GREE XK76 Wired Programmable Controller
Specifications
- Product: Wired Controller XK76
- Manufacturer: Change for Life
- Model: XK76
Product Usage Instructions
Display
- Appearance
The wired controller display features symbols and buttons for various functions. Refer to the user manual for detailed information on the displayed symbols.
Buttons
- Button Graphics
The controller has buttons with specific functions. Familiarize yourself with the button graphics as shown in Fig. 2 of the manual.
Function Instructions of Buttons
- FAN: Allows setting low speed, medium speed,high speed, turbo, and auto speed.
- Set temperature: Adjust temperature settings.
- ON/OFF/BACK: Turn unit on or off and navigate back to the previous page.
- SWING: Control swing functions.
- MENU/OK: Enter menu, confirm settings.
- MODE: Set auto, cooling, dry, fan, and heating modes.
Operation Instructions
- Menu Structure
The wired controller’s main page allows direct setting of fan speed, swing, temperature, mode, and power status. Additional functions can be accessed through corresponding submenus. Refer to Fig. 3 for detailed menu structure.
FAQ
Q: How can I access the detailed menu structure on the wired controller?
A: To access the detailed menu structure, navigate to the main page of the controller and use the MENU/OK button to enter the menu page where you can find settings for various functions.
Q: What does the FAN button on the controller do?
A: The FAN button allows you to set different fan speeds including low speed, medium speed, high speed, turbo, and auto speed.
Q: How do I turn on or off the unit using the controller?
A: To turn on or off the unit, use the ON/OFF/BACK button on the controller. This button also serves to return to the previous page.
Thank you for choosing our product.
Please read this Owner’s Manual carefully before operation and retain it for future reference.
If you have lost the Owner’s Manual, please contact the local agent or visit www.gree.com or send an email to global@gree.com.cn for the electronic version.
User Notices
For correct installation and operation, please read all instructions carefully. Before reading the instructions, please be aware of the following items:
- Prohibit installing the wired controller at wet or sunshine places.
- Do not knock, throw or frequently disassemble the wired controller.
- Do not operate the wired controller with wet hands.
- Do not remove or install the wired controller by yourself. If there is any question,please contact our after-sales service center.
- The wired controller is a general model, applicable for several kinds of units. Some functions of the wired controller are not available for certain kinds of units, more details please refer to the owner’s manual of unit. The setting of such unavailable function will not affect unit’s operation.
- The wired controller is universal. The remote receiver is either in the indoor unit or in the wired controller. Please refer to the specific models.
Display
Appearance
Button Graphics
Function Instructions of Buttons
No. | Button name | Button Function |
1 | FAN |
Set low speed, medium speed,high speed, turbo and auto speed. |
2 | ∧ | (1) Set temperature
(2) Set parameter (3) Move option cursor |
6 | ∨ | |
3 | ON/OFF/BACK | (1) Turn on or turn off unit
(2) Return to last page |
4 | SWING | Set up&down swing and set left&right swing |
5 | < | (1) Set related function on or off
(2) Move option cursor (3) Set parameter |
8 | > | |
7 | MENU/OK | (1) Enter menu page
(2) Confirm setting |
9 | MODE | Set auto, cooling, dry, fan and heating modes for indoor unit. |
10 | Remote control receiver window |
Operation Instructions
Menu Structure
Normal setting of wired controller can be set directly on the main page, including fan speed, swing, set temperature, mode, ON/OFF. The setting and status view of other functions can be set in corresponding submenu. Detailed menu structure is as shown in Fig. 3.
On/Off
When the wired control is on main page, press ON/OFF button to turn on the unit. Press ON/OFF button again to turn off the unit. The interfaces of On/Off status are shown in Fig. 4 and Fig. 5.
Mode Setting
Under On status, pressing MODE button can set mode circularly as:
Note: If save function is on, auto mode is not available.
Temperature Setting
Under unit on status, pressing ”∧” or ”∨” button on the main page increases or decreases set temperature by 1℃(1℉); holding ”∧” or ”∨” button increases or decreases set temperature by 1℃(1℉) every 0.3s.
In cooling,dry,fan and heating mode,temperature setting range is 16℃~30℃ (61℉~86℉). Under auto mode, set temperature cannot be adjusted.
Fan Setting
Under On status, pressing FAN button can set fan speed circularly as:
Low→Medium→High→Turbo→Auto→Low
Symbols displayed are as shown in Fig. 6.
