Era GDF 100 Inline Centrifugal Fan Instruction Manual
Era GDF 100 Inline Centrifugal Fan

Passport/Service instruction

Inline сcentrifugal fan

Assignment
Inline сentrifugal fans MARS is intended for application in rooms of residential and public buildings, and also in auxiliary buildings of the industrial enterprises.

Safety requirements

Base on type of protection from electric shock the fans relate to the class I devices per GOST(all-union State Standard) 12.2.007.0-75. The level of fan protection against dangerous parts and water is IP X4. The level of motor protection against dangerous parts and water is IP44.

Warning Icon ATTENTION!
Fan operation outside the specified temperature range (from -25C to +70C) is prohibited. It is prohibited to install fan in the same air vent line together with smoke emission pipe of the fuel burner device.

Warning Icon ATTENTION!
All options, including linking, configuration, maintenance and repair must be performed only when the main voltage is off.
Electricians with special access to the executed work, install fans.
Disconnecting items from a network have to be built in stationary conducting, according to installation rules. The disconnecting device has to disconnect all poles. The ground cable shouldn’t be broken off.

Warning Icon ATTENTION!
The equipment can not be used by persons (including children) with limited physical, mental or intellectual abilities or if they have no skills or knowledge, unless they are controlled or instructed how to use appliance by a person responsible for their safety. Children must be under supervision to avoid playing with the device.
Safety requirements

Main technical characteristics MARS

MARS fans is issued seven standard sizes depending on the install housing diameter.
Fan look, basic dimensions, connecting sizes and technical characteristics described in pic.1 and lists of dimensions and characteristics (table 1).
Main technical characteristics

Type D Dimensions, mm D1          А B Weight, kg
MARS GDF 100 100 243 194 23 2,9
MARS GDF 125 125 243 195 27 2,9
MARS GDF 150 150 333 222 23 4,1
MARS GDF 160 160 333 222 25 4,1
MARS GDF 200 200 333 223 24 5,0
MARS GDF 250 250 333 230 27 5,4
MARS GDF 315 315 402 228 25 6,6
Characterictic MARS GDF 100 MARS GDF 125 MARS GDF 150 MARS GDF 160 MARS GDF 200 MARS GDF 250 MARS GDF 315
Power consumption, W 62 64 101 102 144 177 278
Productive capacity, m3/h 245 340 550 655 935 1020 1500
Pressure, Pa 355 310 374 390 490 587 725
Frequency of rotation, r.p.m. 2587 2505 2605 2578 2654 2544 2502
Noise level dBA, the distance should be not more than 3 m 55 54 60 60 70 60 61
Сurrent type AC , single phase
Frequency, Hz 50
Supply voltage, V 220-240

“ERA” fans are manufactured according to specs 4681-007-96059883-2016, valid rules and standards. Fans are
intended for alternate current network connection of 220-240 V voltage and 50 Hz frequency (allowed to use the fan at a frequency of 60Hz)

Wiring diagram MARS

Wiring diagram MARS

Fan connection to a network

Warning Icon ATTENTION!
The fan and the service controlling equipment has to be isolated from power supply during the installation time and service. The equipment has to be grounded.
Uncover the distribution block, study wiring diagram (Pic.2) and make necessary connections. Make sure, there is grounding. After the end of connecting works and checking of connections to a distribution box, move a cover and make sure that it is fixed.

Installation:

The length of the well-established pipeline from the fan should be at least 1000 mm. A shorter pipeline should be equipped with a rigid lid/grid that complies with EN ISO 13857: 2008.

Maintenance

  • switch off the fan;
  • disconnect it from air ducts and air dispensers and remove from the installation site;
  • remove dust from blades of the driving wheel, using a soft dry brush or cloth;
  • clean blades of the driving wheel, using soapy water;
  • wipe all plastic parts with a soft cloth dampened with soapy water;
  • wipe all surfaces dry;
  • assemble and install the fan in place;
  • recommended to do the cleaning 1 time in 6 months.

Warning Icon ATTENTION!
Do not allow the cleaning solution to the motor!

Possible problems and solutions

Malfunction Probable cause Remedy
When connected to the power grid, the fan does not rotate, does not respond to controls. The mains supply is not connected. It is necessary to consult a specialist.
Internal connection fault.
Low air flow. The ventilation system is clogged. Clean the ventilation system.
Increased noise or vibration. The impeller is blocked. Clean the impeller.
The fan is not fixed or incorrectly mounted. Correct the installation error.
The ventilation system is clogged. Clean the ventilation system.

Warning Icon ATTENTION!
The fan and the service controlling equipment has to be isolated from power supply during the installation time and service. The equipment has to be grounded.

Storage and transportation

Keep the fan only in manufacturer packaging in a ventilated room with temperature range from -40°C to +80 ° C and relative humidity of 80% (at T = 25 ° C). Shelf life – 5 years from manufacture date.
Products are to be transported by any transport, provided that manufacturer packaging is safe from direct exposure to rainfall, impact from other products, displacement during transportation. Transportation is conducted, according to the rules applicable for this transport.

Utilisation

Dustbin Icon This appliance has label in accordance with European Directive 2002/96/EC on waste electrical and electronic
appliances (waste electrical and electronic equipment – WEEE). This order acts on rules on the territory throughout the EC and recycling of old appliances.

Warranty

Manufacturer guarantees normal fan operation for 2 year from the sale date in retail trade system providing execution of the rules of transportation, storage, installation, operation and other requirements of this instruction. In case the sale date is missing, warranty period will be the date of manufacture.
In case fan work is found faulty, due to manufacturer defects during the warranty period, the consumer has right to replace the fan at the factory, provided the matching of serial numbers on the product and in the passport.

Service lifetime

Established service period – 5 years

Evidence about certificate:
Certificate of compliance No. RU-C-RU.MM06.B.00090. Validity: from 01.09.2016 until 31.08.2021
Series RU No. 0074798
Issued by Authority on production certification Global Standard, LLC
Address: 1 building, 28 house, Volgogradsky avenue, the city of Moscow, 109316

The decryption of serial numbers.
The serial number is located on the label with the characteristics of fan and consists of 10 characters. The serial number is read from left to right, as follows:
Decryption serial numbers

Manufacturer:
«ERA» LLC, 390047, Novelise Ulyanovsk street,17,Ryan city, Russia tel. (4912) 24-16-00,e-mail: sale@era.trade, www.era.trade

Replacement will be made at the following address:
«ERA» LLC, 390047, Tsiolkovsky street,17,Ryan city, Russia tel. (4912) 24-16-00,e-mail: sale@era.trade, www.era.trade

Company logo

Documents / Resources

Era GDF 100 Inline Centrifugal Fan [pdf] Instruction Manual
GDF 100, GDF 125, GDF 150, GDF 160, GDF 200, GDF 250, GDF 315, GDF 100 Inline Centrifugal Fan, GDF 100, Inline Centrifugal Fan, Centrifugal Fan, Fan

References

Leave a comment

Your email address will not be published. Required fields are marked *