TECHNICAL SPECIFICATIONS

KG7T (A and K Series) Two-Stage, Fixed Speed

  • High Efficiency Upflow/Horizontal and Downflow Gas Furnaces
  • Induced Draft – 80+ AFUE
  • Input 60,000 – 140,000 Btuh
  • The high-efficiency gas furnace may be installed free-standing in a utility room, or basement, or enclosed in an alcove or closet.
  • The rounded corner jacket provides a pleasing “appliance appearance.” Design certified by CSA for application in the United States and Canada.

FEATURES and BENEFITS

  • 100% fired and tested: All units and each component are tested on the manufacturing line.
  • Best packaging in the industry: Unique corner post design assures the product will arrive at the homeowner dent-free.
  • Low Boy Height: Easy to apply in low ceiling applications, works well with taller high SEER coils, easier to handle and install.
  • Tubular primary heat exchanger: Heavy gauge aluminized steel heat exchanger assures a long life.
  • 30-second blower delay at start-up: Assures a warm duct temperature at furnace start-up. Adjustable blower-off settings (60, 90, 120, and 180 seconds).
  • 30-second post purge: Increases the life of the heat exchanger.
  • Hot surface ignitor: Innovative application of an appliance-type ignitor with a 20-year history of reliability. Utilizes proven Smartlite® technology.
  • Color-coded wire harness: Designed to fit the components, all with quick-connect fittings for ease of service and replacement.
  • High static blowers: All models are equipped with high static blowers.
  • 90-second cooling cycle blower-off delay (TDR): increases cooling performance when matched with a Nortek Global HVAC coil.
  • Flexible category I venting system: This may be vented with the dedicated venting system or commonly vented with other category one appliances.
  • Variable speed blower kit: Upgradable to full variable speed with the kit.
  • LP convertible: Simple burner orifice and regulator spring change for ease of convertibility.
  • Diagnostic lights for easy troubleshooting without counting flashes: Dedicated light for flame signal strength and 2 lights in combination to indicate all other fault codes with easy to recognize states without counting flashes.
  • Integrated control board: Incorporates connections for electronic air cleaner and humidifier.
  • Two-piece door design: Enhances furnace appearance and uses captured screws to prevent losing door screws.
  • Energy Efficient Brushless DC (ECM) Motor: Gives up to 1 SEER point efficiency gain in cooling.
  • Furnace Air Leakage: These furnaces comply with the Energy Star cabinet air leakage requirement of less than or equal to 2%. Keep the conditioned air flowing to where it’s needed.

GAS FURNACE COMPONENTS

Gibson-KG7T-Two-Stage-Fixed-Speed-High-Efficiency-Upflow-Horizontal-and-Downflow-Gas-Furnaces-FIG-1

Upflow/Horizontal Gas FurnaceGibson-KG7T-Two-Stage-Fixed-Speed-High-Efficiency-Upflow-Horizontal-and-Downflow-Gas-Furnaces-FIG-2

DIMENSIONS

*TA Model #’s Dimension “A” Dimension “B” Dimension “C” Dimension “D”
060-23A1 14 1/4 10 3/4 12 5/8 12 7/8
080-24B1 17 1/2 11 3/4 15 7/8 16 1/8
100-24B1
100-35C1  

21

 

14

19 3/8 19 5/8
120-35C1
140-45D1 24 1/2 15 1/4 22 7/8 23 1/8

Gibson-KG7T-Two-Stage-Fixed-Speed-High-Efficiency-Upflow-Horizontal-and-Downflow-Gas-Furnaces-FIG-3 Gibson-KG7T-Two-Stage-Fixed-Speed-High-Efficiency-Upflow-Horizontal-and-Downflow-Gas-Furnaces-FIG-4

KG7TA 80+ High-Efficiency Upflow/Horizontal Series

*TK Model #’s Dimension “A” Dimension “B” Dimension “C” Dimension “D”
060-23A1 14 1/4 10 3/4 12 5/8 12 7/8
080-24B1 17 1/2 11 3/4 15 7/8 16 1/8
100-24B1
100-35C1  

