Analog Module-fig3

1. Indicator 8. Module extension port
2. PWR power indicator, LINK module communication indicator 9. 35mm DIN guide rail track
3. Terminal definition
4. Removable terminal
5. Guide rail buckle
6. Module lock buckle
7. Module positioning hole

Indicator Description

  1. PWR: power indicator. green, constant light -Power normal; Not light – Power abnormal.
  2. LINK: multi-status indicator . three colors (Red. Yellow. Green), as follow:
    Reference processing mode Module bus state LINK indicator state
     

    Normal

    No communication of module No light
    MPU has identified the module but no communication Constant light in green
    Serial or parallel port in communication Green jitter: indicator on 30ms and off 30ms
    Parallel power supply not enough, must connect to external power supply Without serial or parallel port in communication Yellow flicker: indicator on 0.5s and off 0.5s
    With serial or parallel port in communication Yellow is darkened and jitter alternately: indicator off 0.5s and jitter 0.5s
    Firmware upgrade failed, reupgrade the module firmware Without serial or parallel port in communication Red flicker: indicator on 0.5s and off 0.5s
    With serial or parallel port in communication Red is darkened and jitter alternately: indicator off 0.5s and jitter 0.5s
    Hardware failure and maintenance Without serial or parallel port in communication Constant light in red

Power Supply Specification

Item DC Power Supply
Power supply voltage 24VDC     -15%~+20%
Power supply frequency ——
Instantaneous surge MAX 20A 1.5ms @24VDC
Power loss time 10ms or less
Fuse 0.3A, 250V
24V Output voltage (for input and expansion) None
Isolation Type No Electrical isolation
Power Protection DC input power polarity reverse, over voltage protection

Environmental Specifications for Product

Item Environment Specification
Temperature/Humidity Operating temperature:0~+55℃ Storage temperature:-25~+70℃ Humidity: 5~95%RH, No condensation
Vibration Resistance 10~57 HZ, amplitude=0.075mm, 57HZ~150HZ acceleration=1G, 10 times each for X-axis, Y-axis and Z-axis
Impact Resistance 15G, duration=11ms, 6 times each for X-axis, Y-axis and Z-axis
Interference Immunity DC EFT:±2500V      Surge:±1000V
Over Voltage Resistance 1500VAC/1min between AC terminal and PE terminal, 500VAC/1min between DC terminal and PE terminal
Insulation Impedance Between AC terminal and PE terminal @500VDC,>=5MΩ ,all input/output points to PE terminal @500VDC
Operating environment Avoid dust, moisture, corrosion, electric shock and external shocks

Analog Input (AI) Specification

Properties Voltage input Current input
Input range 0V~+10V 0V~+5V 1V~+5V 0~20mA 4~20mA
Max. allowed input 13V 30mA
Range of digital value 0-32000 0-32000 0-32000 0-32000 0-32000
Input impedance 6MΩ 250Ω
Response time 2.0ms/ch
Resolution 16 bits
 

Basic error

Room temperature

25±5℃

±0.20%
Full temperature range ±0.5%
 

Linearity error

Room temperature

25±5℃

±0.10%
Full temperature range ±0.10%
Status display If the channel is normal, the indicator light will be on.
Diagnostics function If disconnection or limit-exceeding (≥110%FS) is detected, the indicator light will be off.
Isolation Isolation between an analog circuit and a digital circuit No isolation between channels
Power supply 24VDC ±20%,200mA(Max.)
Notices:

1.   If the input signal exceeds the input range, the digital value will be 32000.

2.   If If the input signal exceeds the maximum allowed voltage or current, the channel might be damaged.

3.   It is not allowed to connect the wire inversely.

Analog Output (AQ) Specification

Properties Voltage output Current output
Output range 0V~ +10V 0V~+5V 1V~+5V 0~20mA 4~20mA
Range of digital value 0-32000 0-32000 0-32000 0-32000 0-32000
Load impedance 1KΩ@10V ≥500Ω@ 10V ≤500Ω
Response time 3.0ms/ch
Resolution 12 bits
 

