GRUNDFOS KNIGHTXL Magna 3 Variable Speed Pump

GRUNDFOS-KNIGHTXL-Magna-3-Variable-Speed-Pump-product

 

INSTALLATION INSTRUCTIONS

GRUNDFOS MAGNA 3 VARIABLE SPEED PUMP WITH LOCHINVAR BOILERS FOR KNIGHTXL, FTXL, CREST, AND CREST HELLCAT

Installation and Setup Procedure

  1. Refer to the installation manual provided by the pump manufacturer to install the pump. NOTE: The boiler MUST be installed in the Primary / Secondary piping configuration. A system supply sensor MUST be installed in the Primary (building) loop. Refer to the installation and operation manual provided by the boiler manufacturer to ensure the proper system piping configuration.
  2. Reference FIG. 1 to connect wiring to the boiler’s low voltage control board on the “Boiler Pump Out” terminal:
    • Connect the (+) wire from the boiler to “In” connection on the pump 0-10V wiring terminal.
    • Connect the (-) wire from the boiler to the ground terminal on the pump 0-10V wiring terminal.
  3. Connect line voltage by supplying it directly to the pump. NOTE: This pump is not powered by the boiler. It will have its own dedicated breaker and power supply.
    For Knight and FTXL Models: Wire the boiler pump dry contacts located on the boiler’s line voltage terminal directly to the Magna 3 start/stop connection.
    For Crest and Lectrus Models: Wire a relay to the 115V boiler pump connections on the boiler’s line voltage terminal. Connect the relay to the Magna 3 start/stop connection.
    NOTE: The Magna 3 start/stop terminals have a small jumper installed. To install the wiring you must remove the jumper.
    This method of line voltage supply allows the Pump screen to stay on even when the boiler is in Standby mode. For additional information always reference the “Wiring” section in the boiler installation and operation manual.
  4. Reference Tables 1A, 1B, 1C, 1D, and 1E on this instruction sheet to determine the setpoint percentage of the pump.
  5. Follow the procedure below to apply the pump setpoint:
    • From the pump Home screen use the arrow keys to select [Setpoint].
    • Select [OK] to go to the Setpoint screen.
    • Use the arrow keys to assign a setpoint based on the information provided in FIG. 2, on page 3.
    • Select [OK] to save the setting.
    • Select the [Home] button to return to the Home screen.
  6. The pump is pre-programmed for 0-10V operation, but the boiler will require setup to control the variable speed pump. Follow the instructions for variable speed pump setup in the boiler installation manual.

GRUNDFOS-KNIGHTXL-Magna-3-Variable-Speed-Pump-

TABLE 1A – KNIGHT XL TEMPERATURE RISE APPLICATIONS
Model 20°F 25°F
GPM Magna 3 Setpoint (%) GPM Magna 3 Setpoint (%)
400 37 40-80 92% 30 40-80 75%
501 46 50-150 42% 37 50-150 83%
601 55 50-150 79% 44 50-150 67%
701 65 50-150 79% 52 50-150 64%
801 74 50-150 100% 60 50-150 69%
TABLE 1B – FTXL TEMPERATURE RISE APPLICATIONS
Model 20°F 30°F 40°F
GPM Magna 3 Setpoint (%) GPM Magna 3 Setpoint (%) GPM Magna 3 Setpoint (%)
400 38 40-80 54% N/A N/A
500 48 40-80 68% 32 40-80 45%
600 57 40-80 79% 38 40-80 53% 29 32-60 64%
725 69 40-80 88% 46 40-80 60% 34 40-80 46%
850 81 50-150 50% 55 40-80 70% 40 40-80 53%
1000 98 50-150 48% 65 40-80 67% 49 40-80 56%
TABLE 1C – CREST & CREST HELLCAT TEMPERATURE RISE APPLICATIONS
Model Boiler Connection Size 20°F 40°F 60°F
GPM FT/HD Magna 3 Setpoint GPM FT/HD Magna 3 Setpoint GPM FT/HD Magna 3 Setpoint
751 3″ 72 6.1 50-150 44% 48* 3.6 40-80 55% N/A
1000 / 1001 3″ 96 10.5 50-150 58% 48 6.6 40-80 63%
1251 3″ 120 12.6 50-150 67% 60 6.9 40-80 71% 40 4.5 40-80 52%
1500 / 1501 4″ 144 13.5 50-150 72% 72 7.7 40-80 81% 48 6.0 40-80 62%
1751 4″ 168 15.4 80-100 82% 84 8.5 50-150 51% 56 6.9 40-80 69%
2000 / 2001 4″ 192 16.6 80-100 89% 96 8.7 50-150 55% 64 6.9 40-80 74%
2500 / 2501 4″ 240 11.4 100-120 80% 120 6.2 50-150 58% 80 5.1 40-80 81%
3000 / 3001 4″ 288 13.0 100-120 89% 144 5.2 50-150 65% 96 3.8 40-80 86%
3501 4″ 224* 12.2 100-120 78% 168 6.8 50-150 72% 112 4.6 50-150 53%
4000 / 4001 4″ 256* 14.0 100-120 87% 192 8.1 80-100 75% 128 5.4 50-150 59%
5000 / 5001 6″ Not Available 240 7.9 80-100 86% 160 5.6 80-100 62%
6000 / 6001 6″ 288 8.7 100-120 87% 192 4.3 80-100 68%