21

 

14

19 3/8 19 5/8
120-35C1
140-45D1 24 1/2 15 1/4 22 7/8 23 1/8

Gibson-KG7T-Two-Stage-Fixed-Speed-High-Efficiency-Upflow-Horizontal-and-Downflow-Gas-Furnaces-FIG-5 Gibson-KG7T-Two-Stage-Fixed-Speed-High-Efficiency-Upflow-Horizontal-and-Downflow-Gas-Furnaces-FIG-6

BLOWER PERFORMANCE – KG7TA/TK

G7TA/TK – 80% AFUE, Two Stage Gas Furnace
 

 

Model Number

 

Heating Input (Btuh)

Motor Switch Setting External Static Pressure (in.w.c.)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
1/5 2/6 3/7 4/8 CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise
 *TA/TK-060(C)-*A1  60000 0 0 0 0                                
1 0 0 0                                
0 1 0 0 600 555 510                      
1 1 0 0 705 670 635 600                
0 0 1 0 775 57 740 60 705 665                
1 0 1 0 900 49 870 51 835 53 800 56 765 58 730 61 695 64 660 67
0 1 1 0 950 47 920 48 890 50 855 52 825 54 795 56 765 58 730 61
1 1 1 0 1000 44 970 46 940 47 910 49 880 51 850 52 820 54 790 56
0 0 0 1 1075 41 1045 43 1015 44 985 45 960 46 925 48 900 49 870 51
1 0 0 1 1110 40 1080 41 1055 42 1025 43 1000 44 975 46 945 47 920 48
0 1 0 1 1170 38 1140 39 1115 40 1090 41 1060 42 1035 43 1010 44 985 45
1 1 0 1 1210 37 1185 38 1160 38 1130 39 1105 40 1080 41 1055 42 1025 43
0 0 1 1 1520 29 1225 36 1200 37 1175 38 1150 39 1120 40 1095 41 1070 42
1 0 1 1 1305 34 1280 35 1255 35 1230 36 1205 37 1180 38 1155 38 1130 39
0 1 1 1 1350 33 1230 36 1305 34 1285 35 1260 35 1240 36 1215 37 1195 37
1 1 1 1 1440 31 1400 32 1365 33 1230 36 1295 36 1255 35 1220 36 1185 38
 *TA/TK-080(C)-*B1  80000 0 0 0 0                                
1 0 0 0                                
0 1 0 0                                
1 1 0 0 725                            
0 0 1 0 810                            
1 0 1 0 940 890 845 795 750 700        
0 1 1 0 990 60 945 905 860 820 775 735 690
1 1 1 0 1055 56 1015 58 970 930 890 845 805 760
0 0 0 1 1135 52 1095 54 1055 56 1010 59 960 930 890 850
1 0 0 1 1185 50 1145 52 1105 54 1065 56 1030 58 990 60 950 910
0 1 0 1 1250 47 1210 49 1170 51 1135 52 1095 54 1055 56 1020 58 980 60
1 1 0 1 1290 46 1255 47 1220 49 1180 50 1145 52 1110 53 1075 55 1040 57
0 0 1 1 1315 45 1275 46 1240 48 1200 49 1160 51 1120 53 1085 55 1045 57
1 0 1 1 1350 44 1315 45 1280 46 1245 48 1205 49 1170 51 1135 52 1100 54
0 1 1 1 1390 43 1350 44 1315 45 1275 46 1240 48 1200 49 1160 51 1125 53
1 1 1 1 1420 42 1380 43 1345 44 1310 45 1270 47 1235 48 1200 49 1160 51

Notes:

  1. Motor Switch Settings are for heating speeds using HEAT switches 1, 2, 3, & 4 and cooling speeds using COOL switches 5, 6, 7, & 8.
  2. Two openings are required for airflows above 1600 CFM if the filter(s) is (are) adjacent to the furnace.
  3. Data is shown without the filter.
  4. Temperature rises in the table are approximate. Actual temperature rises may vary.
  5. Temperature rises that are shaded in grey are not recommended.
G7TA/TK – 80% AFUE, Two Stage Gas Furnace
 

