E-FT-10 USER MANUAL

E-FT-10 device control units are designed for rail mounting and should be used in an industrial environment.

  • The package of E-FT-10 device contains;
    DeviceWarning icon
    User manual
    Guarantee certificate
  • After opening the package, please check the contents with the above list. If the delivered product is wrong type, any item is missing or there are visible defects, contact the vendor from which you purchased the product.
  • Before installing and operating the device, please read the user manual thoroughly.
  • The installation and configuration of the controller must only be performed by a person qualified in instrumentation.
  • Keep the unit away from feamable gases, that could cause explosion.
  • Do not use alcohol or other solvents to clean the device. Use a clean cloth soaked in water tightly squeezed to gently wipe the outer surface of the device.
  • The lifetime of device is 10 years.

INTRODUCTION

Elimko FT 10 Series Filter Timer -

E-FT-10 is a programmable timer which has pressure control unit, is used in filter cleaning system. Device contains a control unit and output units, that are controlled by control unit. Control unit controls the output units on communication line. Operating and selonoid voltages of output units are supplied from control unit. Control unit has 8 outputs, each output unit has up to 16 outputs. Outputs can switch maximum 250 VAC, 1A. Device has 2 alarm relays. These relays can give an alarm to user, if any problem exists on output selonoids. RS-485 communication line on the device works according to Modbus protocol. Configuration parameters and error messages can also be viewed using Modbus. Outputs scanning order is configured by comminucation line.
Device has 2 different kind of pressure input according to device type code, that is explained in
1.1 TYPE CODING
If U (TYPE CODING) is selected as “1”, pressure inputs are connected on quick connect, that is shown as LO and HI on the front panel. In this case, differential pressure is measured by internal pressure sensor. If U (TYPE CODING) is selected as “2”, an analog signal (current or voltage) is connected to analog input of device. In these two different situation, pressure value is shown on display, retransmitted on analog output. Device can perform ON/OFF or proportional control according to pressure value. These control
methods are explained in 4.1 CONTROL TYPES .
1.1. TYPE CODING

Elimko FT 10 Series Filter Timer - TYPE CODING

(1) Pressure sensor of device works in 7kPa range. If pressure control is selected as analog input, input type and input range must be defined on order.
(2) When X is selected as “1” (Solenoid Voltage Yes) than Y must be selected as “1”. When X is selected as “1” factory default is 24 VDC.
1.2. TECHNICAL SPECIFICATION

Operating Voltage 85-265 V AC / 85-375 V DC 20-60 V AC / 20-85 V DC
Display Type 2×4 digit 10 mm 7 segment display
Alarm Outputs Relay: SPST-NO 250 V AC, 3 A
Retransmission Output Current: 0-20 mA, 4-20 mA (isolated)
Relay Outputs Minimum 8 Relays, maximum 128 Relays SPST-NO 250 V AC, 1 A
Relay Mechanical Life 10 000 000 operation
Relay Electrical Life Almost same as mechanical life, because the switching is made with semiconductor.
Control Type On/Off, Proportional(P)
Power Consumption 7W (10 VA)
Operating Temperature 0 °C, +55 tC (With no condensation or icing)
Storage Temperature -25 °C, +55 °C (With no condensation or icing)
Memory EEPROM max. 10000 writing
Weight 400 g

1.3. DIMENSIONS

Elimko FT 10 Series Filter Timer - DIMENSIONS

CONNECTION DIAGRAMS

2.1. CONTROL UNIT CONNECTION DIAGRAM

Elimko FT 10 Series Filter Timer - CONNECTION DIAGRAMS

 

  • A21 and A22 (+VSUP-) terminals are power supply of output units and are connected to A2 and A3 terminals of output units. A23 (DATA) terminal is data line of output units, and are connected to A1 terminal of output units. These terminals must be connected in order to power output units.
  • Selonoids supply voltage must be connected B9 and B10 (+VSIN-) terminals.
  • B11 and B12 (-VOUT+) terminals must be connected to B5 and B6 (+VIN-) terminals of output units for selonoid supply voltage on output units. If these terminals are not connected, all of selonoids on output units are open circuit, so device gives alarm and selonoids are not powered.
  • Alarm1 and Alarm2 give alarm according to different alarm source, that is explained 4.2 ALARM RELAYS.