Swing Setting
In unit on status, press SWING button for swing setting. Two swing modes are available: fixed-angle swing and simple swing.
When fixed-angle swing mode is set, swing operation is as follows:
In unit on status, press SWING button to select up&down swing . Up&down swing angle will be adjusted circularly as below:
Select up&down swing and left&right swing through ”<” or ”>” button. When left&right swing is selected. Left&right swing angle will be adjusted circularly as below:
NOTE
- Turn on fixed-angle swing mode in function setting page;
- If fixed-angle swing is not available for the model, fixed-angle swing will be invalid when the wired controller turns on fixed-angle swing mode.
Simple swing mode: when fixed-angle swing mode is turned off, swing operation is as below:
Pressing SWING button under unit on status, up&down swing frame occurs. Then press SWING button to turn on or turn off up&down swing. is displayed when up&down swing is on and is not displayed when up&down swing is off. When up&down swing frame have not disappeared, press ”<” or ”>” button to switch to left&right swing setting. Then left&right swing frame occurs. In this case, press SWING button to turn on or turn off left&right swing.
is displayed when left&right swing is on and is not
displayed when left&right swing is off. For detailed operation, please refer to Fig. 7.
Functions Setting
Press MENU/OK button on main page to enter main menu page. Press ”∧” or ”∨”or ”<”or ”>” button to select the function setting symbol. Then press MENU/OK button to enter user function setting page. Press ”∧” or ”∨” button to select specific function item. Press ”<” or ”>” button to turn on or turn off this function. If the function item cann’t be set, it will displays with gray color. Please refer to Fig.8.
Fresh Air Function Setting
After entering user function page, press ”∧” or ”∨” button to select fresh air function and press ”<” or ”>” button to turn on or turn off air function. Press MENU button to adjust the mode of fresh air.
After entering fresh air mode setting, press ”∧” or ”∨” button to adjust the mode in the range of 1~10. After setting, press MENU button to save the setting.
Sleep Function Setting
After entering user function page, press ”∧” or ”∨”button to select sleep function and press ”<”or ”>” button to turn on or turn off sleep function with auto saving.
If this function is turned on, the unit will operate according to the preset sleep curve to provide comfortable sleep environment.
Note:
- In fan or auto mode, sleep function is not available.
- Sleep function will be cancelled when turning off the unit or switching modes.
Health Function Setting
After entering user function page, press ”∧” or ”∨” button to select health function and press ”<” or ”>” button to turn on or turn off health function with auto saving.
I-DEMAND Function Setting
After entering user function page, press ”∧” or ”∨” button to select IDEMAND function option and press ”<” or ”>” button to turn on or turn off this function with auto saving.
NOTE
- This function is only available in cooling mode.
- When this function has been set, set temperature is displayed in SE.
- In this case, temperature setting and fan speed setting are shielded.
- This function will be cancelled when switching modes.
- This function and sleep function cannot be on simultaneously. If I-demand function is set firstly and then sleep function is set, I-demand function will be cancelled while sleep function will be valid, and vice versa.
Absence Function Setting
After entering user function page, press ”∧” or ”∨” button to select holiday function option and press ”<” or ”>” button to turn on or turn off this function with auto saving.
This function is used to maintain indoor temperature so that unit can realize fast heating.
Note:
- This function is only available in heating mode.
- When this function has been set, set temperature is displayed in 8℃(46℉). In this case, temperature setting and fan speed setting are shielded.
- This function will be cancelled when switching modes.
- This function and sleep function cannot be on simultaneously. If absence function is set firstly and then sleep function is set, absence function will be cancelled while sleep function will be valid, and vice versa.
Memory Function Setting
After entering user function page, press ”∧” or ”∨” button to select memory function and press ”<” or ”>” button to turn on or turn off memory function with auto saving.
Fixed-angle Swing Mod e Setting
After entering user function page, press ”∧” or ”∨” button to select lock swing function option and press ”<” or ”>” button to turn on or turn off this function with auto saving.
NOTE
If fixed-angle swing function is not available for the connected unit, this function will be cancelled automatically after setting.
Save Function Setting
After entering user function page, press ”∧” or ”∨” button to select save function and press ”<” or ”>”button to turn on or turn off save function. Press MENU button to enter save function setting page.
After entering save function setting page, press ”<” or ”>” button to select cooling or heating limitation temperature. After selecting cooling or heating limitation temperature, press ”∧” or ”∨” button to adjust limitation temperature value. After setting, press MENU button to save the setting.