 

Model Number

 

Heating Input (Btuh)

 

Motor Switch Setting

External Static Pressure (in.w.c.)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
1/5 2/6 3/7 4/8 CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise
 

 

 

 

 

 

 

 

*TA100(C)-*B1

 

 

 

 

 

 

 

 

100000

0 0 0 0 905 890 805 780                
1 0 0 0 980 930 900 835 820 800 715 670
0 1 0 0 1095 1015 980 915 895 870 810 765
1 1 0 0 1160 64 1100 1065 1035 995 940 895 865
0 0 1 0 1230 60 1195 62 1170 1110 1075 1060 995 970
1 0 1 0 1315 56 1275 58 1240 60 1195 62 1160 64 1140 65 1115 1075
0 1 1 0 1345 55 1310 57 1280 58 1250 59 1220 61 1190 62 1140 65 1115
1 1 1 0 1445 51 1390 53 1350 55 1315 56 1280 58 1250 59 1230 60 1185 63
0 0 0 1 1490 50 1430 52 1420 52 1380 54 1340 55 1310 57 1280 58 1275 58
1 0 0 1 1550 48 1510 49 1475 50 1450 51 1420 52 1375 54 1340 55 1325 56
0 1 0 1 1600 46 1270 58 1540 48 1500 49 1475 50 1445 51 1425 52 1385 53
1 1 0 1 1640 45 1605 46 1570 47 1550 48 1525 49 1490 50 1460 51 1430 52
0 0 1 1 1690 44 1665 44 1630 45 1600 46 1570 47 1550 48 1515 49 1490 50
1 0 1 1 1755 42 1730 43 1680 44 1660 45 1640 45 1610 46 1575 47 1550 48
0 1 1 1 1805 41 1770 42 1740 43 1715 43 1690 44 1655 45 1645 45 1605 46
1 1 1 1 1860 40 1825 41 1790 41 1765 42 1745 42 1710 43 1695 44 1660 45
 TA/TK-100(C)-*C1  100000 0 0 0 0 1125 66 1040 960                    
1 0 0 0 1205 61 1120 1040 960                
0 1 0 0 1305 57 1225 60 1150 64 1070 995 915        
1 1 0 0 1430 52 1350 55 1270 58 1190 62 1110 1030 950 865
0 0 1 0 1525 49 1450 51 1375 54 1300 57 1225 60 1150 64 1075 1000
1 0 1 0 1620 46 1540 48 1465 51 1390 53 1315 56 1240 60 1165 64 1090
0 1 1 0 1695 44 1620 46 1545 48 1465 51 1390 53 1315 56 1235 60 1160 64
1 1 1 0 1770 42 1700 44 1630 45 1555 48 1485 50 1410 53 1340 55 1265 59
0 0 0 1 1875 40 1805 41 1730 43 1655 45 1580 47 1510 49 1435 52 1340 55
1 0 0 1 1905 39 1840 40 1775 42 1710 43 1640 45 1575 47 1510 49 1445 51
0 1 0 1 1980 37 1910 39 1845 40 1780 42 1715 43 1650 45 1580 47 1515 49
1 1 0 1 2025 37 1960 38 1895 39 1830 40 1765 42 1700 44 1635 45 1570 47
0 0 1 1 2085 36 2025 37 1960 38 1900 39 1840 40 1775 42 1715 43 1655 45
1 0 1 1 2135 35 2070 36 2010 37 1945 38 1880 39 1815 41 1750 42 1685 44
0 1 1 1 2200 34 2145 35 2090 35 2035 36 1980 37 1925 38 1870 40 1820 41
1 1 1 1 2280 32 2225 27 2170 34 2115 35 2065 22 2010 37 1955 38 1900 39

Notes:

