ENDA EHTC7425A HUMIDITY AND TEMPERATURE CONTROLLER Logo

ENDA EHTC7425A HUMIDITY AND TEMPERATURE CONTROLLER

ENDA EHTC7425A HUMIDITY AND TEMPERATURE CONTROLLER product

  • Read this document carefully before using this device. The guarantee will be expired by damaging of the device if you don’t attend to the directions in the user manual. Also we don’t accept any compensations for personal injury, material damage or capital disadvantages.

ENDA EHTC7425A HUMIDITY AND TEMPERATURE CONTROLLER

  • 72 x mm sized.
  • Dual 4 digit display
  • 0/4-20mA, 0-10V, 1- 5V analog or digital input (Specify at Order).
  • Heating or cooling control selection.
  • PID, On-Off Temperature control selection.
  • PID Auto-calculation (SELF TUNE).
  • Humidification or drying control selection.
  • Internal supply output for sensor.
  • Time and temperature-dependent fan relay output selection.
  • 2 Relay outputs with time setting for incubation operations.
  • Adjustable buzzer alarm feature for measurement values.
  • CE marked according to European Norms.
    BOSCH GLM 100 C Professional Laser RangeFinders 01BOSCH GLM 100 C Professional Laser RangeFinders 02
  1. Input
    AS….. ..Analog Input
    DS….. .Digital Input
    Sensor must be ordered separately.
  2. Supply Voltage
    230………230V AC
    110……….110V AC
    SM……..10…30V DC
    8…24V AC
  3. Mod Bus
    Blank……N/A
    RSI………Mod Bus
    Specify at Order).
    Please see page 6 for Modbus Connection Diagram.
  4. SSR
    Blank……N/A
    SSR………Mod Bus
    Applies to the heat output)

TECHNICAL SPECIFICATIONS

BOSCH GLM 100 C Professional Laser RangeFinders TABLE O1BOSCH GLM 100 C Professional Laser RangeFinders TABLE 02 BOSCH GLM 100 C Professional Laser RangeFinders TABLE 03 BOSCH GLM 100 C Professional Laser RangeFinders TABLE 04 BOSCH GLM 100 C Professional Laser RangeFinders TABLE 05

DIMENSIONS
BOSCH GLM 100 C Professional Laser RangeFinders 03

  1. To removing the device from panel : – While pressing both side of the device in direction 1 and push it in direction 2BOSCH GLM 100 C Professional Laser RangeFinders 04

BOSCH GLM 100 C Professional Laser RangeFinders 05

    NOTE:-

  1. While panel mounting, additional distance is required for connection cables.
  2. Panel thickness should be maximum 10mm
  3. If there is no 90mm free space at back side of the device, it would be difficult to remove it from the panel.

SENSOR (Must be ordered separately)

EHTD-CB-100 Digital Output Humidity Temperature Sensor
BOSCH GLM 100 C Professional Laser RangeFinders 06
EHTD-CB-100 ( Used with EHTC7425A-DS-XX )

INSTALLATION

BOSCH GLM 100 C Professional Laser RangeFinders 07
BOSCH GLM 100 C Professional Laser RangeFinders 08
Note :-

  1. Mains supply cords shall meet the requirements of IEC 60227 or IEC 60245.
  2. In accordance with the safety regulations, the power supply switch shall bring the identification of the relevant instrument and it should be easily accessible by the operator.

ENDA EHTC725A is intended for installation in control panels. Make sure that the device is used only for intended purpose. The shielding must be grounded on the instrument side. During an installation, all of then cables that are connected to the device must be free of energy. The device must be protected against inadmissible humidity, vibrations, severe soiling. Make sure that the operation temperature is not exceeded. All input and output lines that are not connected to the supply network must be laid out as shielded and twisted cables. These cables should not be close to the power cables or components. The installation and electrical connections must be carried on by a qualified staff and must be according to the relevant locally applicable regulations.

