Hager ADC906R Residual Current Operated Circuit Breaker
Product Specifications
- Model: Residual current operated circuit-breaker RCBO with switched neutral
- Current Range: 6 to 32 A
- Electrical Connection: Top or bottom supply without alteration of functions
- Mounting: DIN rail mount & Invicta panel board (excluding UK market)
Product Usage Instructions
- Installation:
This device should only be installed by a professional electrician according to local installation standards. Do not plug in or unplug the product when it is live. - Mounting:
The device can be mounted either from the top or bottom using the plastic DIN rail clip for easy dismounting. - Locking Device:
Use the locking device for the handle MZN175 to secure the device in place. - Testing:
Perform insulation resistance tests on the top terminals with the device in the OFF position without disconnecting the RCBO.
Residual current operated circuit-breaker RCBO with switched neutral 6 to 32 A
This device is to be installed only by a professional electrician or fitter according to local applicable installation standards. Do not plug in or unplug this product when it is live.
Electrical connection
This device can be supplied either from the top or bottom without any alteration of its functions (bi-directional device).
230/240 V-50Hz
Easy dismounting with the plastic DIN rail clip
Locking device for handle MZN175
RCBO 1 module suitable for DIN rail mount & Invicta panel board (excluding the UK market)
Note:
With the device in the OFF position, an insulation resistance test can be carried out on the top terminals of this product without disconnecting the RCBO.
Information
EVCS Guidance Notes
- ADC932R 32 A RCBO
- Where an ADC932R RCBO is used to supply a 7.5 kWh car charger 10 mm2 cable must be used from the RCBO to the installed vehicle charge point.
- Can only be used in a 6-way or larger enclosure for this application.
Guidance Notes for All 100 A Dual RCCB Flush Consumer Units
ADC932R 32 A RCBO is not verified in any Flush 100 A Dual RCCB consumer units for the continuous loading of a 7.5 kWh car charger and MUST not be used.
- T +33 (0)3 88 49 50 50 info@hager.com
- hager.com – 2023.11.27
- Hager Electro S.A.S., Boulevard d’Europe, B.P. 3, 67215 OBERNAI CEDEX, France – www.hager.com
FAQS
- Q: Can this device be used to supply power to a car charger?
A: Yes, when used to supply a 7.5 kWh car charger, a 10 mm2 cable must be used from the RCBO to the charge point. Ensure it is installed in a 6-way or larger enclosure for this application. - Q: Can the RCBO be used in a Flush 100 A Dual RCCB consumer unit for a car charger?
A: No, the ADC932R 32 A RCBO is not verified for continuous loading of a 7.5 kWh car charger in Flush 100 A Dual RCCB consumer units and must not be used for this purpose. - Q: How can I contact support for this product?
A: Contact Hager Electro S.A.S. at +33 (0)3 88 49 50 50 or email info@hager.com for assistance.
Documents / Resources
![]() |
hager ADC906R Residual Current Operated Circuit Breaker [pdf] Instruction Manual ADC906R Residual Current Operated Circuit Breaker, ADC906R, Residual Current Operated Circuit Breaker, Current Operated Circuit Breaker, Operated Circuit Breaker, Circuit Breaker |