  1. Motor Switch Settings are for heating speeds using HEAT switches 1, 2, 3, & 4 and cooling speeds using COOL switches 5, 6, 7, & 8.
  2. Two openings are required for airflows above 1600 CFM if the filter(s) is (are) adjacent to the furnace.
  3. Data is shown without a filter.
  4. Temperature rises in the table are approximate. Actual temperature rises may vary.
  5. temperature rises that are shaded in grey are not recommended.
G7TA/TK – 80% AFUE, Two Stage Gas Furnace
Model Number Heating Input (Btuh) Motor Switch Setting External Static Pressure (in.w.c.)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
1/5 2/6 3/7 4/8 CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise
*TA/TK-120(C)-*C1 120000 0 0 0 0 1125 1040                          
1 0 0 0 1205 1120 1040                    
0 1 0 0 1305 1225 1150 1070                
1 1 0 0 1430 62 1350 1270 1190 1110 1030        
0 0 1 0 1525 58 1450 61 1375 65 1300 1225 1150 1075 1000
1 0 1 0 1620 55 1540 58 1465 61 1390 64 1315 1240 1165 1090
0 1 1 0 1695 52 1620 55 1545 58 1465 61 1390 64 1315 1235 1160
1 1 1 0 1770 50 1700 52 1630 55 1555 57 1485 60 1410 63 1340 66 1265
0 0 0 1 1875 47 1805 49 1730 51 1655 54 1580 56 1510 59 1435 62 1340 66
1 0 0 1 1905 47 1840 48 1775 50 1710 52 1640 54 1575 56 1510 59 1445 62
0 1 0 1 1980 45 1910 47 1845 48 1780 50 1715 52 1650 54 1580 56 1515 59
1 1 0 1 2025 44 1960 45 1895 47 1830 49 1765 50 1700 52 1635 54 1570 57
0 0 1 1 2085 43 2025 44 1960 45 1900 47 1840 48 1775 50 1715 52 1655 54
1 0 1 1 2135 42 2070 43 2010 44 1945 46 1880 47 1815 49 1750 51 1685 53
0 1 1 1 2200 40 2145 41 2090 43 2035 44 1980 45 1925 46 1870 48 1820 49
1 1 1 1 2280 39 2225 40 2170 41 2115 42 2065 43 2010 44 1955 45 1900 47
*TA/TK-140(C)-*D1 140000 0 0 0 0 1395 1350 1305 1260 1210 1165        
1 0 0 0 1465 1420 1375 1330 1290 1245 1200    
0 1 0 0 1555 67 1510 69 1470 1425 1380 1340 1295 1250
1 1 0 0 1625 64 1585 65 1540 67 1500 69 1460 1415 1375 1335
0 0 1 0 1690 61 1650 63 1610 64 1570 66 1530 68 1485 70 1445 1405
1 0 1 0 1760 59 1715 60 1670 62 1625 64 1575 66 1530 68 1485 70 1440
0 1 1 0 1835 57 1790 58 1745 59 1695 61 1650 63 1605 65 1555 67 1510 69
1 1 1 0 1885 55 1840 56 1790 58 1745 59 1700 61 1655 63 1610 64 1565 66
0 0 0 1 1945 53 1900 55 1850 56 1805 57 1760 59 1710 61 1665 62 1620 64
1 0 0 1 1950 53 1905 54 1860 56 1820 57 1775 58 1735 60 1690 61 1650 63
0 1 0 1 2075 50 2030 51 1990 52 1945 53 1900 55 1855 56 1810 57 1770 59
1 1 0 1 2125 49 2085 50 2040 51 2000 52 1955 53 1910 54 1870 55 1825 57
0 0 1 1 2170 48 2130 49 2090 50 2045 51 2005 52 1965 53 1925 54 1880 55
1 0 1 1 2215 47 2180 48 2140 48 2105 49 2070 50 2035 51 2000 52 1965 53
0 1 1 1                 2225 47 2165 48 2100 49 2040 51
1 1 1 1                     2170 48 2120 49 2065 50

Notes:

  1. Motor Switch Settings are for heating speeds using HEAT switches 1, 2, 3, & 4 and cooling speeds using COOL switches 5, 6, 7, & 8.
  2. Two openings are required for airflows above 1600 CFM if the filter(s) is (are) adjacent to the furnace.
  3. Data is shown without the filter.
  4. Temperature rises in the table are approximate. Actual temperature rises may vary.
  5. Temperature rises that are shaded in grey are not recommended.

