ELKO HRN-31 Multi Function Voltage Monitoring RelaysELKO logo

ELKO EP, s.r.o.
Palackého 493
769 01 Holešov, Všetuly
Czech Republic
Tel.: +420 573 514 211
e-mail: elko@elkoep.com
www.elkoep.com

Made in Czech Republic

02-67/2023

HRN-31
HRN-31/2
HRN-32/2
HRN-36
HRN-36/2
HRN-39
HRN-39/2

Multifunction voltage monitoring relays in 1P – AC/DC

ELKO - Labels


Characteristics

  • It is used to monitor the value of alternating or direct voltage in 1-phase circuits.
  • Supply voltage from monitored voltage.
  • Monitors voltage exceeding the upper voltage level (Umax) and falling below the lower voltage level (Umin) – according to the selected function.
  • Smooth adjustment of both voltage levels – the lower level Umin is set in % of the upper level Umax.
  • Adjustable time delay (to eliminate short-term voltage drops and spikes).
  • Option to select functions with fault state memory (Latch).
  • The fault state memory can be reseted by the control input (R).
  • Measures true root mean square value of the voltage – TRUE RMS.
  • Type HRN-32/2 has an independent output contact for each voltage level.
Description

HRN-31/2

ELKO HRN-31 Multi Function Voltage Monitoring Relays - a1

  1. Control input terminal (R)
  2. Indication of supply/monitored voltage
  3. Function settings
  4. Lower level setting (Umin)
  5. Supply/monitored voltage terminals (A1-A2)
  6. Indication of operating states
  7. Upper level setting (Umax)
  8. Time delay setting
  9. Output contact 2 (25-26-28), only HRN-3x/2
  10. Output contact 1 (15-16-18)
Connection

HRN-3x               HRN-3x/2

ELKO HRN-31 Multi Function Voltage Monitoring Relays - a2                ELKO HRN-31 Multi Function Voltage Monitoring Relays - a3

Indication of operating states

ELKO HRN-31 Multi Function Voltage Monitoring Relays - a4

Type of load

Contact material
AgNi, 16A

ELKO HRN-31 Multi Function Voltage Monitoring Relays - b1cos φ ≥ 0.95
AC1

250V / 16A

ELKO HRN-31 Multi Function Voltage Monitoring Relays - b2AC2

250V / 5A

ELKO HRN-31 Multi Function Voltage Monitoring Relays - b2AC3

250V / 3A

ELKO HRN-31 Multi Function Voltage Monitoring Relays - b3AC5a
uncompensated

230V / 3A (690VA)

ELKO HRN-31 Multi Function Voltage Monitoring Relays - b4AC5a
compensated

x

ELKO HRN-31 Multi Function Voltage Monitoring Relays - b5AC5b

800W

ELKO HRN-31 Multi Function Voltage Monitoring Relays - b6AC6a

x

ELKO HRN-31 Multi Function Voltage Monitoring Relays - b7AC7b

250V / 3A

ELKO HRN-31 Multi Function Voltage Monitoring Relays - b1AC12

250V / 10A

ELKO HRN-31 Multi Function Voltage Monitoring Relays - b8AC13

250V / 6A

ELKO HRN-31 Multi Function Voltage Monitoring Relays - b9AC14

250V / 6A

ELKO HRN-31 Multi Function Voltage Monitoring Relays - b10AC15

250V / 6A

ELKO HRN-31 Multi Function Voltage Monitoring Relays - b1DC1

24V / 16A

ELKO HRN-31 Multi Function Voltage Monitoring Relays - b2DC3

24V / 6A

ELKO HRN-31 Multi Function Voltage Monitoring Relays - b2DC5

24V / 4A

ELKO HRN-31 Multi Function Voltage Monitoring Relays - b1DC12

24V / 16A

ELKO HRN-31 Multi Function Voltage Monitoring Relays - b9DC13

24V / 2A

ELKO HRN-31 Multi Function Voltage Monitoring Relays - b9DC14

24V / 2A
Technical parameters

HRN-31
HRN-31/2


HRN-32/2
HRN-36
HRN-36/2

HRN-39
HRN-39/2

Supply and measuring
Supply/monitored terminals:

A1-A2

Supply/monitored voltage:

AC/DC
48 – 276 V
(AC 50-60 Hz)

AC/DC
48 – 276 V
(AC 50-60 Hz)
DC
6 – 30 V

AC/DC
24 – 150 V
(AC 50-60 Hz)

Consumption (max.):

2.5 VA/0.55 W
2.7 VA/0.65 W


2.7 VA/0.65 W
0.35 W
0.5 W

2.5 VA/0.55 W
2.7 VA/0.65 W

Upper level setting (Umax):

AC/DC
160 – 276 V

AC/DC
160 – 276 V
DC
12 – 30 V

AC/DC
80 – 150 V

Lower level setting (Umin):

30 – 95 % Umax

30 – 95 % Umax 50 – 95 % Umax

30 – 95 % Umax

Max. permanent voltage:

AC/DC 276 V

AC/DC 276 V DC 36 V

AC/DC 276 V

Peak overload (1 s):

AC/DC 290 V

AC/DC 290 V DC 48 V

AC/DC 290 V

Time delay (d):

300 ms

Time delay (t):

adjustable, 0.5 – 10 s

Accuracy
Setting accuracy (mech.):

5 % – mechanical setting

Repeat accuracy:

< 1 %

Temperature dependency:

< 0.1 %/°C (°F)

Hysteresis
(fault to OK):

5 % (functions O1, U1, W)
Umax – Umin (functions O2, U2, U3) 

Output
Contact type:

1× changeover
2× changeover

1× changeover for each level 

1× changeover
2× changeover

1× changeover
2× changeover

Contact material:

AgNi

Current rating:

16 A/AC1

Breaking capacity:

4000 VA/AC1, 384 W/DC1

Switching voltage:

250 V AC/24 V DC

Power dissipation (max.):

1.2 W

Mechanical life:

10.000.000 ops.

