Innovair Installation Manual

Single Zone Ductless Heat Pump (Outdoor Unit)

Indoor Units

Outdoor Units

IMPORTANT NOTE: Read this manual carefully before installing or operating your new air conditioning unit. Make sure to save this manual for future reference.

Safety Instructions

Model Fuse of Indoor unit Fuse of outdoor unit
9K(115V) T 3.15A or T 5A 250V T 25A 250V
12K(115V) T 3.15A or T 5A 250V T 25A 250V
9K-12K(208/230V) T 3.15A or T 5A 250V T 15A 250V
18K(208/230V) T 3.15A or T 5A 250V T 20A 250V
24K-36K(208/230V) T 3.15A or T 5A 250V T 30A 250V

Safety Precautions

Precautions for using R32 and R454B refrigerant

For the multi system, the refrigerant refer to the multi outdoor unit. The basic installation work procedures are the same as the conventional refrigerant (R22 or R410A). However, pay attention to the following points:

CAUTION

CAUTION

CAUTION

Precautions for using UV-C germicidal lamp systems (Optional)

CAUTION

Installation Instructions

Installation Diagram

A diagram shows the outdoor unit with recommended clearances:

Note: Above figure is only a simple presentation of the unit, it may not match the external appearance of the unit you purchased. Installation must be performed in accordance with the national wiring standards by authorized personnel only.

Suggested Tools

In order to install your air-conditioner more conveniently and safely, you might use those special tools listed below.

Site Instructions

Site for Installing Outdoor Unit

A diagram shows pipe length and height differences between indoor and outdoor units.

Pipe length is 20 meters(65.6ft) Max.

Height should be less than 5m (16.41)

Outdoor unit is higher than indoor unit

In case the pipe length is more than 7.5m(24.6ft), the refrigerant should be charged additionally, according to below table.

Model Required amount of additional refrigerant (g/m)
9K-18K 20
24K 30
30K-36K 40

If the height or pipe length is out of the scope of the table, please consult the merchant.

Installation of indoor unit refers to the indoor unit installation manual.

Outdoor Unit Installation

1. Install Condensate Drain for Outdoor Unit

The condensate drains from the outdoor unit when the unit operates in heating mode. In order not to disturb your neighbor and protect the environment, install a drain port and a drain hose to direct the condensate water. Just install the drain port and rubber washer to the chassis of the outdoor unit, then connect a drain hose to the port as the following figure demonstrates.

A diagram shows how to install the condensate drain port and hose.

Place under the leg pedestal

Rubber pad (optional)

Drain port

Washer

Drain hose (prepared by user)

2. Install Ground Pad or Wall Hangers

  1. Determine proper location for outdoor unit.
  2. Follow all instructions provided by manufacturer for installing wall hangers rubber pad.
  3. Verify the wall hangers or rubber pad can safely support the weight of the outdoor unit.
  4. Verify the wall hangers or rubber pad is level and meets all outdoor dimensional clearance.
  5. Fix with bolts and nuts tightly on a flat and strong floor.

If installed on the wall or roof, make sure to fix the supporter well to prevent it from shaking due to serious vibration or strong wind.

Piping Connections to Outdoor Unit

WARNING Florida wind load requirements state that outdoor unit must be anchored to concrete pad using four 3/8-in diameter power wedge bolt plus (or equivalent) with 1-in diameter fender washers. Anchor bolts must be embedded into 3000 PSI minimum concrete at a distance of 4 1/2- in from any concrete edge. The concrete thickness must exceed 1.5 times the anchor depth.

Pipe diameter /inch(mm) Nut Size /inch(mm) Tightening Torque (ft-lbs) Tightening Torque (N-m)
1/4(6.35) 1/4(17) 11 to 15 15 to 20
3/8(9.5) 3/8(22) 22 to 26 30 to 35
1/2(12.7) 1/2(25) 37 to 41 50 to 55
5/8(15.9) 5/8(29) 44 to 48 60 to 65
3/4(19) 3/4(32) 52 to 55 70 to 75

Note: Over tightening may damage flare connections and cause leaks.

A diagram shows the service valve cover.

Power and Wiring

Connecting of the Cable

Outdoor Unit
  1. Remove the cable cross board from the unit by loosening the screw. Connect the wires to the terminals on the control board individually as follows.
  2. Secure the power cord onto the control board with cable clamp.
  3. Reinstall the cable cross board to the original position with the screw.
  4. Use a recognized circuit breaker between the power source and the unit. A disconnecting device to adequately disconnect all supply lines must be fitted.

Caution:

1. Never fail to have an individual power circuit specifically for the air conditioner. As for the method of wiring, refer to the circuit diagram posted on the inside of the access door.

2. Confirm that the cable thickness is as specified in the power source specification.

3. Check the wires and make sure that they are all tightly fastened after cable connection.

4. Be sure to install an earth leakage circuit breaker in wet or moist areas.

A diagram shows the outdoor unit with cable cross board and wire hole.

Attention: The plug must be accessible even after the installation of the appliance in case there is a need to disconnect it. If not possible, connect appliance to a double-pole switching device with contact separation of at least 3 mm placed in an accessible position even after installation.