*Based on 30°F Temperature Rise

TABLE 1D – KBX TEMPERATURE RISE APPLICATIONS
Model 20°F 25°F
GPM Magna 3 Setpoint (%) GPM Magna 3 Setpoint (%)
400 38 40-80 67% 30 40-80 55%
500 48 40-80 80% 38 40-80 72%
650 62 50-150 60% 50 40-80 74%
800 76 50-150 63% 61 50-150 55%
1000 96 50-150 68% 76 50-150 54%
TABLE 1E – CREST & CREST HELLCAT TEMPERATURE RISE APPLICATIONS
Model 20°F 30°F 40°F
GPM FT/HD Magna 3 Setpoint % GPM FT/HD Magna 3 Setpoint % GPM FT/HD Magna 3 Setpoint %
KEB0015 5.4 3.3 32-60 41% 3.3 3.6 32-60 42% 2.4 3.6 32-60 42%
KEB0030 11.0 3.4 32-60 43% 7.0 3.5 32-60 43% 4.7 3.6 32-60 42%
KEB0045 16.0 3.5 32-60 48% 10.8 3.5 32-60 44% 7.9 3.6 32-60 43%
KEB0060 21.9 3.7 40-80 40% 14.2 3.7 32-60 47% 10.8 3.7 32-60 45%
KEB0075 27.1 3.9 40-80 44% 18.1 3.8 32-60 52% 13.1 3.8 32-60 47%
KEB0090 32.7 4.1 40-80 47% 21.0 3.9 32-60 55% 16.0 3.9 32-60 50%
KEB0105 37.0 4.3 40-80 50% 25.7 4.0 32-60 62% 18.9 3.9 32-60 53%
KEB0120 41.6 4.4 40-80 53% 28.1 4.0 32-60 65% 20.8 3.8 32-60 55%
KEB0135 45.7 4.7 40-80 58% 31.1 4.2 32-60 70% 23.8 4.0 32-60 59%
KEB0150 52.0 5.1 40-80 62% 35.1 4.3 32-60 76% 26.1 4.3 32-60 63%

GRUNDFOS-KNIGHTXL-Magna-3-Variable-Speed-Pump- GRUNDFOS-KNIGHTXL-Magna-3-Variable-Speed-Pump-

  • Revision Notes: Revision A (ECO C14573) initial release.
  • Revision B (ECO C14859) reflects the update of Table 1A, Table 1B and other text adjustments.
  • Revision C (ECO C15375) reflects the addition of FTX Models and Table 1C.
  • Revision D (ECO C17117) reflects the addition of the system sensor note on page 1, Step 1.
  • DIR# 2000505834 Rev A (CN# 500000615) creation of TLT DIR in SAP.
  • Rev B (CN # 500000827) reflects the addition of Crest 751 – 1251 models and update of Tables 1B and 1C.
  • Revision C (PCP #3000030930 / CN# 500020087) reflects an update to Table 1C.
  • Revision D (PCP #3000036241 / CN #500024638) reflects an update to the installation of the wiring procedure on page 1.
  • Revision E (PCP #3000047451 / CN #500035320) reflects the addition of Table 1D – KBX Temperature Rise Applications on page 2.
  • Revision F (PCP #3000051890 / CN #500038865) reflects addition of the 1000 to table 1B on page 2.
  • Revision G (PCP #3000057460 / CN #500043669) reflects the addition of the Crest. Revision H (PCP #3000063036 / CN #500048969) reflects the addition of table 1E.

FAQ

  • Q: Can the pump be powered by the boiler?
    No, the pump requires its own dedicated breaker and power supply.
  • Q: How do I determine the pump setpoint?
    Refer to Tables 1A-1E on the instruction sheet to determine the setpoint percentage based on model and GPM.
  • Q: How do I save the pump setpoint? 
    After assigning the setpoint using arrow keys, select [OK] to save the setting.

Documents / Resources

GRUNDFOS KNIGHTXL Magna 3 Variable Speed Pump [pdf] Installation Guide
KNIGHTXL, KNIGHTXL Magna 3 Variable Speed Pump, Magna 3 Variable Speed Pump, Speed Pump