MODEL IDENTIFICATION CODE

Gibson-KG7T-Two-Stage-Fixed-Speed-High-Efficiency-Upflow-Horizontal-and-Downflow-Gas-Furnaces-FIG-7

SPECIFICATIONS

KG7TA/TK  MODEL NUMBERS  060C-23A1  080C-24B1  100C-24B1  100C-35C1  120C-35C1  140C-45D1
Input – Btuh (a) 60,000 / 39,000 80,000 / 52,000 100,000 / 65,000 100,000 / 65,000 120,000 / 78,000 140,000 / 91,000
Heating Capacity – Btuh 48,000 / 31,200 64,000 / 41,600 80,000 / 52,600 80,000 / 52,600 96,000 / 62,400 112,000 / 72,800
AFUE 80.0 80.0 80.0 80.0 80.0 80.0
Blower D x W 10 x 6 11 x 8 11 x 8 11 x 10 11 x 10 11 x 10
Motor H.P. – Speed – Type 1/2 BLDC 1/2 BLDC 1/2 BLDC 3/4 BLDC 3/4 BLDC 1 BLDC
Motor FLA 6.2 6.2 8.7 8.7 8.7 11.7
Rated Ext. SP – In. W.C. 0.5 0.5 0.5 0.5 0.5 0.5
Temperature Rise Range – ºF 25-55 30-60 30-60 35-65 35-65 40-70
Shipping Weights – TA 104lbs 116lbs 120lbs 135lbs 135lbs 154lbs
Shipping Weights – TK 104lbs 116lbs 116lbs 135lbs 140lbs 146lbs
  • All models are 115 V and 60 HZ. Gas connections are 1/2″ N.P.T.
  • AFUE= Annual Fuel Utilization Efficiency

ACCESSORIES

KG7TA/TK KITS
Description SKU
Fixed Speed to Variable Speed 904880
“A” Cabinet Downflow Sub Base Kit 902974
“B”, “C”, “D” Cabinet Downflow Sub Base Kit 904911
U.S. LP Conversion Kit (0 to 10,000 ft.) 905028
Canada LP Conversion Kit (0 to 4,500 ft.) 905029
Bottom Return Filter 20 per Box, “B” Cabinet 904916
Bottom Return Filter 20 per Box, “D” Cabinet 904918
Side Return Filter Kit 541036

GENERAL TERMS OF LIMITED WARRANTY

  • Nortek Global HVAC, LLC will furnish a replacement for any part of this product that fails in normal use and service within the terms and conditions of the warranty.
  • For complete details of the Limited Warranty, including applicable terms and conditions, see your local installer or contact the Nortek Global HVAC, LLC warranty department for a copy.
  • Before purchasing this appliance, read important energy cost and efficiency information available from your retailer.
  • Specifications and illustrations are subject to change without notice and without incurring obligations.
  • Printed in U.S.A (06/2017)
  • 834C-0617 (Replaces 834C-0916)
  • www.gibsonhvac.com
  • GIBSON is a pending or registered trademark of Electrolux Home Products Inc. and used under a license from Electrolux Home Products, Inc. © Nortek Global HVAC, LLC. All Rights Reserved.

Documents / Resources

Gibson KG7T Two Stage Fixed Speed High Efficiency Upflow Horizontal and Downflow Gas Furnaces [pdf] User Manual
KG7T Two Stage Fixed Speed High Efficiency Upflow Horizontal and Downflow Gas Furnaces, KG7T, Two Stage Fixed Speed High Efficiency Upflow Horizontal and Downflow Gas Furnaces, Fixed Speed High Efficiency Upflow Horizontal and Downflow Gas Furnaces, High Efficiency Upflow Horizontal and Downflow Gas Furnaces, Upflow Horizontal and Downflow Gas Furnaces, Horizontal and Downflow Gas Furnaces, and Downflow Gas Furnaces, Downflow Gas Furnaces, Gas Furnaces