Basic error

Room temperature

25±5℃

±0.30%
Full temperature range ±0.60%
 

Linearity error

Room temperature

25±5℃

±0.20%
Full temperature range ±0.20%
Status display If the channel is normal, the indicator light will be on.
Isolation Isolation between an analog circuit and a digital circuit No isolation between channels
Power supply 24VDC ±20%,200mA(Max.)
Properties Voltage output Current output
Notices:

1.   If the load doesn’t meet the requirement, the accuracy of output might be effected.

2.   If there is short-circuit or voltage backflow, the channel might be damaged.

Analog Input (AI) Wiring Diagram

Haiwell A04AI Series Card-type PLC Analog Module-fig4

Analog Output (AQ) Wiring Diagram

Haiwell A04AI Series Card-type PLC Analog Module-fig5

Terminal Diagram

Haiwell A04AI Series Card-type PLC Analog Module-fig6

Module Parameter Table

4- channel analog module parameter table
Note: CR code is corresponding to the Modbus register address, the ray parts are read-only ,the white parts are readable and writable.

CR code Function Description
A04AI A04AO A04XA
00H Low byte for module code, and high byte for module version number.
01H Communication address
 

CR code

Function Description
A04AI A04AO A04XA
 

02H

Communication protocol: The low 4-bit of the low byte: 0 – N,8,2 For RTU, 1 – E,8,1 For RTU, 2 – O,8,1 For RTU, 3 – N,7,2 For ASCII, 4 – E,7,1 For ASCII, 5 – O,7,1 For ASCII, 6 – N,8, 1 For RTU

The high 4-bit of the low byte: 0 – 2400, 1 – 4800, 2 – 9600, 3 – 19200, 4 – 38400, 5 – 57600, 6 – 115200

03H~06H Module name
07H~08H Default IP address: 192.168.1.111
09~0AH Reserve
0BH High byte subnet mask (b3~b0,1 indicates 255, 0 indicates 0, for example subnet mask 255.255.255.0, b3~b0=1110), low byte reserved
0CH-0EH Reserve
0FH Error code: 0-Normal, 1-Illegal firmware identity, 2-Incomplete firmware, 3-System data access exception, 4-No external 24V power supply
10H channel 1 input value channel 1 output value input channel 1 input value
11H channel 2 input value channel 2 output value input channel 2 input value
12H channel 3 input value channel 3 output value input channel 1 signal type, note 2
13H channel 4 input value channel 4 output value input channel 2 signal type, note 2
14H channel 1 signal type, note 2 channel 1 signal type, note 2 Use the engineering value mark, note 6
15H channel 2 signal type, note 2 channel 2 signal type, note 2 input channel 1 engineering lower limiting value
16H channel 3 signal type, note 2 channel 3 signal type, note 2 input channel 2 engineering lower limiting value
17H channel 4 signal type, note 2 channel 4 signal type, note 2 input channel 1 engineering upper limiting value
18H Use the engineering value mark, note 6 Use the engineering value mark, note 6 input channel 2 engineering upper limiting value
19H channel 1 engineering lower limiting value channel 1 engineering lower limiting value input channel 1 sampling frequency, note 1
1AH channel 2 engineering lower limiting value channel 2 engineering lower limiting value input channel 2 sampling frequency, note 1
1BH channel 3 engineering lower limiting value channel 3 engineering lower limiting value input channel 1 zero point correction value
1CH channel 4 engineering lower limiting value channel 4 engineering lower limiting value input channel 2 zero point correction value
1DH channel 1 engineering upper limiting value channel 1 engineering upper limiting value Channel 1~2 input disconnection alarm, note 5
1EH channel 2 engineering upper limiting value channel 2 engineering upper limiting value output channel 1 output value
1FH channel 3 engineering upper limiting value channel 3 engineering upper limiting value output channel 2 output value
20H channel 4 engineering upper limiting value channel 4 engineering upper limiting value output channel 1 signal type, note 2
21H channel 1 sampling frequency, note 1 power-off output mark, note 8 output channel 2 signal type, note 2
22H channel 2 sampling frequency, note 1 channel 1 power-off output value Use the engineering value mark, note 6
23H channel 3 sampling frequency, note 1 channel 2 power-off output value output channel 1 engineering lower limiting value
24H Channel 4 sampling frequency, note 1 channel 3 power-off output value output channel 2 engineering lower limiting value
25H channel 1 zero point correction value channel 4 power-off output value output channel 1 engineering upper limiting value
26H channel 2 zero point correction value Channel indicator status, note 7 output channel 2 engineering upper limiting value
27H channel 3 zero point correction value Reserve power-off output mark, note 8
28H channel 4 zero point correction value output channel 1 power-off output value
29H Channel 1~4 input disconnection alarm, note 5 output channel 2 power-off output value
2AH Reserve output channel indicator, note 7
2BH~2FH Reserve

channel analog module parameter table
Note: CR code is corresponding to the Modbus register address, the gray parts are read-only, the white parts are readable and writable.