2.2. OUTPUT UNIT CONNECTION DIAGRAM

Elimko FT 10 Series Filter Timer - OUTPUT UNIT CONNECTION DIAGRAM

  • Control Unit A1-A3, B9-B28, output unit A7-A18, B5-B18 terminals have dangerous voltage. While device is powered, never touch to these terminalsWarning icon .
  • Before operating the device, ensure that the device is correctly configured. Incorrect configuration could result malfunction.

3. USAGE
E-FT-10 front panel image is shown in 1.INTRODUCTION part. RL1 led lights when Relay1 (RL1) is powered, led lights when Relay2 RL2 (RL2) is powered, led lights when any selonoid output is powered, OUT and led lights during configuration mode. During normal operation page, active group number (XX) is shown on the top display like as ( XX), and active output number (YYY) is shown on the bottom display like as ( YYY). During normal operation page, button is used for displaying PR Gr O ENTER SETL differential pressure and set values and changing set values. While and parameters are shown,Elimko FT 10 Series Filter Timer - icon1 and Elimko FT 10 Series Filter Timer - icon2buttons change SETH PRG the set values Elimko FT 10 Series Filter Timer - icon1 and Elimko FT 10 Series Filter Timer - icon2 button reverts to the normal operation page. During normal operation page, if and buttons are pressed together, error message display is opened. During error message display, button is used for scanning outputs that have an error, button reverts to the normal operation page. Except the normal operation page, if any button isn’t pressed for more than 25 seconds, device reverts to normal operation page automatically. Configuration page is opened to configure other parameters of device. ENTER PRG

  • Pressing PRG button for more over 2 seconds enters the configuration page.
  • When the configuration page is entered, COD message is shown on the top display and is shown on the bottom display. Security code must be entered correctly to configure the parameters. If the security code is entered incorrectly, parameters are showned, but parameters can not be changed.
  • Factory setting of the security code Elimko FT 10 Series Filter Timer - icon1 and Elimko FT 10 Series Filter Timer - icon2. The security code can be changed with SCOD parameter. If the security code is forgotten, repower the device and pressing , and buttons together ENTER with in 1 minute after start up. After that security code control isn’t made one time to enter configuration page, so the security code can be changed with SCOD parameter.
  • When the security code is entered correctly, pressing ENTER button enters the configuration pages.
  • During configuration pages, Elimko FT 10 Series Filter Timer - icon1 and Elimko FT 10 Series Filter Timer - icon2 buttons select pages, button enters to the selected page,  NTER button reverts to normal PRG operation page.
  • While in configuration pages, ENTER button selects parameters Elimko FT 10 Series Filter Timer - icon1 and Elimko FT 10 Series Filter Timer - icon2 buttons change the value of parameters, button is pressed for more over 1 second for revert to configuration pages display, PRG button reverts to normal operation page.

NOTE : Error Message Display (see 3.2 DISPLAY FIGURES )