FRONT PANEL COMMANDS & USAGE
BOSCH GLM 100 C Professional Laser RangeFinders 09
Displaying and Changing Temperature Set Values
BOSCH GLM 100 C Professional Laser RangeFinders 10

  • During “Running Mode”, if   BOSCH GLM 100 C Professional Laser RangeFinders key 01  key is preset, temperature setpoint value flashes for 3 seconds. While flashing, by pressing  BOSCH GLM 100 C Professional Laser RangeFinders key 02 and  BOSCH GLM 100 C Professional Laser RangeFinders key 03  keys, temperature value can be changed
  • If no key is pressed for 3 seconds or if one of the set keys is pressed again, adjusted set value is saved and the “Running Mode” is entered.

Displaying and Changing Humidity Set Values
BOSCH GLM 100 C Professional Laser RangeFinders 11

  • During “Running Mode”, if  BOSCH GLM 100 C Professional Laser RangeFinders key 04 key is preset, humidity setpoint value flashes for 3 seconds. While flashing, by pressing  BOSCH GLM 100 C Professional Laser RangeFinders key 02  and  BOSCH GLM 100 C Professional Laser RangeFinders key 03  keys, humidity set value can be changed
  • If no key is pressed for 3 seconds or if one of the set keys is pressed again, adjusted set value is saved and the “Running Mode” is entered.

Locking & Unlocking Keypad
BOSCH GLM 100 C Professional Laser RangeFinders 12

  • During “Running Mode”, if   BOSCH GLM 100 C Professional Laser RangeFinders key 01 and  BOSCH GLM 100 C Professional Laser RangeFinders key 03  keys are pressed together for 2 seconds, L o c message is displayed and the keypad locked. While keypad is locked, if  BOSCH GLM 100 C Professional Laser RangeFinders key 01 and  BOSCH GLM 100 C Professional Laser RangeFinders key 03 keys are pressed together for 2 seconds,
  • u n L message is displayed and the keypad unlocked and “Running Mode” is entered. While keypad is locked, if one of the key is pressed, L o c message is displayed. During keypad locked, temperature and humidity set values can be displayed but can not be changed.

Activating / Deactivating Control Outputs

  • During “Running Mode”, if  BOSCH GLM 100 C Professional Laser RangeFinders key 03  key is pressed for 2 seconds,C.d,5 message displayed and the control outputs become deactivated and device works as an indicator.
  • While control outputs deactivated, by pressing   BOSCH GLM 100 C Professional Laser RangeFinders key 03  key for 2 seconds, C.E n B message displayed and device continues to control functions.

Stopping Buzzer Alam

  • When an alarm condition occurs, an audible alarm is triggered. By pressing  BOSCH GLM 100 C Professional Laser RangeFinders key 02 key, buzzer alarm can be turned off.

Default Settings

  • Powered on device by pressing  BOSCH GLM 100 C Professional Laser RangeFinders key 03 key  d. p a r message appears on display and device reset to default settings.

Displaying Revision Number

  • If  BOSCH GLM 100 C Professional Laser RangeFinders key 05  keys are pressed together in “Running Mode”, revision number r.001 appears on display.

ROTATION OUTPUT GRAPHICS

Capture 2

  • Rotation process runs sequentially for left and right directions, Rotation process runs consecutively as opened until open duration time(r.on)and closed until close duration time (r. o f F)

Error – Warning – Alarm Definitions

  • BOSCH GLM 100 C Professional Laser RangeFinders error01Sensor Failure. Check the sensor connection. The audible warning is activated. Temperature and humidification outputs are disabled. Analog outputs are zero.
  • BOSCH GLM 100 C Professional Laser RangeFinders error02Temperature Alarm. Audible warning is activated. Current temperature flashes.Outputs are disabled when the upper limit is exceeded.
  • BOSCH GLM 100 C Professional Laser RangeFinders error03Humidification Alarm. Audible warning is activated. Current humidity flashes.Outputs are disabled when the upper limit is exceeded.
  • BOSCH GLM 100 C Professional Laser RangeFinders error04Self tune menu has been entered.
  • BOSCH GLM 100 C Professional Laser RangeFinders error05During self tune menu, indicates that the measured temperature value is greater than 60% of the set value. In this case, self tune process can not be started.
  • BOSCH GLM 100 C Professional Laser RangeFinders error06Self tune process is running.
  • BOSCH GLM 100 C Professional Laser RangeFinders error07Self tune process has been successfully completed.

