Fire-LITe logo ACC-25-50 Voice Evacuation Control Panel
Owner’s ManualFire-LITe Alarms ANN-S-PG Serial Parallel Printer Interface Module

General

The ANN-S/PG Interface module connects either a serial or parallel printer with a compatible Fire Alarm Control Panel (FACP) to print real-time logs of system events, detector status reports, and event histories.
The ANN-S/PG and the FACP communicate over a two-wire serial interface employing the ANN-Bus communication format. An additional two wires are used for 24-volt DC power. A single  four-conductor unshielded cable may be  used for both power and data communications.
Up to eight devices may be connected to the ANN-Bus of each FACP.

Features

  • Listed to UL Standard 864, 9th edition
  • Auto-configure menu selection allows programmer to bring all the devices attached to the ANN-Bus on-line quickly
  • Surface mounts directly to wall
  • Can be remotely located up to 6,000 feet (1,829 m) from the panel
  • May be powered by 24 VDC from the host FACP or by remote power supply (requires 24 VDC)
  • Connects a remote printer using a standard cable (DB-9 for a serial printer; DB-25 for a parallel printer)

Specifications

  • Operating Voltage: 24 VDC
  • Current (Alarm and Standby): 45mA
  • Ambient Temperature: 32°F to 120°F (0°C to 49°C)
  • Relative Humidity: 93% ± 2% RH (non-condensing) at 32°C ± 2°C (90°F ± 3°F)
  • Maximum wiring distance from FACP: 6,000 ft. (1,829 m.)
  • Dimensions: 6.00” (15.2 cm.) high x 7.76” (19.7 cm.) wide x 1.46” (3.7 cm.) deep
  • For use indoors in a dry location
  • Connections to FACP are power-limited and supervised

The ANN-Bus
POWERING THE DEVICES ON THE ANN-BUS FROM AUXILIARY POWER SUPPLY
ANN-Bus devices can be powered by an auxiliary power supply when available panel power is exceeded. See FACP manual for information.
ANN-BUS DEVICE ADDRESSING
Each ANN-Bus device requires a unique address (ID Number) in order to communicate with the FACP. A maximum of eight devices can be connected to the FACP ANN-Bus communication circuit. See the FACP manual for more information.
Agency Listings and Approvals
The listings and approvals below apply to the ANN-S/PG. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process.
Consult factory for latest listing status.

  • UL: S2424
  • CSFM: 7120-0075:0213
  • MEA: 442-06-E

FireLite® Alarms is a registered trademark of Honeywell International Inc. ©2018 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.Fire LITe Alarms ACC 25 50 Voice Evacuation Control Panel - iconThis document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice.

Fire-LITe logoFor more information, contact FireLite Alarms.
Phone: 800-627-3473,
FAX: 877-699-4105.
www.firelite.com
firealarmresources.com
Fire LITe Alarms ACC 25 50 Voice Evacuation Control Panel - icon 1

Documents / Resources

Fire-LITe Alarms ANN-S-PG Serial Parallel Printer Interface Module [pdf] Owner's Manual
ANN-S-PG Serial Parallel Printer Interface Module, ANN-S-PG, Serial Parallel Printer Interface Module, Parallel Printer Interface Module, Printer Interface Module, Interface Module, Module

References

Leave a comment

Your email address will not be published. Required fields are marked *