INSTALLATION INSTRUCTIONS
GRUNDFOS MAGNA 3 VARIABLE SPEED PUMP WITH LOCHINVAR BOILERS FOR KNIGHTXL, FTXL, CREST, AND CREST HELLCAT
Installation and Setup Procedure
- Refer to the installation manual provided by the pump manufacturer to install the pump. NOTE: The boiler MUST be installed in the Primary / Secondary piping configuration. A system supply sensor MUST be installed in the Primary (building) loop. Refer to the installation and operation manual provided by the boiler manufacturer to ensure the proper system piping configuration.
- Reference FIG. 1 to connect wiring to the boiler's low voltage control board on the “Boiler Pump Out” terminal:
- Connect the (+) wire from the boiler to "In" connection on the pump 0-10V wiring terminal.
- Connect the (-) wire from the boiler to the ground terminal on the pump 0-10V wiring terminal.
- Connect line voltage by supplying it directly to the pump.
NOTE: This pump is not powered by the boiler. It will have its own dedicated breaker and power supply.
For Knight and FTXL Models: Wire the boiler pump dry contacts located on the boiler's line voltage terminal directly to the Magna 3 start/stop connection.
For Crest and Lectrus Models: Wire a relay to the 115V boiler pump connections on the boiler's line voltage terminal. Connect the relay to the Magna 3 start/stop connection.
NOTE: The Magna 3 start/stop terminals have a small jumper installed. To install the wiring you must remove the jumper.
This method of line voltage supply allows the Pump screen to stay on even when the boiler is in Standby mode. For additional information always reference the "Wiring" section in the boiler installation and operation manual.
- Reference Tables 1A, 1B, 1C, 1D, and 1E on this instruction sheet to determine the setpoint percentage of the pump.
- Follow the procedure below to apply the pump setpoint:
- From the pump Home screen use the arrow keys to select [Setpoint].
- Select [OK] to go to the Setpoint screen.
- Use the arrow keys to assign a setpoint based on the information provided in FIG. 2, on page 3.
- Select [OK] to save the setting.
- Select the [Home] button to return to the Home screen.
- The pump is pre-programmed for 0-10V operation, but the boiler will require setup to control the variable speed pump. Follow the instructions for variable speed pump setup in the boiler installation manual.
Figure 1 Wiring Connections
A diagram illustrating wiring connections to the Grundfos Magna 3 pump's terminal block. Key terminals include:
- POWER CONNECTION
- 0-10VDC terminals: "In", "Ground", "Vcc Signal"
- 4-20mA terminals
- BMS (Building Management System) terminals
- SYSTEM PUMP
- OUTDOOR SENSOR
- SYSTEM SUPPLY SENSOR
- SYSTEM RETURN SENSOR
- BOILER PUMP OUT (for boiler signal connection)
- ALARM, CONTACTS, RUN TIME
- TANK SENSOR
- THERMOSTAT
- ENABLE
- LOUVER
- PROVING
- RELAY
- AUX SWITCH
- MODBUS, LON (communication protocols)
DETAIL A shows the 0-10V terminal block, highlighting the "In" and "Ground" connections for pump control signal. It explicitly states "REMOVE JUMPER TO INSTALL WIRING". Specifications nearby indicate "Max. 24 V DC, 22 mA, 0-10 V DC".
Figure 2 Pump Setpoint Screens
Two user interface screens are depicted:
- Setpoint Menu Screen: Shows navigation options like "Home", "Status", "Settings", "Assist". The main display shows "Setpoint" selected, with "Control mode" and "Constant curve" settings. A percentage value "100%" is prominently displayed, along with "Flow rate" (0 gpm) and "Head" (0 ft). Navigation controls include left/right arrows for selection and an "OK" button for confirmation.
- Adjust Setpoint Screen: Displays "Adjust setpoint" with the instruction "Press OK to start the setting." A percentage value "100%" is shown with up/down arrows for adjustment. "Actual value" is also displayed. Navigation buttons are labeled "Previous" and "Next", with an "OK" button for saving.