 

SELF TUNE OPERATION

  • In order to start the Self-tune operation, t.Pid parameter must be set to YE5 .
    BOSCH GLM 100 C Professional Laser RangeFinders 13

PROGRAMMING THE DEVICE (1/2)

Device has two menus as user and hidden menu. User menu is the frequently used parameters and the hidden menu is where all parameters are found. Menus can be transferred between parameters. If SET and keys are pressed together for 2 seconds in the hidden menu, the parameter is transferred to the user menu. Up to 10 parameters can be transferred to the user menu in this way. If SET and keys are pressed together for 2 seconds in the user menu, parameter is removed from user menu.
BOSCH GLM 100 C Professional Laser RangeFinders 14
The marked parameters are valid only for the humidity temperature sensor model with analogue input.

 

PROGRAMMING THE DEVICE (2/2)

BOSCH GLM 100 C Professional Laser RangeFinders 15
MODBUS CONNECTION

BOSCH GLM 100 C Professional Laser RangeFinders 16

  • Termination should be accomplished by attaching 120 Ohm resistors to the start and at the end of the communication line.
  • Applies to devices with Modbus function.

PARAMETER LIST

PARAMETER LIST
CONFIGURATION PARAMETERS Minimum Maximum Unit Type Default
Unit Temperature unit OFF=°C,ON=°F °C °f °C
d.pnt Decimal indication OFF=no, ON=YE5 no YE5 no
5nd Buzzer OFF=no, ON=YE5 no YE5 no
TEMPERATURE CONTROL PARAMETERS
t.inp Temperature, input type (:00~2200mA,               44~2200m: A,              :00~1100V,            :11~5V5) Only available in humidity temperature sensor models with analog output. 0-20 1-5 mA / V 0-20
t.upl Temperature Upper Limit. Only available in humidity temperature sensor models with analog output. t.Lol 125 °C / °F 60
t.Lol Temperature Lower Limit. Only available in humidity temperature sensor models with analog output. -40 t.upl °C / °F -40
t.Hy5 Temperature hysteresis 1 20 °C / °F 2
t.oFF Temperature of set value -20 20 °C / °F 0
t.cnt Temperature control. Lo :Output is active when the temperature is below set value (cooling control),

Hi : The output is active when the temperature is above the set value (heating control).

LO Hi Hi
t.Pon Temperature output delay time after power-up 00:00 99:00 min:sec 1:00
t.Pid PID temperature control selection (:nOon-Off control          YEP5I:D control) no YE5 no
t.pb Proportional band for PID control 0 100 % 14
t.ti Integral time for PID control 00:00 99:00 min:sec 1:56
t.td Derivation time for PID control. 00:00 99:00 min:sec 0:35
t.Pcp Periodic time for PID control 00:00 02:00 min:sec 0:20
HUMIDIFICATION CONTROL PARAMETERS
h.inp Humidity input type (:00~2200mA,               44~2200m: A,              :00~1100V,            :11~5V5) Only available in humidity temperature sensor models with analog output. 0-20 1-5 mA / V 0-20
h.upl Humidity Upper Limit. Only available in humidity temperature sensor models with analog output. h.Lol 100 %RH 100
h.Lol Humidity Lower Limit. Only available in humidity temperature sensor models with analog output. 0 h.upl %RH 0
h.Hy5 Humidity hysteresis 1 20 %RH 2
h.oFF Humidity of sset value -20 20 %RH 0
h.cnt Humidification control. Lo: Output is active when the humidity is below set value (cooling control),

Hi : The output is active when the humidification is above the set value (heating control).

LO Hi Hi
h.Pon Humidification output delay time after power-up 00:00 99:00 min:sec 1:00
FAN CONTROL PARAMETERS
F.Cnt Fan Control (:n Foan not active,         Y:EF5an active) nO YE5 YE5
FtYP Fan output type selection (:t TihmeEfan runs at time-dependent.,

tEmp: The fan runs at temperature-dependent.)

timE tEmp tEmp
F5Et Fan setpoint value -40 125 °C / °F 38
 

F5tA

Fan temperature control

(L: To the fan will be activated when the temperature value below the setpoint. ,

YE5 : The fan will be activated when the temperature value above the setpoint).