Electrical life (AC1):

100.000 ops.

Other information
Operating temperature:

-20 .. +55 °C (-4 .. 131 °F)

Storage temperature:

-30 .. +70 °C (-22 .. 158 °F)

Dielectric strength:

AC 4 kV (supply – output)

Operating position:

any

Mounting:

DIN rail EN 60715

Protection degree:

IP40 front panel / IP20 terminals

Overvoltage category:

III.

Pollution degree:

2

Cross-wire section – solid/stranded with ferrule (mm²):

max. 1× 2.5, 2× 1.5/
max. 1× 2.5 (AWG 14)

Dimensions:

90 × 17.6 × 64 mm (3.5″ × 0.7″ × 2.5″)

Weight:

60 g (2.11 oz)
77 g (2.72 oz)


77 g (2.72 oz)
60 g (2.11 oz)
77 g (2.72 oz)

60 g (2.11 oz)
77 g (2.72 oz)

Standards:

EN 60255-1, EN 60255-26, EN 60255-27

Warning

This device is constructed for connection in 1-phase network or direct circuit (according to the type, voltage ranges must be respected) and must be installed according to norms valid in the state of an application. Installation, connection, setting and servicing must be carried out by qualified electrician sta only, which have perfectly understood the instructions and functions. This device contains protection against overvoltage peaks and disturbing impulses in the power supply network. For the correct function of the protection of this device, there must be suitable protections of higher degrees (A,B,C) installed in front of them and according to the standards, interference of switching devices must be securely eliminated (contactors, motors, inductive loads, etc.). Before installation, make sure that the device is de-energized and the main switch is in the “OFF” position. Don`t install the device to sources of excessive electromagnetic interference. Ensure correct installation by perfect air circulation so that during continuous operation and a higher ambient temperature, the device does not exceed the maximum allowed operating temperature. For installation and setting use a screwdriver with a width of approx. 2 mm. Keep in mind that this is a fully electronic device and approach accordingly with the installation. Non-problematic function of the device is also dependent on the previous method of transportation, storage, and handling. In case of any signs of damage, deformation, malfunction, or missing parts, don`t install this device and claim it at the dealer. The product must be treated as electronic waste at the end of its life.

Functions

(O1) OVER (hysteresis 5%)

ELKO HRN-31 Multi Function Voltage Monitoring Relays - c1

(O2) OVER (hysteresis to Umin)

ELKO HRN-31 Multi Function Voltage Monitoring Relays - c2

(OL) OVER + Latch

ELKO HRN-31 Multi Function Voltage Monitoring Relays - c3

(UL) UNDER + Latch

ELKO HRN-31 Multi Function Voltage Monitoring Relays - c4

(U1) UNDER (hysteresis 5%)

ELKO HRN-31 Multi Function Voltage Monitoring Relays - c5

(U2) UNDER (hysteresis to Umax)

ELKO HRN-31 Multi Function Voltage Monitoring Relays - c6

(U3) UNDER (hysteresis to Umax)

ELKO HRN-31 Multi Function Voltage Monitoring Relays - c7

OVER:

If the value of the monitored voltage is lower than the set upper level “Umax”, the output contact is closed. If the “Umax” is exceeded, the output contact will opens after the set delay (fault state).

If the voltage falls below the fixed hysteresis (O1 function) or the set lower level “Umin” (O2 function), the output contact will closes again.

If the OL function (OVER + Latch) is selected, when the upper voltage level “Umax” is exceeded, the output contact remains open even when the voltage returns from the fault state.

Fault memory reset can be done in three ways: 

  • Short-term interruption of supply voltage 
  • Using the control input (R) 
  • By setting the function switch to position R (RESET) or any function without memory fault

The RESET state lasts for 3 s after switching the function switch from the R position to a function with a memory fault (UL, OL, WL).

When moving to any other function from the R position, this delay does not apply.

UNDER:

If the value of the monitored voltage is higher than the set lower level “Umin”, the output contact is closed. When the voltage drops below the “Umin”, output contact opens after the set delay (fault state).

If the voltage exceeds the fixed hysteresis (function U1) or the set upper level “Umax” (function U2, U3), the output contact closes again.

If the UL function (UNDER + Latch) is selected, when the voltage drops below the lower level “Umin”, the output contact remains open even when returning from the fault state. Fault memory reset can be done as in the previous case.

(W) WINDOW (hysteresis 5%)

ELKO HRN-31 Multi Function Voltage Monitoring Relays - c8

(WL) WINDOW + Latch

ELKO HRN-31 Multi Function Voltage Monitoring Relays - c9

WINDOW:

If the value of the monitored voltage is lower than upper level “Umax” and at the same time higher than lower level “Umin”, the output contact in closed. If the “Umax” is exceeded or drops below the “Umin”, output contact opens after the set delay (fault state).

To return from the fault state, a fixed hysteresis is applied.

If the WL function (WINDOW + Latch) is selected, the fault state is again stored in memory and output contact stays open, even when returning from the fault state. Fault memory reset can be done as in the previous cases.