Wiring diagram

Warning: Before obtaining access to terminals, all supply circuits must be disconnected. Make sure that the color of the wires in the outdoor unit and terminal No, are the same as those of the indoor unit, the details please refer to the wiring diagram which is near the terminal inside the unit.

Cable Specifications

capacity(Btuh) Power cord Power connecting cord
Type Normal cross-sectional areas Type Normal cross-sectional areas
9K-12K(208/230V) SJ TW 3X16 AWG SJ TW 4X18 AWG
18K(208/230V) SJ TW 3X14 AWG SJ TW 4X18 AWG
24K-36K(208/230V) SJ TW 3X12 AWG SJ TW 4X18 AWG
9K,12K(115V) SJ TW 3X14 AWG SJ TW 4X18 AWG

Vacuum Testing and Charging

The air which contains moisture remaining in the refrigeration cycle may cause a malfunction on the compressor. After connecting the indoor and outdoor units, release air and moisture from the refrigerant cycle using a vacuum pump, as shown below.

Note: To protect the environment, be sure not to discharge the refrigerant to the air directly. See next page for air purging steps.

A diagram illustrates the vacuum testing and charging setup, including the indoor unit, outdoor unit, 3-way valve, 2-way valve, and vacuum pump.

How to Vacuum Air Tubes:

  1. Unscrew and remove caps from 2 and 3-way valves.
  2. Unscrew and remove cap from service valve.
  3. Connect vacuum pump flexible hose to the service valve.
  4. Start vacuum pump for 10-15 minutes until reaching a vacuum of 10 mm Hg absolutes.
  5. With vacuum pump still running close the low pressure knob on vacuum pump manifold. Then stop the vacuum pump.
  6. Open 2-way valve, 1/4 turn, then close it after 10 seconds. Check tightness of all joints using liquid soap or an electronic leak detector.
  7. Turn 2 and 3-way valves stem to fully open the valves. Disconnect the flexible vacuum pump hose.
  8. Replace and tighten all valve caps.

The design and specifications are subject to change without prior notice for product improvement. Consult with the sales agency or manufacturer for details. Any updates to the manual will be uploaded to the service website, please check for the latest version.

CS019UI-EP(R454B)

16122000011774

2024.05.16

Models: QHW09H2UZRA, QHW12H2UZRA, QHW18H2UZRA, QHW24H2UZRA, QOS09H2BM5A, QOS12H2BM5A, QOS18H2BM5A, QOS24H2BM5A, QHW09H2UZRA Ductless Single Zone Heat Pump, QHW09H2UZRA, Ductless Single Zone Heat Pump, Single Zone Heat Pump, Zone Heat Pump, Heat Pump

PDF preview unavailable. Download the PDF instead.

Q4 Installation-Manual-Outdoor-Unit-EN .aspx?lang=en-CA Adobe PDF library 17.00

Related Documents

Preview Innovair Q4 Ductless Single Zone Heat Pump Approval Drawings
Detailed approval drawings and specifications for the Innovair Q4 Ductless Single Zone Heat Pump, covering performance, features, technical data, and dimensions for various models.
Preview Innovair Q4 Ductless Mini-Split Heat Pump - Technical Specifications and Features
Detailed specifications and features for the Innovair Q4 series of ductless mini-split heat pumps, including SEER2, EER2, heating and cooling capacities, refrigerant type (R454B), and operational parameters. Highlights energy efficiency and advanced features like Wi-Fi connectivity.
Preview Innovair Q4+ Heat Pump & Air Conditioner Systems | Efficient Climate Control
Explore the Innovair Q4+ series of heat pumps and air conditioners, featuring advanced DC inverter technology, R454B refrigerant, and exceptional cold climate performance. Discover models for High Wall, Ducted, and Ceiling Cassette installations.
Preview Innovair Q4 Multi Heat Pump System: Efficient and Versatile Air Conditioning
Explore the Innovair Q4 Multi Heat Pump System, offering efficient performance, low ambient operation, and flexible indoor unit options including High Wall, Fan Coils, and Cassettes. Features R454B refrigerant, WiFi connectivity, and Energy Star certification.
Preview Innovair Elite Heat Pump Ductless Splits Remote Controller Manual
This manual provides instructions for operating the Innovair Elite Heat Pump Ductless Splits remote controller. It covers features such as ON/OFF, fan speed control, mode selection, temperature adjustment, and special functions like I FEEL and SLEEP modes.
Preview Innovair SLIM24 High Efficiency Heat Pump System: Installation and Owner's Manual
Comprehensive guide for installing and operating the Innovair SLIM24 High Efficiency Heat Pump System, covering safety precautions, maintenance, and troubleshooting for optimal performance.
Preview Innovair Deluxe 17: Ductless Inverter Heat Pump Mini Split System
Explore the features and specifications of the Innovair Deluxe 17, a ductless inverter heat pump mini split system designed for efficient and quiet air conditioning and heating.
Preview Innovair PXV36H2A Inverter Heat Pump Package Unit Installer's Guide
Comprehensive installer's guide for the Innovair PXV36H2A Inverter Heat Pump Package Unit, covering safety precautions, installation procedures, component details, electrical wiring, and testing.