Elimko FT 10 Series Filter Timer - During Alarm

3.1. PARAMETERS EXPLANATIONS

Elimko FT 10 Series Filter Timer - PARAMETERS

Elimko FT 10 Series Filter Timer - icon3 :Differential pressure value.
Elimko FT 10 Series Filter Timer - icon4 : Differential pressure value low set value. Parameter can be set between -1999 and SETH .
Elimko FT 10 Series Filter Timer - icon5 :Differential pressure value high set value. Parameter can be set between Elimko FT 10 Series Filter Timer - icon4and 9999.
Elimko FT 10 Series Filter Timer - icon6 :Differential pressure value alarm set value. Parameter can be set between -1999 and 9999.
Elimko FT 10 Series Filter Timer - icon7 :Security code value for setting parameters. Security code enters between 0 and 9999.
Parameters of Elimko FT 10 Series Filter Timer - icon8Page
Elimko FT 10 Series Filter Timer - icon10 Control Type. Parameter can set Elimko FT 10 Series Filter Timer - icon9 (Refer to 4.1. CONTROL TYPES )
Elimko FT 10 Series Filter Timer - icon11 : Decimal point of differential pressure. Parameter can be set between 0 and 3.
Elimko FT 10 Series Filter Timer - icon12 :Analog output retransmission low level. Parameter can be set between -1999 and 9999.
Elimko FT 10 Series Filter Timer - icon13 :Analog output retransmission high level. Parameter can be set between -1999 and 9999.
Elimko FT 10 Series Filter Timer - icon16 :Analog output retransmission current range. Parameter can be set Elimko FT 10 Series Filter Timer - icon15
Elimko FT 10 Series Filter Timer - icon16: Differential pressure offset value. According to that paramater, differential pressure value has positiveor negative offset. Parameter can be set between -1999 and 9999.
Elimko FT 10 Series Filter Timer - icon17 : Hysterisis value of differential pressure alarm set value (Elimko FT 10 Series Filter Timer - icon6 ). Parameter can be set between 0 and 9999.
Elimko FT 10 Series Filter Timer - icon19 :Alarm type of RL1 alarm relay. Parameter can be set Elimko FT 10 Series Filter Timer - icon20 .(see Table 4)
Elimko FT 10 Series Filter Timer - icon21 :Alarm function of RL1 alarm relay. Parameter can be set between 0 and 15. (see 4.2 ALARM RELAYS)
Elimko FT 10 Series Filter Timer - icon22 :When Elimko FT 10 Series Filter Timer - icon22 is selected , in case of an alarm, user must acknowledge the alarm by pressing Elimko FT 10 Series Filter Timer - icon1 and Elimko FT 10 Series Filter Timer - icon2 buttons in order to deactivate alarm output. Parameter can be set Elimko FT 10 Series Filter Timer - icon36 or Elimko FT 10 Series Filter Timer - icon23.
Elimko FT 10 Series Filter Timer - icon156:Alarm type of RL2 alarm relay. Parameter can be set or Elimko FT 10 Series Filter Timer - icon111 .(see Table 4)
Elimko FT 10 Series Filter Timer - icon110 :Alarm function of RL2 alarm relay. Parameter can be set between 0 and 15. (see 4.2 ALARM RELAYS)
Elimko FT 10 Series Filter Timer - icon159: When Elimko FT 10 Series Filter Timer - icon159 is selected , in case of an alarm, user must acknowledge the alarm by ON pressing Elimko FT 10 Series Filter Timer - icon1 and Elimko FT 10 Series Filter Timer - icon2 buttons in order to deactivate alarm output.Parameter can be set Elimko FT 10 Series Filter Timer - icon36 or Elimko FT 10 Series Filter Timer - icon23.
Elimko FT 10 Series Filter Timer - icon24 : Selonoid outputs break time. This parameter determines the break time between two outputs. Parameter can be set between 0.1 and 999.9 in seconds.
Elimko FT 10 Series Filter Timer - icon25 : Selonoid outputs pulse time. This parameter determines the pulse time of each outputs. Parameter can be set between 0.1 and 100.0 in seconds.
Elimko FT 10 Series Filter Timer - icon26  : Selonoid outputs group break time. While Elimko FT 10 Series Filter Timer - icon27parameter is higher than “1”, this parameter determines the break time between each group. Parameter can be set between 0.1 and 999.9 in seconds.
Elimko FT 10 Series Filter Timer - icon77 : Selonoid outputs waiting time. This parameter determines waiting time, after all outputs are powered. Parameter can be set between 0.1 and 999.9 in seconds.
Elimko FT 10 Series Filter Timer - icon28 : Number of outputs. This parameter determines the number of outputs. Parameter can be set between 1 and 128.
Elimko FT 10 Series Filter Timer - icon27 : Number of groups. This parameter determines number of groups while filtering is done with different groups. Parameter can be set between 1 and 16. If this parameter set “1”, filtering is done only one group.
Elimko FT 10 Series Filter Timer - icon29 : Type of group operation. Parameter can be selected Elimko FT 10 Series Filter Timer - icon30and Elimko FT 10 Series Filter Timer - icon31
Elimko FT 10 Series Filter Timer - icon32 : Number of selonoids scanning after deactivation of start input. Parameter can be set between 0 and 50.