 

Lo

 

Hi

 

Hi

FHY5 Fan hysteresis value 1 20 °C / °F 1
F.on Fan ON time duration. 00:00 99:00 hr:min 1:00
F.oFF Fan OFF time duration. 00:00 99:00 hr:min 1:00
F.t5P Fan alarm setpoint value. t.lol t.uPL °C / °F 50
F.AH5 Fan alarm hysteresis. 1 20 °C / °F 2
RIGHT – LEFT Rotating CONTROL PARAMETERS
r.Cnt Rotating Control (:n Rotating not active,         Y:ER5otating active) nO YE5 YE5
r.on Rotating ON time duration. 00:00 99:00 min:sec 1:00
r.oFF Rotating OFF time duration. 00:00 99:00 hr:min 1:00
ALARM PARAMETERS
A.Pon Alarm message display delay time after power up 00:00 99:00 min:sec 1:00
 

A.ttp

Temperature alarm configuration (AB5 : Absolute alarm, rEF : Relative alarm)

A.b5:  Alarm values are AtLo  and AtHi

rEF:  Alarm values are Atlo  = t.5EtA.tlo and A.tHi = t.5Et+A.tHi

 

Ab5

 

rEF

 

Ab5

A.tHi Temperature upper level alarm (If AttP is changed, this parameter must be re-programmed). A.tLo 125 °C / °F 125
A.tlo Temperature lower level alarm (If AttP is changed, this parameter must be re-programmed) -40 A.tHi °C / °F -40
A.tH5 Temperature alarm hysteresis 1 20 °C / °F 2
 

A.htp

Humidity alarm configuration (AB5 : Absolute alarm, rEF : Relative alarm)

A.b5: Alarm values are A.hLo and A.hHi

rEF: Alarm values are A.hlo = t.5EtA.hlo and A.hHi  =   h.5Et+A.hHi

 

Ab5

 

rEF

 

Ab5

A.hHi Humidity upper level alarm. (If A.htP  is changed, this parameter must be re-programmed) A.hLo 100 %RH 100
A.hlo Humidity lower level alarm.(If A.htP is changed, this parameter must be re-programmed) 0 A.hHi %RH 0
A.hH5 Humidity alarm hysteresis. 1 20 %RH 2
MODBUS COMMUNICATION PARAMETERS
Adr5 Slave device address selection 1 247 1
baud Communication speed (baud rate)selection OFF 19.20 Bps 9600

 

ENDA EHTC7425A HUMIDITY AND TEMPERATURE CONTROLLER MODBUS ADDRESS MAP
1.1 HOLDING REGISTERS
Holding Register

Addresses

 

Data Type

 

Data Content

 