TABLE 1A - KNIGHT XL TEMPERATURE RISE APPLICATIONS
Model | 20°F | 25°F | ||
---|---|---|---|---|
GPM | Magna 3 Setpoint (%) | GPM | Magna 3 Setpoint (%) | |
400 | 37 | 40-80 92% | 30 | 40-80 75% |
501 | 46 | 50-150 42% | 37 | 50-150 83% |
601 | 55 | 50-150 79% | 44 | 50-150 67% |
701 | 65 | 50-150 79% | 52 | 50-150 64% |
801 | 74 | 50-150 100% | 60 | 50-150 69% |
TABLE 1B - FTXL TEMPERATURE RISE APPLICATIONS
Model | 20°F | 30°F | 40°F | |||
---|---|---|---|---|---|---|
GPM | Magna 3 Setpoint (%) | GPM | Magna 3 Setpoint (%) | GPM | Magna 3 Setpoint (%) | |
400 | 38 | 40-80 54% | N/A | N/A | ||
500 | 48 | 40-80 68% | 32 | 40-80 45% | 29 | 32-60 64% |
600 | 57 | 40-80 79% | 38 | 40-80 53% | 34 | 40-80 46% |
725 | 69 | 40-80 88% | 46 | 40-80 60% | 40 | 40-80 53% |
850 | 81 | 50-150 50% | 55 | 40-80 70% | 40 | 40-80 53% |
1000 | 98 | 50-150 48% | 65 | 40-80 67% | 49 | 40-80 56% |
TABLE 1C - CREST & CREST HELLCAT TEMPERATURE RISE APPLICATIONS
Model | Boiler Connection Size | 20°F | 40°F | 60°F | |||
---|---|---|---|---|---|---|---|
GPM | FT/HD Magna 3 Setpoint | GPM | FT/HD Magna 3 Setpoint | GPM | FT/HD Magna 3 Setpoint | ||
751 | 3" | 72 | 6.1 50-150 44% | 48* | 3.6 40-80 55% | N/A | |
1000/1001 | 3" | 96 | 10.5 50-150 58% | 48 | 6.6 40-80 63% | ||
1251 | 3" | 120 | 12.6 50-150 67% | 60 | 6.9 40-80 71% | 40 | 4.5 40-80 52% |
1500/1501 | 4" | 144 | 13.5 50-150 72% | 72 | 7.7 40-80 81% | 48 | 6.0 40-80 62% |
1751 | 4" | 168 | 15.4 80-100 82% | 84 | 8.5 50-150 51% | 56 | 6.9 40-80 69% |
2000/2001 | 4" | 192 | 16.6 80-100 89% | 96 | 8.7 50-150 55% | 64 | 6.9 40-80 74% |
2500/2501 | 4" | 240 | 11.4 100-120 80% | 120 | 6.2 50-150 58% | 80 | 5.1 40-80 81% |
3000/3001 | 4" | 288 | 13.0 100-120 89% | 144 | 5.2 50-150 65% | 96 | 3.8 40-80 86% |
3501 | 4" | 224* | 12.2 100-120 78% | 168 | 6.8 50-150 72% | 112 | 4.6 50-150 53% |
4000/4001 | 4" | 256* | 14.0 100-120 87% | 192 | 8.1 80-100 75% | 128 | 5.4 50-150 59% |
5000/5001 | 6" | 240 7.9 80-100 86% | 160 | 5.6 80-100 62% | |||
6000/6001 | 6" | Not Available | 288 | 8.7 100-120 87% | 192 | 4.3 80-100 68% | |
*Based on 30°F Temperature Rise |
TABLE 1D - KBX TEMPERATURE RISE APPLICATIONS
Model | 20°F | 25°F | ||
---|---|---|---|---|
GPM | Magna 3 Setpoint (%) | GPM | Magna 3 Setpoint (%) | |
400 | 38 | 40-80 67% | 30 | 40-80 55% |
500 | 48 | 40-80 80% | 38 | 40-80 72% |
650 | 62 | 50-150 60% | 50 | 40-80 74% |
800 | 76 | 50-150 63% | 61 | 50-150 55% |
1000 | 96 | 50-150 68% | 76 | 50-150 54% |
TABLE 1E - CREST & CREST HELLCAT TEMPERATURE RISE APPLICATIONS
Model | 20°F | 30°F | 40°F | |||
---|---|---|---|---|---|---|
GPM | FT/HD Magna 3 Setpoint % | GPM | FT/HD Magna 3 Setpoint % | GPM | FT/HD Magna 3 Setpoint % | |
KEB0015 | 5.4 | 3.3 32-60 41% | 3.3 | 3.6 32-60 42% | 2.4 | 3.6 32-60 42% |
KEB0030 | 11.0 | 3.4 32-60 43% | 7.0 | 3.5 32-60 43% | 4.7 | 3.6 32-60 42% |
KEB0045 | 16.0 | 3.5 32-60 48% | 10.8 | 3.5 32-60 44% | 7.9 | 3.6 32-60 43% |
KEB0060 | 21.9 | 3.7 40-80 40% | 14.2 | 3.7 32-60 47% | 10.8 | 3.7 32-60 45% |
KEB0075 | 27.1 | 3.9 40-80 44% | 18.1 | 3.8 32-60 52% | 13.1 | 3.8 32-60 47% |
KEB0090 | 32.7 | 4.1 40-80 47% | 21.0 | 3.9 32-60 55% | 16.0 | 3.9 32-60 50% |
KEB0105 | 37.0 | 4.3 40-80 50% | 25.7 | 4.0 32-60 62% | 18.9 | 3.9 32-60 53% |
KEB0120 | 41.6 | 4.4 40-80 53% | 28.1 | 4.0 32-60 65% | 20.8 | 3.8 32-60 55% |
KEB0135 | 45.7 | 4.7 40-80 58% | 31.1 | 4.2 32-60 70% | 23.8 | 4.0 32-60 59% |
KEB0150 | 52.0 | 5.1 40-80 62% | 35.1 | 4.3 32-60 76% | 26.1 | 4.3 32-60 63% |
Revision Notes
- Revision A (ECO C14573) initial release.