Elimko FT 10 Series Filter Timer - icon33 : Low limit of internal impedance of selonoids. If the impedance measurement of selonoids are lower than that value, device gives a short circuit alarm. Parameter can be set between 0.00 k Ω and Elimko FT 10 Series Filter Timer - icon34. If this parameter set to “0″ the device dosen’t control short circuit.
Elimko FT 10 Series Filter Timer - icon34 : High limit of internal impedance of selonoids. If the impedance measurement of selonoids are higher than that value, device gives an open circuit alarm. Parameter can be set between Elimko FT 10 Series Filter Timer - icon33and 30.00 kΩ
Elimko FT 10 Series Filter Timer - icon35: When Elimko FT 10 Series Filter Timer - icon35is selected as Off , faulty selonoids are skipped immediately, and when Elimko FT 10 Series Filter Timer - icon35is selected as , all the timings work as usual. Parameter can be set or Elimko FT 10 Series Filter Timer - icon36 ON Elimko FT 10 Series Filter Timer - icon23
Elimko FT 10 Series Filter Timer - icon37 : Communication baud rate. Parameter can be set Elimko FT 10 Series Filter Timer - icon38 k Baud. Baud rate of all devices in same communication line should be the same as baud rate of master device.
Elimko FT 10 Series Filter Timer - icon39 : Communication parity. Parameter can be set Elimko FT 10 Series Filter Timer - icon41  . Parity of all devices in same communication line should be the same as parity of master device.
Elimko FT 10 Series Filter Timer - icon40 : Communication address. Parameter can be set between 1 and 127. All device in same communication line should have an unique address.
Parameters of Elimko FT 10 Series Filter Timer - icon42Page
Elimko FT 10 Series Filter Timer - icon43 : Filter value of differential pressure value. This parameter determines the number of samples to be averaged for calculation of differential pressure value. Parameter can be set between 1 and 16.
Elimko FT 10 Series Filter Timer - icon44 : 0 Ohm calibration value of selenoid resistance measurument. This parameter isn’t advised to change. Selonoid supply voltage that is connected to B9 and B10 terminals is broken. B11 and B12 terminals are done short-circuit Elimko FT 10 Series Filter Timer - icon1 and Elimko FT 10 Series Filter Timer - icon2 buttons press together in order to save value.
Elimko FT 10 Series Filter Timer - icon45 : 1000 Ohm calibration value of selonoid resistance measurument. This parameter isn’t advised to change. Selonoid supply voltage that is connected to B9 and B10 terminals is broken. 1000 ohm resistance is connected to B11 and B12 terminals. Elimko FT 10 Series Filter Timer - icon1 and Elimko FT 10 Series Filter Timer - icon2 buttons press together in order to save value.
Elimko FT 10 Series Filter Timer - icon46 : This parameter determines pressure value of low calibration of pressure input. Parameter can be set between -1999 and 9999.
Elimko FT 10 Series Filter Timer - icon47 : Zero calibration value of differential pressure. This parameter isn’t advised to change. ZERO value differential pressure is applied to differential pressure input of device Elimko FT 10 Series Filter Timer - icon1 and Elimko FT 10 Series Filter Timer - icon2 buttons press together, in order to save value.
Parameters of Elimko FT 10 Series Filter Timer - icon49 Page (continuation)
Elimko FT 10 Series Filter Timer - icon50 : This parameter determines pressure value of high calibration of pressure input. Parameter can be set between -1999 and 9999.
Elimko FT 10 Series Filter Timer - icon51 : Span calibration value of differential pressure. This parameter isn’t advised to change. SPAN value differential pressure is applied to differential pressure input of device  Elimko FT 10 Series Filter Timer - icon1 and Elimko FT 10 Series Filter Timer - icon2 buttons press together, in order to save value.
Elimko FT 10 Series Filter Timer - icon53 : Analog output 4 mA calibration value. This parameter isn’t advised to change. Connect an ampermeter A27(-) and A28(+) terminals. While the parameter is selected, adjust the parameter with Elimko FT 10 Series Filter Timer - icon1 and Elimko FT 10 Series Filter Timer - icon2 buttons value until the meter reading is equal to 4 mA.
Elimko FT 10 Series Filter Timer - icon54 : Analog output 20 mA calibration value. This parameter isn’t advised to change. Connect an ampermeter A27(-) and A28(+) terminals. While the parameter is selected, adjust the parameter with Elimko FT 10 Series Filter Timer - icon1 and Elimko FT 10 Series Filter Timer - icon2  buttons value until the meter reading is equal to 20 mA.
Elimko FT 10 Series Filter Timer - icon55: Security code.
Parameters of Elimko FT 10 Series Filter Timer - icon56 Page
The parameters between Elimko FT 10 Series Filter Timer - icon57 and Elimko FT 10 Series Filter Timer - icon58 are used to determine the count of output on the connected output cards. The output  cards are produced 8 or 16 outputs in manufacturing period. These parameters are used to define the count of outputs to device.These parameters are set to or Elimko FT 10 Series Filter Timer - icon59 or Elimko FT 10 Series Filter Timer - icon60.
3.2. DISPLAY FIGURES