Note: When save function has been set, auto mode cannot be set.
Auxiliary Heating Function Setting
After entering user function page, press ”∧” or ”∨” button to select auxiliary heating function and press ”<” or ”>” button to turn on or turn off this function with auto
saving.
X-fan Function Setting
After entering user function page, press ”∧” or ”∨” button to select dry function option and press ”<” or ”>” button to turn on or turn off this function with auto saving.
Note:
- This function is only available in cooling mode and dry mode.
Quiet Function Setting
After entering user function page, press ”∧” or ”∨” button to select quiet function and press ”<” or ”>” button to turn on or turn off this function with auto saving.
Note: This function is only available in cooling mode, heating mode and auto mode.
Fahrenheit Temperature Setting
After entering user function page, press ”∧” or ”∨” button to select Fahrenheit temperature function and press ”<” or ”>” button to turn on or turn off this function with auto saving. After closing this function, Celsius temperature will be displayed
Air Function Setting
After entering user function page, press ”∧” or ”∨” button to select Air Function and press ”<” or ”>” button to turn on or turn off air function. Press MENU button to adjust the mode of Air Function .
After entering Air Function mode setting, press ”∧” or ”∨” button to adjust the mode in the range of 1~2. After setting, press MENU button to save the setting.
The each mode means as follows:1- suction 2-discharge
Unit Status View
Press MENU button to enter the menu and select the function symbol to be viewed. Then press MENU button to enter view function page. Press ”∧” or ”∨” button to select status view function. Press MENU button to enter unit status view page. Press BACK button to return to the. Please refer to Fig. 9.
The following statuses can be viewed: if auxiliary heating is operating;indoor ambient temperature; outdoor ambient temperature.
Current Error View
When error occurs in the unit, error symbol will be displayed on the main page of wired controller to indicate that the unit is with error. In this case, you can enter error view page to view the current error.
Press MENU button to enter the menu and select the function symbol to be viewed. Then press MENU button to enter view function page. Press ”∧” or ”∨” button to select error information. Press MENU button to enter error view page. If there are too many errors, press ”∧” or ”∨” to turn pages. Press BACK button to return to the last page. Please refer to Fig. 10.
Error | Error
Code |
Error | Error
Code |
Return air temperature sensor open/
short circuited |
F1 | Drive board communication error | P6 |
evaporator temperature sensor open/
short circuited |
F2 | Compressor overheating protection | H3 |
Indoor unit liquid valve temperature
sensor open/short circuited |
b5 | Indoor and outdoor units unmatched | LP |
Indoor gas valve temperature sensor
open/ short circuited |
b7 | Communication line misconnected or
expansion valve error |
dn |
IPM temperature sensor open/short
circuited |
P7 | E7 | |
Outdoor ambient temperature sensor
open/ short circuited |
F3 | Pump-down | Fo |
Outdoor unit condenser mid-tube
temperature sensor open/short circuited |
F4 | Jumper error | C5 |
Discharge temperature sensor open/
short circuited |
F5 | Forced defrosting | H1 |
Indoor and outdoor communication error | E6 | Compressor startup failure | Lc |
DC bus under-voltage protection | PL | High discharge temperature protection | E4 |
DC bus over-voltage protection | PH | Overload protection | E8 |
Compressor phase current sensing
circuit error |
U1 | Whole unit over-current protection | E5 |
Compressor demagnetization protection | HE | Over phase current protection | P5 |
PFC protection | Hc | Compressor desynchronizing | H7 |
IPM Temperature Protection | P8 | IPM Current protection | H5 |
Over-power protection | L9 | Compressor phase loss/reversal
protection |
Ld |
System charge shortage or blockage
protection |
FO | Frequency restricted/reduced with whole
unit current protection |
F8 |
Capacitor charging error | PU | Frequency restricted/reduced with IPM
current protection |
En |
High pressure protection | E1 | Frequency restricted/reduced with high
discharge temperature |
F9 |
Low pressure protection | E3 | Frequency restricted/reduced with anti-
freezing protection |
FH |
Compressor stalling | LE | Frequency restricted/reduced with
overload protection |
F6 |
Over-speeding | LF | Frequency restricted/reduced with IPM
temperature protection |
EU |
Drive board temperature sensor error | PF | Indoor unit full water error | E9 |
AC contactor protection | P9 | Anti-freezing protection | E2 |
Temperature drift protection | PE | AC input voltage abnormal | PP |
Sensor connection protection | Pd | Whole unit current sensing circuit error | U5 |
DC bus voltage drop error | U3 | 4-way valve reversing error | U7 |
Outdoor fan 1 error protection | L3 | Motor stalling | H6 |
Outdoor fan 2 error protection | LA | PG motor zero-crossing protection | U8 |
compressor inhalation temperature sensor error | dc | Indoor fan tripping error | UO |
Communication error between IOU and grid connection | Ln | IOU network address error | y3 |
Communication error between OOU and grid connection | LM | Ip address allocation overflow | yb |
Main error at grid connection side | y2 |
Timer Setting
The wired controller can set 6 kinds of timer: one time clock timer, everyday timer, one week timer, two week timer, countdown timer on and countdown timer off. Select timer symbol after entering menu page. Press MENU button to enter timer setting page. Press ”∧” or ”∨” button to select one kind of timer. Press ”<” or ”>” button to turn on or turn off this timer. Please refer to Fig. 11.