- Revision B (ECO C14859) reflects the update of Table 1A, Table 1B and other text adjustments.
- Revision C (ECO C15375) reflects the addition of FTX Models and Table 1C.
- Revision D (ECO C17117) reflects the addition of the system sensor note on page 1, Step 1.
- DIR# 2000505834 Rev A (CN# 500000615) creation of TLT DIR in SAP.
- Rev B (CN # 500000827) reflects the addition of Crest 751 - 1251 models and update of Tables 1B and 1C.
- Revision C (PCP #3000030930 / CN# 500020087) reflects an update to Table 1C.
- Revision D (PCP #3000036241 / CN #500024638) reflects an update to the installation of the wiring procedure on page 1.
- Revision E (PCP #3000047451 / CN #500035320) reflects the addition of Table 1D - KBX Temperature Rise Applications on page 2.
- Revision F (PCP #3000051890 / CN #500038865) reflects addition of the 1000 to table 1B on page 2.
- Revision G (PCP #3000057460 / CN #500043669) reflects the addition of the Crest.
- Revision H (PCP #3000063036 / CN #500048969) reflects the addition of table 1E.
- 10/24 - Printed in U.S.A.
Related Documents
![]() |
Grundfos DDA 12-10 FCM-C Digital Dosing Pump - Features and Specifications Detailed overview of the Grundfos SMART Digital DDA-C chemical dosing pump, including its features, operation modes, connectivity, and technical specifications. Model DDA 12-10 FCM-C-PV/T/C-F-31U2U2IG. |
![]() |
Grundfos UPM3(K) AUTO Circulation Pump - Installation and Operation Instructions Comprehensive instructions for the Grundfos UPM3(K) AUTO high-efficiency circulation pump, covering installation, operation, technical specifications, and safety guidelines. |
![]() |
Grundfos ALPHA2 L Model C Circulator Pump: Installation and Operating Instructions Comprehensive instructions for the Grundfos ALPHA2 L Model C circulator pump, covering installation, operation, safety, and technical specifications. Learn how to install and use your Grundfos pump efficiently. |
![]() |
Grundfos MI 301 : Guide d'installation et de fonctionnement Ce document fournit des instructions essentielles pour l'installation et le fonctionnement de l'interface mobile Grundfos MI 301. Il détaille les caractéristiques du produit, les options de connectivité via Bluetooth, radio et infrarouge, et propose des conseils de dépannage pour une intégration transparente avec les équipements Grundfos. |
![]() |
Grundfos CRT Installation and Operating Instructions Comprehensive guide for the installation and operation of Grundfos CRT pumps, covering technical specifications, electrical connections, maintenance, and troubleshooting. |
![]() |
Grundfos MQ Series Pressure Booster Pump Installation and Operating Instructions Comprehensive installation and operating instructions for the Grundfos MQ series pressure booster pumps, including models MQ 3-25, MQ 3-35, and MQ 3-45. This manual covers setup, operation, technical data, and troubleshooting for residential and garden water supply applications. |
![]() |
Grundfos SCALA2 3-45 A Water Booster Pump Technical Specifications Detailed technical specifications for the Grundfos SCALA2 3-45 A, a fully integrated, self-priming, compact waterworks for pressure boosting in domestic applications. Includes performance data, materials, installation, and electrical information. |
![]() |
Grundfos SCALA2 3-45: Integrated Waterworks for Domestic Pressure Boosting Detailed technical specifications and features of the Grundfos SCALA2 3-45, a self-priming, compact waterworks designed for domestic pressure boosting applications. Learn about its integrated speed control, automatic reset function, and low-noise operation. |