Normal Operating Display Error Messages Display
Elimko FT 10 Series Filter Timer - icon61 1. Group 15. Output Elimko FT 10 Series Filter Timer - icon66 No Selonoid Voltage
Elimko FT 10 Series Filter Timer - icon62 3. Group 8. Output Elimko FT 10 Series Filter Timer - icon67 Selonoid on Output 2
Short Circuit
Elimko FT 10 Series Filter Timer - icon63 3. Group Break Time Elimko FT 10 Series Filter Timer - icon68 Selonoid on Output 13
Open Circuit
Elimko FT 10 Series Filter Timer - icon64 Waiting Time Elimko FT 10 Series Filter Timer - icon69 High Pressure Alarm
Elimko FT 10 Series Filter Timer - icon65 Wait Start Input Elimko FT 10 Series Filter Timer - icon70 No Alarm

WORKING PRINCIPLES

When Elimko FT 10 Series Filter Timer - icon71 parameter is equal to “1”, Starting of scanning  selonoids, device waits for Elimko FT 10 Series Filter Timer - icon72 break time, after that O1 output is activated. This output is active for Elimko FT 10 Series Filter Timer - icon73 pulse time, after that O1 output is deactivated. Device waits Elimko FT 10 Series Filter Timer - icon74 break time and same process repeats with the next selonoid. This process continues until number of outputs reach to Elimko FT 10 Series Filter Timer - icon75parameter. When last output is deactivated at the end of Elimko FT 10 Series Filter Timer - icon73 pulse time, device starts to waiting time. After waiting that time, Elimko FT 10 Series Filter Timer - icon78 break time is started and O1 output is activated at the end of Elimko FT 10 Series Filter Timer - icon78 break time and repeats same process.
If start input of device is active, this process continues. After deactivation of start input, the device repeats this process for Elimko FT 10 Series Filter Timer - icon80 times and stop the process.
First of 8 outputs is used on the control unit. Output units must be used for more than 8 outputs.