One Time Clock Timer
The wired controller can set one time clock timer. If the unit is off, timer on can be set. If the unit is on, timer off can be set. This timer will be carried out for only once when timer time is reached and then the timer will be off automatically.
In timer function setting page, when one time timer is selected, press ”<” or ”>” button to turn on or turn off this timer function. Press MENU button to enter timer time setting page, as shown in Fig. 12.
Press ”<” or ”>” button to select timer hour or minute and press ”∧” or ”∨” button to adjust time. Holding ”∧” or ”∨” button increases or decreases time rapidly. After finishing setting, press MENU button to save timer time.
Note: If this timer function is turned on, when the unit is turned on or turned off, this timer function will be cancelled automatically.
Daily Timer
In daily timer, user can set eight segments of timer individually. The individual segment will be valid only when it is turned on. In each segment, you can set time, unit ON/OFF, set temperature in cooling (it is valid only when the current mode is cooling), set temperature in heating (it is valid only when the current mode is heating). Please refer to Fig. 13. to select setting
After entering daily timer setting page, press ”<” or ”>” button item. Press ”∧” or ”∨” button to adjust the value. Press MENU button to save setting.
Weekly Timer
The user can set the everyday timer content for a week. In each day, the user can set eight segments of timer content. The unit will execute corresponding timer setting in a week.
After entering weekly timer setting page, press ”<” or ”>” button to select the day to be set. Then press MENU button to enter timer programming of that day. Press ”<” or ”>” button to select the item to be set. Press ”∧” or ”∨” button to adjust the content. Press MENU button to save setting. Please refer to Fig. 14.
Two Week Timer
The user can set the everyday timer content for two weeks. In each day, the user can set eight segments of timer content. The unit will execute corresponding timer setting in two weeks.
In timer function setting page, press ”∧” or ”∨” button to select two week timer setting and then press MENU button to enter two week timer menu page. Press ”∧” or ”∨” button to select current week option and then press ”<” or ”>” button to set current week as first week or second week Press MENU button to save current week setting.
Please refer to Fig. 15.
After entering two week timer menu page, press ”∧” or ”∨” button to select the two week schedule option and then press MENU button to enter two week timer programming. After entering two week timer setting page, press ”<” or ”>” button to select the day to be set. Then press MENU button to enter timer programming of that day. Press ”<” or ”>” button to select the item to be set. Press ”∧” or ”∨” button to adjust the content. Press MENU button to save setting. Press BACK button to exit this page. The setting symbols please refer to weekly timer setting.
Countdown Timer
Countdown timer includes timer on and timer off. Unit On/Off after a desired hour can be set. In unit on status, timer off can be set, or timer off and timer on can be set simultaneously. In unit off status, timer on can be set, or timer off and timer on can be set simultaneously. If timer off in x hours and timer on in y hours are set simultaneously in unit on status, the unit will be off in x hours and then the unit will be on in y hours after timer off.
After entering timer on setting page, press ”∧” or ”∨” button to increases or decreases timer time by 0.5h. Press MENU button to save setting. Press BACK button to return to the last page. Please refer to Fig. 16.
After entering timer off setting page, press ”∧” or ”∨” button to increases or decreases timer time by 0.5h. Press MENU button to save setting. Press BACK button to return to the last page. Please refer to Fig. 17.
If timer function is on, the set hours will decrease as the unit operation time increases. In this case, residual hours can be viewed after entering timer setting page.
