EnCLEIum - Logo

SIM
INSTALLATION INSTRUCTIONS

PRODUCT SAFETY

When using electrical equipment, basic safety precautions should always be followed, including the following:

READ THESE INSTRUCTIONS BEFORE USING THIS PRODUCT.

Do not let power supply cords touch hot surfaces.
Do not mount near gas or electric heaters.
Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.
The use of accessory equipment is not recommended by Encelium as it may cause an unsafe condition.
Do not use this equipment for other than the intended use.

SAVE THESE INSTRUCTIONS.

GETTING STARTED

Overview
The Sensor Interface Module (SIM) provides an interface between sensors such as occupancy and photosensors to the GreenBusTM communication network. The SIM is automatically addressed as soon as it is connected to the Encelium Wired Manager.

The SIM is available in two models:

  • Indoor
  • Damp Rated

WIRED SYSTEM OVERVIEW

GreenBus technology makes wiring fast and error-free, since it’s intuitive to install. With Encelium X, you can control DALI devices exclusively or a mixture of GreenBus and DALI.

EnCLEIum EN-SIM-AI Sensor Interface Module - WIRED SYSTEM OVERVIEW

INSTALLATION

The SIM connects to LED drivers and electronic dimming, non-dimming, HID, etc., ballasts to make each individual device addressable and controllable.

Notes: The SIM is to be installed in dry, indoor locations ONLY. For damp installations, ensure to use the SIM (damp rated). Damp locations are defined as: interior locations subject to moderate degrees of moisture, such as some basements, some barns, some cold-storage warehouses, and the like, and partially protected locations under canopies, marquees, roofed open porches, and the like.

MOUNTING OPTION

Junction Box Mount
For some installations, a junction box may be required. It is recommended to securely mount the SIM to the junction box using an available Pg-7 (0.5 inch) trade-size knock-out and retainer nut.

EnCLEIum EN-SIM-AI Sensor Interface Module - MOUNTING OPTION

ELECTRICAL CONNECTIONS

  1. SIM to Low-Voltage Sensor or Wattstopper Wiring
    EnCLEIum EN-SIM-AI Sensor Interface Module - ELECTRICAL CONNECTIONS
  2. SIM to Sensor Junction Box Wiring
    EnCLEIum EN-SIM-AI Sensor Interface Module - ELECTRICAL CONNECTIONS 2
  3. SIM to Sensor Junction Box Wiring
    EnCLEIum EN-SIM-AI Sensor Interface Module - ELECTRICAL CONNECTIONS 3
  4. Contact Closure Wiring
    EnCLEIum EN-SIM-AI Sensor Interface Module - Contact Closure Wiring
  5. SIM Wiring
    GreenBus communication wiring is still accessible from the outside of the luminaire, while all necessary wiring to the electronic dimming ballast is available on the inside.
    The module is made from tested material to be used in plenum or “plenum rated” areas. All wiring is rated 600V, 105ºC for use in luminaires.
    To control a two ballast luminaire, parallel all ballast input wires (line, neutral and control wires purple and pink). It is recommended to use one module per ballast. Do not connect more than two ballasts in parallel.
    EnCLEIum EN-SIM-AI Sensor Interface Module - SIM Wiring Recommended relay switching capacity, 120-347V, 300VA maximum.
    Due to the internal relay, power feed to luminaire may be live even if lights are off. Turn off power at circuit breaker or fuse before installing or servicing module. Observe lockout procedures.

TROUBLESHOOTING

There are no user-serviceable parts inside. For detailed information about how to set-up, install, use, and maintain Encelium hardware and software, please visit: help.encelium.com

Copyright © 2021 Digital Lumens, Incorporated. All rights reserved. Digital Lumens, the Digital Lumens logo, We Generate Facility Wellness, SiteWorx, LightRules, Lightelligence, Encelium, the Encelium logo, Polaris, GreenBus, and any other trademark, service mark, or tradename (collectively “the Marks”) are either trademarks or registered trademarks of Digital Lumens, Inc. in the United States and/or other countries, or remain the property of their respective owners that have granted Digital Lumens, Inc. the right and license to use such Marks and/or are used herein as nominative fair use. Due to continuous improvements and innovations, specifications may change without notice.
DOC-000438-00 Rev B 12-21

EnCLEIum - Logoencelium.com

Documents / Resources

EnCLEIum EN-SIM-AI Sensor Interface Module [pdf] Instruction Manual
EN-SIM-AI, Sensor Interface Module, EN-SIM-AI Sensor Interface Module

References

Leave a comment

Your email address will not be published. Required fields are marked *