CR code Function description
A08AI A08AO A08XA
00H Low byte for module code, and high byte for module version number.
01H Communication address
 

02H

Communication protocol: The low 4-bit of the low byte: 0 – N,8,2 For RTU, 1 – E,8,1 For RTU, 2 – O,8,1 For RTU, 3 – N,7,2 For ASCII, 4 – E,7,1 For ASCII, 5 – O,7,1 For ASCII, 6 – N,8, 1 For RTU

The high 4-bit of the low byte: 0 – 2400, 1 – 4800, 2 – 9600, 3 – 19200, 4 – 38400, 5 – 57600, 6 – 115200

 

CR code

Function description
A08AI A08AO A08XA
03H~06H Module name
07H~08H Default IP address: 192.168.1.111
09~0AH Reserve
0BH High byte subnet mask (b3~b0,1 indicates 255, 0 indicates 0, for example subnet mask 255.255.255.0, b3~b0=1110), low byte reserved
0CH~0EH Reserve
0FH Error code: 0-Normal, 1-Illegal firmware identity, 2-Incomplete firmware, 3-System data access exception, 4-No external 24V power supply
10H channel 1 input value channel 1 output value input channel 1 input value
11H channel 2 input value channel 2 output value input channel 2 input value
12H channel 3 input value channel 3 output value input channel 3 input value
13H channel 4 input value channel 4 output value input channel 4 input value
14H channel 5 input value channel 5 output value input channel 1 signal type, note 2
15H channel 6 input value channel 6 output value input channel 2 signal type, note 2
16H channel 7 input value channel 7 output value input channel 3 signal type, note 2
17H channel 8 input value channel 8 output value input channel 4 signal type, note 2
18H channel 1 signal type, note 2 channel 1 signal type, note 2 Use the engineering value mark, note 6
19H channel 2 signal type, note 2 channel 2 signal type, note 2 input channel 1 engineering lower limiting value
1AH channel 3 signal type, note 2 channel 3 signal type, note 2 input channel 2 engineering lower limiting value
1BH channel 4 signal type, note 2 channel 4 signal type, note 2 input channel 3 engineering lower limiting value
1CH channel 5 signal type, note 2 channel 5 signal type, note 2 input channel 4 engineering lower limiting value
1DH channel 6 signal type, note 2 channel 6 signal type, note 2 input channel 1 engineering upper limiting value
1EH channel 7 signal type, note 2 channel 7 signal type, note 2 input channel 2 engineering upper limiting value
1FH channel 8 signal type, note 2 channel 8 signal type, note 2 input channel 3 engineering upper limiting