Elimko FT 10 Series Filter Timer - Working diagram

In case the device Elimko FT 10 Series Filter Timer - icon98 parameter is greater than 1, 2 different operating type is available. This operating type is determined by the Elimko FT 10 Series Filter Timer - icon83 parameter. In applications where the number of groups is greater than 1, the group 1 output card is used as the selection card.
When the Elimko FT 10 Series Filter Timer - icon83 parameter is set to Elimko FT 10 Series Filter Timer - icon30, the device works as shown in .
Figure 4.2 When scanning starts, O1 output of group card is energized and 1st Group is selected. Elimko FT 10 Series Filter Timer - icon73 break time is started. O1 output of the device is energized at the end of the break time period and the Elimko FT 10 Series Filter Timer - icon76 pulse time is started. At the end of the pulse time period, O1 is de-energized and Elimko FT 10 Series Filter Timer - icon79 break time is started again and the same operation is repeated until the number of output reaches the value of  parameter. When the last output is de-energized, O1 output of the group card is de-energized togetherly. group waiting time is started. At the end of the group waiting time period, the O2 output of the Elimko FT 10 Series Filter Timer - icon96 group card is energized and the 2nd Group is selected. The operations in the 1st group are repeated exactly. this group operations is repeated until the number of group reaches the value of Elimko FT 10 Series Filter Timer - icon81 parameter. At the end of the last group operation, Elimko FT 10 Series Filter Timer - icon90 waiting time period starts. After the waiting time period, 1st group is selected again and same operations are repeated.

Elimko FT 10 Series Filter Timer - Working diagram1

When the Elimko FT 10 Series Filter Timer - icon82parameter is set to Elimko FT 10 Series Filter Timer - icon30, the device works as shown in
Figure 4.3 . When scanning starts, O1 output of group card is energized and 1st group is selected. Elimko FT 10 Series Filter Timer - icon24 break time is started. O1 output of the device is energized at the end of the Elimko FT 10 Series Filter Timer - icon72 break time period and the pulse time is started. At the end of the Elimko FT 10 Series Filter Timer - icon76 pulse time period, O1 is de-energized and break time is started again and the same operation is repeated until the number of output reaches the value of parameter. When the last output is de-energized, O1 output of the group card is de-energized togetherly. group waiting time is started. At the end of the Elimko FT 10 Series Filter Timer - icon26 group waiting time period, the O2 output of the group card is energized and the 2nd group is selected. The outputs of 2nd group starts from where the last output of 1st group, and scanning operation is repeated until the number of output reaches the value of Elimko FT 10 Series Filter Timer - icon27 parameter. As seen in the example, the last output of 1st group is energized O3 output, and the first output of 2nd group is energized O4 output. This group operations is repeated until the number of group reaches the value of parameter. At the end of the last group operation, Elimko FT 10 Series Filter Timer - icon77 waiting time period starts. After the waiting time period, 1st group is selected again and same operations are repeated.

Elimko FT 10 Series Filter Timer - Working diagram2

If start input of device is active, this process continues. After deactivation of start input, device repeats this process for Elimko FT 10 Series Filter Timer - icon100times and stop the process.
First of 8 outputs is used on control unit. Output units must be used for more than 8 outputs. One output unit is used to group selection unit. Selonoid supply of group selection unit (+VIN-) is connected to control unit (+VSIN-) terminal.
4.1. CONTROL TYPES
Elimko FT 10 Series Filter Timer - icon101  parameter determines control type of the device, is selected as Elimko FT 10 Series Filter Timer - icon9
If Elimko FT 10 Series Filter Timer - icon101 parameter is selected as Elimko FT 10 Series Filter Timer - icon179 , device doesn’t do any control during Elimko FT 10 Series Filter Timer - icon99 waiting times. Entire of Elimko FT 10 Series Filter Timer - icon99 waiting time is waited.
If Elimko FT 10 Series Filter Timer - icon101parameter is selected as Elimko FT 10 Series Filter Timer - icon180 , if differential pressure value is higher than Elimko FT 10 Series Filter Timer - icon106 parameter, waiting time is skipped during Elimko FT 10 Series Filter Timer - icon107  the process. If differential pressure value is lower than parameter, Entire of Elimko FT 10 Series Filter Timer - icon99 waiting time is waited during the process. If differential pressure value is between Elimko FT 10 Series Filter Timer - icon107 and Elimko FT 10 Series Filter Timer - icon106parameters, device does the same as previous scanning.