This timer function will be carried out for only once and then it will be cancelled automatically.
Note: If this timer function is turned on, when the unit is turned on or turned off, this timer function will be cancelled automatically.
Clock Setting
Time Format Setting
The user can set the time format in 12-hour system or 24-hour system. Select clock symbol in menu page and then press MENU button to enter clock setting page. Press ”∧” or ”∨” button to select time format and then press ”<” or ”>” button to select 1 2-hour system or 24-hour system. Please refer to Fig. 18.
Clock Setting
Select clock symbol in menu page and then press MENU button to enter clock setting page. Press ”∧” or ”∨” button to select time set and then press MENU button to enter time setting.
Press ”<” or ”>” button to select setting items: hour, minute, year, month, day; press”∧” or ”∨” button to set the value and then press MENU button to save setting. Please refer to Fig. 19.
Note: If you need to use both the wired controller and remote controller, please set the time of them identically.
Lock Setting
Select lock symbol in menu page and then press MENU button to enter lock setting page. Press ”∧” or ”∨” button to select the item to be locked and then press ”<” or ”>” button to lock or unlock. Please refer to Fig. 20.
Items can be locked: ON/OFF, mode setting, temperature setting, fan speed setting, key lock. After locking, the corresponding item cannot be set through buttons.
If the keys are locked, all keys cannot be operated after returning to the main page. Please unlock according to the instructions on main page. During unlocking, press MENU button, press ”<” button and then press ”>” button to unlock keys.
Installation Instructions
Parts and Dimension of Wired Controller
Installation Requirements
- Prohibit installing the wired controller at wet places.
- Prohibit installing the wired controller at the places with direct sunshine.
- Prohibit installing the wired controller at the place near high temperature objects or water-splashing places.
Installation Methods
Fig. 23 is the simple installation process of wired controller; please pay attention to the following items:
- Before installation, please cut off the power for indoor unit;
- Pull out the four-core twisted pair line from the installation holes and then let it go through the rectangular hole behind the soleplate of the wired controller.
- Stick the soleplate of wired controller on the wall and then use screw M4×25 to fix soleplate and installation hole on wall together, attach the sponge 20×20×3 at the screw hole and then press it with fingers to make sure it’s attached firmly.
- Insert the four-core twisted pair line into the slot of the wired controller and then buckle the front panel and the soleplate of the wired controller together.
- Block the four-core wire into the groove at the left side of wiring column; bundle the front panel of wired controller to its soleplate.
Note:
- Separate the signal and communication lines of the wired controller from the power cord and connection lines between the indoor and outdoor unit, with a minimum interval of 20cm, otherwise the communication of the unit will probably work abnormally.
- If the air conditioning unit is installed where is vulnerable to electromagnetic interference,then the signal and communication lines of the wired controller must be the shielding twisted pair lines.
- The 4-core terminal connects the air conditioner, while the 2-core terminal connects the centralized controller. The connecting method for the 2-core connection wire is same as that of 4-core connection wire.
- No need to set the wire of wired controller into the clasp.
For matching with different models, the patch cord and the connection wire are provided in the packaging box of wired controller. As shown in fig. A.
- If the air conditioner has been installed with the patch cord (f ig . C ) used for connecting the wired controller.
Only use the connection wire (fig. B) in the packing box of wired controller. Connect the terminal ② to the terminal ④ of patch cord which has been installed on the air conditioner; insert terminal ① to needle stand CN2 of wired controller. If there’s protection terminal ③, pull out the protection terminal at first and then install it. - If the air conditioner hasn’t been installed with the patch cord used for connecting the wired controller.
Use the connection wire and patch cord in the packing box of wired controller. Pull out the protection terminal of patch cord at first, connect the connection wire with the patch cord according to fig. D, and then insert the terminal ① of connection wire into the needle stand CN2 of wired controller and insert the terminal ⑤ of patch cord into the terminal of wired controller of air conditioner as well.
Disassembly
GREE ELECTRIC APPLIANCES, INC. OF ZHUHAI
Add: West Jinji Rd, Qianshan, Zhuhai,Guangdong, China, 519070
Tel: (+86-756) 8522218
Fax: (+86-756) 8669426
E-mail: gree@gree.com.cn www.gree.com
Documents / Resources
![]() |
GREE XK76 Wired Programmable Controller [pdf] Owner's Manual 81001021, XK76, XK76 Wired Programmable Controller, XK76, Wired Programmable Controller, Programmable Controller |