value

20H Use the engineering value mark, note 6 Use the engineering value mark, note 6 input channel 4 engineering upper limiting value
21H channel 1 engineering lower limiting value channel 1 engineering lower limiting value input channel 1 sampling frequency, note 1
22H channel 2 engineering lower limiting value channel 2 engineering lower limiting value input channel 2 sampling frequency, note 1
23H channel 3 engineering lower limiting value channel 3 engineering lower limiting value input channel 3 sampling frequency, note 1
24H channel 4 engineering lower limiting value channel 4 engineering lower limiting value input channel 4 sampling frequency, note 1
25H channel 5 engineering lower limiting value channel 5 engineering lower limiting value input channel 1 zero point correction value
26H channel 6 engineering lower limiting value channel 6 engineering lower limiting value input channel 2 zero point correction value
27H channel 7 engineering lower limiting value channel 7 engineering lower limiting value input channel 3 zero point correction value
28H channel 8 engineering lower limiting value channel 8 engineering lower limiting value input channel 4 zero point correction value
29H channel 1 engineering upper limiting value channel 1 engineering upper limiting value Channel 1~4 input disconnection alarm, note 5
2AH channel 2 engineering upper limiting value channel 2 engineering upper limiting value output channel 1 output value
2BH channel 3 engineering upper limiting value channel 3 engineering upper limiting value output channel 2 output value
2CH channel 4 engineering upper limiting value channel 4 engineering upper limiting value output channel 3 output value
2DH channel 5 engineering upper limiting value channel 5 engineering upper limiting value output channel 4 output value
2EH channel 6 engineering upper limiting value channel 6 engineering upper limiting value output channel 1 signal type, note 2
2FH channel 7 engineering upper limiting value channel 7 engineering upper limiting value output channel 2 signal type, note 2
30H channel 8 engineering upper limiting value channel 8 engineering upper limiting value output channel 3 signal type, note 2
31H channel 1 sampling frequency, note 1 power-off output mark output channel 4 signal type, note 2
32H channel 2 sampling frequency, note 1 channel 1 power-off output value Use the engineering value mark, note 6
33H channel 3 sampling frequency, note 1 channel 2 power-off output value output channel 1 engineering lower limiting value
34H channel 4 sampling frequency, note 1 channel 3 power-off output value output channel 2 engineering lower limiting value
 

CR code

Function description
A08AI A08AO A08XA
35H channel 5 sampling frequency, note 1 channel 4 power-off output value output channel 3 engineering lower limiting value
36H channel 6 sampling frequency, note 1 channel 5 power-off output value output channel 4 engineering lower limiting value
37H channel 7 sampling frequency, note 1 channel 6 power-off output value output channel 1 engineering upper limiting value
38H channel 8 sampling frequency, note 1 channel 7 power-off output value output channel 2 engineering upper limiting value
39H channel 1 zero point correction value channel 8 power-off output value output channel 3 engineering upper limiting value
3AH channel 2 zero point correction value Channel indicator status output channel 4 engineering upper limiting value
3BH channel 3 zero point correction value Reserve power-off output mark
3CH channel 4 zero point correction value output channel 1 power-off output value
3DH channel 5 zero point correction value output channel 2 power-off output value
3EH channel 6 zero point correction value output channel 3 power-off output value
3FH channel 7 zero point correction value output channel 4 power-off output value
40H channel 8 zero point correction value output channel indicator
41H Channel 1~8 input disconnection alarm, note 5 Reserve
42H~4FH Reserve

Note

  • Sampling frequency:0 – 2 times, 1 – 4 times, 2 – 8 times, 3 – 16 times, 4 – 32 times, 5 – 64 times, 6 – 128 times, 7 – 256 times
  • Signal type: 0 – [4,20]mA, 1 – [0,20]mA, 2 – [1,5]V, 3 – [0,5]V, 4 – [0,10]V
  • Disconnection alarm: Each bit indicates 1 channel, 0-normal, 1-disconnection
  • Use the engineering value mark: Each bit indicates 1 channel, 0-No, 1-Yes
  • Channel indicator status:Each bit indicates 1 channel, 0-off, 1-on
  • Power-off output mark:Each bit indicates 1 channel, 0-No, 1-Yes

Mounting and installation

The PLC should be secured to an enclosed cabinet while mounting. For heat dissipation, make sure to provide a minimum clearance of 50mm between the unit and all sides of the cabinet. (See the figure.)
Rail Mounting: Use standard 35 mm rail.

Connecting Extended Module
Join lower right parallel interface of Last module (Host or Extension Module ) to the lower right of the parallel interface of next module, then tight with two buckles on top and bottom.
The interface of the right side module is left for extension interface for next extension module.

Haiwell A04AI Series Card-type PLC Analog Module-fig7

Analog Module Application Case

  1. Expand module through the host PLC parallel port

Module power supply
Analog module can be the expansion module for A series PLC; When the module is directly connect to the host PLC, no need to take external power supply, the module is powered by host PLC.