Elimko FT 10 Series Filter Timer - Working diagram3

If Elimko FT 10 Series Filter Timer - icon103 parameter is selected as Elimko FT 10 Series Filter Timer - icon108 , if differential pressure value is higher than Elimko FT 10 Series Filter Timer - icon106 parameter, Elimko FT 10 Series Filter Timer - icon99 waiting time is skipped  Elimko FT 10 Series Filter Timer - icon107  during the process. If differential pressure value is lower than parameter, Entire of Elimko FT 10 Series Filter Timer - icon99 waiting time is waited during the  rocess. If differential pressure value is between Elimko FT 10 Series Filter Timer - icon107 and Elimko FT 10 Series Filter Timer - icon106 parameters, Elimko FT 10 Series Filter Timer - icon99 waiting time is set between 0 and Elimko FT 10 Series Filter Timer - icon99 proportionally.

Elimko FT 10 Series Filter Timer - Working diagram4

4.2. ALARM RELAYS

Rl1 and RL2 are alarm relays, that give alarm according to one or more than one alarm source. Alarm type of these relays are adjusted as normally open or normally closed.
Device gives alarm in case of break selonoid supply, open or short selonoids and high differential pressure value. These alarm sources are adjusted for both of the relays with Elimko FT 10 Series Filter Timer - icon109and Elimko FT 10 Series Filter Timer - icon110 parameters, like as Table 4.2 . Alarm types of relays, that is Elimko FT 10 Series Filter Timer - icon36 normally open and Elimko FT 10 Series Filter Timer - icon111 normally closed are adjusted for both of the relays with Elimko FT 10 Series Filter Timer - icon112 and Elimko FT 10 Series Filter Timer - icon156 parameters, like as Table 4.1
When alarm relays are powered, user can acknowledge the alarm and deactivate the alarm relay according to Elimko FT 10 Series Filter Timer - icon154and Elimko FT 10 Series Filter Timer - icon159 parameters. If these parameters are selected , user open error message page and deactivates relay, but led of relay continues to light. In this situation, error message of alarm is shown in error message page. Led of relay fades after alarm state. If these parameters are selected Elimko FT 10 Series Filter Timer - icon23 , relay and led deactivates after the alarm state ends.
Elimko FT 10 Series Filter Timer - Alarm Types

Elimko FT 10 Series Filter Timer - icon116 Explanations
(SC: Short Circuit,
OC: Open Circuit,
HP: High Pressure,
NSS: No Selonoid Supply, SA: Scan Active)
Elimko FT 10 Series Filter Timer - icon116 Explanations
(SC: Short Circuit,
OC: Open Circuit,
HP: High Pressure,
NSS: No Selonoid Supply SA: Scan Active)
0 No Alarm 16 SA
1 SC 17 SA/SC
2 OC 18 SA/ OC
3 SC/OC 19 SA/OC/SC
4 HP 20 SA/ HP
5 HP/SC 21 SA/HP/SC
6 HP/OC 22 SA/HP/OC
7 HP/OC/SC 23 SA/HP/OC/SC
8 NSS 24 SA/NSS
9 NSS/SC 25 SA/NSS/SC
10 NSS/OC 26 SA/NSS/OC
11 NSS/ OC /SC 27 SA/NSS/OC/SC
12 NSS/HP 28 SA/NSS/HP
13 NSS/ HP/SC 29 SA/NSS/HP/SC
14 NSS/HP/OC 30 SA/NSS/HP/OC
15 NSS / HP / OC/ SC 31 SA/NSS/HP/OC/SC

