PowerShield Maintenance Bypass Switch
PSMBSW10K don 6KVA ko 10KVA UPS
www.powershield.com.au
Gabatarwa
Ana amfani da PSMBSW10K azaman madaidaicin gyare-gyare na waje don samar da wutar lantarki mara katsewa ga abubuwan da aka haɗa yayin tsarin kulawar UPS, baturi.
maye gurbin da ko maye gurbin UPS. Ya dace don amfani tare da 6kVA ko 10kVA UPS.
Hawan bangon Unit
Da fatan za a duba girman PSMBSW10K na zahiri a ƙasa don shigarwar bango.
Samfurin Ƙarsheview
- UPS shigar da breaker
- Maintenance bypass canji
- Sarrafa mai haɗa siginar fitarwa
- Tashoshin fitarwa
- Tashar shigar da kayan aiki
- UPS fitarwa tashoshi
- UPS shigarwa tashoshi
- M filin sauka
Shigarwa da Aiki
Dubawa
Cire kwandon PSMBSW10K kuma duba abubuwan da ke ciki don abubuwa masu zuwa:
- PSMBSW10K PowerShield Maintenance Bypass Switch module x 1
- Jagora mai sauri x1
- Gland M25 x 3
- Gland M19 x 1
NOTE: Kafin shigarwa, da fatan za a duba sashin kuma bincika lalacewa yayin sufuri. Idan akwai wata shaida ta lalacewa ko ɓarna, kar a yi amfani da wutar lantarki ga naúrar kuma nan da nan sanar da dillali ko dillali.
Saiti na farko da Haɗin UPS da PSMBSW10K mai sauyawa module Dole ne a yi shigarwa da wayoyi daidai da dokokin / ƙa'idodin lantarki na gida kuma dole ne a gudanar da su ta hanyar ƙwararrun ma'aikata da ƙwararrun ma'aikata.
- Kebul na 6K/6KL yakamata a kimanta don ɗaukar har zuwa 40A na yanzu.
- Kebul na 10K/10KL yakamata a kimanta don ɗaukar har zuwa 63A na yanzu.
- Haɗa shigarwar Utility zuwa Tashoshin shigarwar Utility na PSMBSW10K mai sauyawa.
- Haɗa tashoshin shigarwar UPS na PSMBSW10K sauya module zuwa tashoshi na UPS.
- Haɗa tashoshin fitarwa na UPS zuwa tashar fitarwa ta UPS na PSMBSW10K sauya module.
- Haɗa tashoshi masu fitarwa na PSMBSW10K sauya module zuwa kaya.
- Haɗa tashoshin EMBS na UPS zuwa tashoshin PSMBSW10K EMBS
Haɗin UPS da Module Canjin Keɓaɓɓen Kulawa na waje
Koma ga hoton da ke ƙasa don haɗin waya:
GARGADI: Yana da mahimmanci don haɗa tashoshi na EMBS (C1, C2) akan UPS zuwa tashar EMBS (C1, C2) akan tsarin Canjawar Maintenance Bypass. Rashin yin hakan zai haifar da lalacewa ga UPS kuma ya ɓata garanti. Bincika ƙirar UPS ɗin mai amfani don aikin Rear Panel Terminal Block Pin assignment.
Aiki
Canja wurin zuwa Kewaya Mai Kulawa
Don canja wurin daga yanayin UPS zuwa kiyaye "Bypass", bi matakan da ke ƙasa:
Mataki 1:
Don canja wurin UPS zuwa yanayin ketare ta atomatik, cire maɗauran maɗauran biyun kuma cire farantin murfin gaban mai gyara sama da mai juyawa. Wannan zai saki micro-switch ta atomatik wanda ke bayan farantin murfin kulawa (kuma zai haɗa C1 zuwa C2 akan lambobi masu sauyawa da aka saba buɗewa a cikin tashoshi na EMBS).
Muhimmanci: Tabbatar cewa UPS ya canza zuwa yanayin keɓancewa a tsaye akan LCD ɗin da ke gaban panel na UPS. Idan hakan bai faru ba to kar a ci gaba.
NOTE: Dole ne a haɗa tashoshi na EMBS a kan tsarin daidai da tashoshi na EMBS akan UPS.
Mataki 2:
- Don Keɓancewa da Yanayin Gwaji - juya sauyawa zuwa matsayin "BYPASS". A cikin wannan matsayi, UPS zai ci gaba da karɓar wutar lantarki duk da haka za a ciyar da kaya daga mains. Ana iya yin gwaji a yanzu akan UPS.
- Don Keɓewa da Yanayin Warewa – kashe mai karya shigar da shigar da PSMBSW10K akan tsarin. A cikin wannan matsayi, UPS ba za ta sami wani iko ba kuma za a ba da kaya daga mains. Bayan tabbatarwa babu voltage ba a kan tashoshi da UPS za a iya amince cire daga da'irar.
Duk na'urorin lodi yanzu za a yi amfani da su kai tsaye ta hanyar mai amfani ba ta UPS ba. Bayan cire haɗin batura daga UPS, sabis da kula da kayan aikin na iya farawa.
Komawa zuwa yanayin UPS
Don canja wurin daga kiyayewa "Bypass" zuwa yanayin UPS, bi matakan da ke ƙasa:
Muhimmanci: Tabbatar cewa PSMBSW10K yana kashe farantin murfin gaba.
Mataki 1: Sake haɗa tsarin baturi kuma canza mai karya shigar da UPS kuma kunna mai karya shigar da bayanai na PSMBSW10K. UPS ɗin za ta shigar da yanayin wucewa a tsaye.
Muhimmi: Tabbatar da UPS ya kunna kuma yana cikin yanayin kewayawa a tsaye akan LCD dake gaban gaban UPS. Idan hakan bai faru ba to kar a ci gaba.
Mataki 2: Juya canjin zuwa matsayi "UPS". Duk na'urorin lodi yanzu za a yi amfani da su ta hanyar mai amfani ta hanyar UPS da ke aiki a cikin yanayin kewaye.
Mataki 3: Sauya da amintar da PSMBSW10K mai canza murfin murfin.
Mataki 4: Danna maɓallin "ON" da ke kan gaban panel na UPS. Tabbatar cewa fitarwa na UPS yana aiki ta hanyar inverter akan LCD. Duk na'urorin Load yanzu za su sami cikakken kariya ta UPS.
Ƙayyadaddun Abubuwan Abubuwan Mahimmanci
Siga | Max. | |
Mai karya shigar da bayanai | A halin yanzu | 63 A |
Voltage | 240 V | |
Canjin wucewa | A halin yanzu | 63 A |
Voltage | 690 V | |
Tashar shigarwa/fitarwa | A halin yanzu | 60 A |
Voltage | 600 V |
Takardu / Albarkatu
![]() |