The analog need’t be written any conversion program, read the analog register value directly.
For example, the host PLC AT16S0R, respectively, is expanded with three modules of A16DI, A16XDR, A04AI and A04AO from left to right, assuming the scene:

  • Analog module A04AI input channel 1, signal type is 4-20mA, used to measure the pressure, the pressure range of 0.0~3.0Mpa;
  • Analog module A04AO input channel 1, signal type is 0-10V, used to control the inverter frequency of 0.0~50.0Hz;
    First enter the PLC programming software menu bar – view – hardware configuration, in accordance with the external order of actual modules to add the module models, after added, the analog address will be automatically arranged, as shown below:Haiwell A04AI Series Card-type PLC Analog Module-fig8

Haiwell analog module need’t be written any conversion program, as for above pressure measurement, we only need to check the use of engineering value, set the lower limit value of 0 corresponding 0.0Mpa, set the upper limit value of 3000 indicating 3.000Mpa, the upper limit value 3000 hidden three decimal places can achieve magnification times and improve accuracy. Then we read the value of the analog input register AI0, if AI0 = 1234, then the actual value is 1.234Mpa.

Haiwell A04AI Series Card-type PLC Analog Module-fig9

Similarly, for the analog output, check the use of engineering value, set the lower limit value of 0 indicating 0.0Hz, set the upper limit value of 500 indicating 50.0Hz, if you want the inverter frequency output is 25.6Hz, as long as force the AQ0 value as 256 or through other logic instructions to output the AQ0 value of 256. As shown below:

Haiwell A04AI Series Card-type PLC Analog Module-fig10

Programming skills
If you want to write the alarm program that pressure exceeds the setting value,for example, when the pressure is more than 1.25Mpa, it will alarm, the program of PLC can be written as follows:

Haiwell A04AI Series Card-type PLC Analog Module-fig11

Display analog value on SCADA, HMI
If the SCADA, touch screen, text and other PC software want to display the current pressure, only need to set three decimal digits on the numerical display primitive, then the read value will be automatically reduced 1000 times in the configuration, that is the actual temperature value, for example, you can set 3 on decimal digits of Haiwell Cloud SCADA settings.

Haiwell A04AI Series Card-type PLC Analog Module-fig12

So that when the PLC read AI0 value, AI0=1234, that is the actual value of 1.234Mpa, there is no need to have data processing in PLC and configuration, only set the 3 decimal places on the numerical display primitive, then it will be automatically reduced by 1000 times, displaying value of 1.234, that is the actual value of 1.234Mpa.

when the engineering value is not used, the default code value is 0 ~ 32000
When using the engineering value, the linear transformation is specified by the lower limit and the upper limit value, and the program is automatically transformed. When the engineering value is not used, all types are unified to correspond with 0 ~ 32000 code value.The same case of pressure measurement, this time can according to the linear transformation formula: Out = (In – InDw) * (OutUp- OutDw) / (InUp- InDw) + OutDw to write the conversion program, or use the SC linear transformation instructions to calculate directly.
Haiwell analog used easily, it is recommended to check the use of engineering value, so that the analog will be very convenient without writing any program.

Module CR code application example: Read the module channel disconnection alarm
In this example, in order to read the external sensor disconnection information of A08XA module, the disconnection alarm data of A08XA module input channel 1-4 is stored in CR29, that is, 29H (hexadecimal), decimal 41. (More CR contents can be found in the software online help – hardware manual – expansion module parameters within the corresponding model). This program is as follows:

  • Slot: Position number, A08XA is the third module, so fill in 3;
  • CR: Module disconnection alarm CR41, that is, 29H (hexadecimal) = 41 (decimal), it can be directly input 41 or 0x29 into the instruction CR terminal;
  • N: Number for readings, 1 register for 16 bits, low 4 bits corresponding channel 1-4, disconnection for 1 (ON), normal for 0 (OFF).Haiwell A04AI Series Card-type PLC Analog Module-fig13

Thanks for choosing Haiwell Products, If you have any questions about our products or services, please let us know!Haiwell website: www.haiwell.com Copyright © 2005 Xiamen Haiwell Technology Co.,Ltd.

Documents / Resources

Haiwell A04AI Series Card-type PLC Analog Module [pdf] User Manual
A04AI Series Card-type PLC Analog Module, A04AI Series, Card-type PLC Analog Module, PLC Analog Module, Analog Module, Module

References

Leave a comment

Your email address will not be published. Required fields are marked *