Parameter Name

Read / Write Permission
Decimal Hex
0000d 0x0000 word Temperature set value t.5Et R / W
0001d 0x0001 word Temperature set value Upper Limit t.uPL R / W
0002d 0x0002 word Temperature set value Lower Limit t.LoL R / W
0003d 0x0003 word Temperature upper level alarm A.tHi R / W
0004d 0x0004 word Temperature lower level alarm A.tlo R / W
0005d 0x0005 word Temperature hysteresis t.HY5 R / W
0006d 0x0006 word Temperature of set value t.off R / W
0007d 0x0007 word Temperature alarm hysteresis A.tH5 R / W
0008d 0x0008 word Humidity set value h.5Et R / W
0009d 0x0009 word Humidity set value Upper Limit h.upl R / W
0010d 0x000A word Humidity set value Lower Limit h.lol R / W
0011d 0x000B word Humidity hysteresis h.Hy5 R / W
0012d 0x000C word Humidity of set value h.off R / W
0013d 0x000D word Humidity upper level alarm a.hHi R / W
0014d 0x000E word Humidity lower level alarm a.hlo R / W
0015d 0x000F word Humidity alarm hysteresis a.hH5 R / W
0016d 0x0010 word Temperature output delay time after power-up t.pon R / W
0017d 0x0011 word Humidity output delay time after power-up h.pon R / W
0018d 0x0012 word Fan setpoint value. F5Et R / W
0019d 0x0013 word Fan hysteresis. FHY5 R / W
0020d 0x0014 word Fan alarm setpoint value. Ft5p R / W
0021d 0x0015 word Fan alarm hysteresis. FAH5 R / W
0022d 0x0016 word Fan ON time duration. f.on R / W
0023d 0x0017 word Fan OFF time duration. F.oFF R / W
0024d 0x0018 word Rotating ON time duration. r.on R / W
0025d 0x0019 word Rotating OFF time duration.. r.oFF R / W
0026d 0x001A word Alarm message display delay time after power-up A.Pon R / W
0027d 0x001B word Integral time for PID control t.ti R / W
0028d 0x001C word Derivation time for PID control. t.td R / W
0029d 0x001D word Temperature input type (0:0-20, 1:4-20, 2:0-10, 3:1-5) t.inp R / W
0030d 0x001E word Humidity input type (0:0-20, 1:4-20, 2:0-10, 3:1-5) h.inp R / W
0031d 0x001F word Proportional band for PID control t.pb R / W
0032d 0x002A word Periodic time for PID control t.pcp R / W
0033d 0x0021 word Address selection for slave device. Adr5 R / W
0034d 0x0022 word Baud Rate bAud R / W
1.2 INPUT REGISTERS
Input Register

Addresses

 

Data Type

 

Data Content

 

Parameter Name

 

Read /Write Permisson

Decimal Hex
0000d 0x0000 word Measured temperature value (°C / °F) R
0001d 0x0001 word Measured humidity value (%RH) R
* Holding and Input Register parameters of type integer, those “signed integer” is defined as the decimal port of and associated with these parameters. (So,”14.0” is a parameter value of “140” will be read in). Relevant parameters for a period of “mm : ss” type ones in seconds, ”hh :mm” while those species defined in minutes.
1.3 COILS
Coil

Addresses

 

Data Type

 

Data Content

 

Parameter Name

 

Read /Write Permisson

Decimal Hex
00d 0x00 bit Temperature unit OFF=°C,ON=°F Unit R / W
01d 0x01 bit Decimal indication OFF=no, ON=YE5 D.PNt R / W
02d 0x02 bit Buzzer OFF=no, ON=YE5 5nd R / W
03d 0x03 bit Temperature control OFF = lo, ON = Relative alarm Hi t.cnt R / W
04d 0x04 bit Humidity control OFF = lo, ON = Relative alarm Hi h.cnt R / W
05d 0x05 bit Fan Control (:n Foan not active,         Y:EF5an active) F.cnt R / W
06d 0x06 bit Fan output type selection (OFF =  time, ON =  tEmp) F.tYP R / W
07d 0x07 bit Fan temperature control (OFF =  Lo, ON =  Hi) F.5tA R / W
08d 0x08 bit Rotating Control (:nRotating not active,         Y:ER5otating active) r.cnt R / W
09d 0x09 bit Temperature alarm configuration OFF = Ab5,  ON = Relative alarm rEF a.ttp R / W
010d 0x0A bit Humidity alarm configuration OFF = Ab5, ON = Relative alarm rEF a.htp R / W
011d 0x0B bit PID temperature control selection OFF = yE5, ON = no t.pid R / W
1.4 DISCRATE INPUTS
Discrate Inputs

Addresses

 

Data Type

 

Data Content

Parameter Name  

Read /Write Permisson

Decimal Hex
0000d 0x0000 bit Temperature relay output status (0=OFF; 1=ON) R
0001d 0x0001 bit Humidification relay output status (0=OFF; 1=ON) R
0002d 0x0002 bit Fan relay output status (0=OFF; 1=ON) R
0003d 0x0003 bit Right Rotating relay output status (0=OFF; 1=ON) R
0004d 0x0004 bit Left Rotating relay output status (0=OFF; 1=ON) R