Table 4.2. Alarm Sources
4.2.1. OPEN / SHORT CIRCUIT ALARM

Device can give alarm, while short or open circuit happen on selonids. Device measures the selonoid line and controls any error on the selonoid line, before device powers the selonoids. If any error is occured on selonoid, device doesn’t power the selonoid and gives alarm, so that outputs of device don’t need any fuses. In the selonoids scanning, while the selonoid has any problem, device works differently according to Elimko FT 10 Series Filter Timer - icon170 parameter.
If parameter is selected Elimko FT 10 Series Filter Timer - icon36 , device waits Elimko FT 10 Series Filter Timer - icon72 and Elimko FT 10 Series Filter Timer - icon73 timing for that selonoid, but output doesn’t powered. If the parameter is selected Elimko FT 10 Series Filter Timer - icon23 , device doesn’t wait Elimko FT 10 Series Filter Timer - icon74 and Elimko FT 10 Series Filter Timer - icon73 timing, and continues next output. Elimko FT 10 Series Filter Timer - icon118 parameter determines open circuit state, Elimko FT 10 Series Filter Timer - icon119 parameter determines short circuit state. Elimko FT 10 Series Filter Timer - icon119 parameter should be set to half of the nominal resistance of the selonoids,Elimko FT 10 Series Filter Timer - icon118  parameter should be set to two times of the nominal resistance of the selonoids.
4.2.2. HIGH PRESSURE ALARM
Device, that has pressure control gives high pressure alarm according to Elimko FT 10 Series Filter Timer - icon120 and Elimko FT 10 Series Filter Timer - icon121 parameters. If differential pressure is higher than Elimko FT 10 Series Filter Timer - icon120parameter, device gives high pressure alarm. The alarm condition ends when the differential pressure reading decrease to Elimko FT 10 Series Filter Timer - icon120 – Elimko FT 10 Series Filter Timer - icon121 .
4.2.3. NO SELONOID SUPPLY ALARM
If Selonoid supply of device, that is connected (+VSIN-) terminals is broken, device gives no selonoid supply alarm.
4.2.4. SCAN ACTIVE ALARM
When Start input of device that is in A24 (IN1) terminal is active, the device gives scan active alarm.
All of these alarms is shown on display to user. In addition, if device has RS-485 communication, the alarms can be read from Modbus protocol.
4.3. SCANNING ORDER OF OUTPUTS
Scanning order of the device starts with 1, and ends with 128 in factory settings. The scanning order can be configured using Modbus protocol. Register addresses of these order parameters are shown in Table 4.3

Address Parameter Property Address Parameter Property
100 OUT 1-2 R/W 132 OUT 65-66 R/W
101 OUT 3-4 RAN 133 OUT 67-68 R/W
102 OUT 5-6 R/W 134 OUT 69-70 R/W
103 OUT 7-8 R/W 135 OUT 71-72 R/W
104 OUT 9-10 R/W 136 OUT 73-74 R/W
105 OUT 11-12 RIW 137 OUT 75-76 R/W
106 OUT 13-14 R/W 138 OUT 77-78 R/W
107 OUT 15-16 R/W 139 OUT 79-80 R/W
108 OUT 17-18 R/W 140 OUT 81-82 R/W
109 OUT 19-20 RAN 141 OUT 83-84 R/W
110 OUT 21-22 R/W 142 OUT 85-86 R/W
111 OUT 23-24 R/W 143 OUT 87-88 R/W
112 OUT 25-26 R/W 144 OUT 89-90 R/W
113 OUT 27-28 R/W 145 OUT 91-92 R/W
114 OUT 29-30 R/W 146 OUT 93-94 R/W
115 OUT 31-32 R/W 147 OUT 95-96 R/W
116 OUT 33-34 R/W 148 OUT 97-98 R/W
117 OUT 35-36 R/W 149 OUT 99-100 R/W
118 OUT 37-38 R/W 150 OUT 101-102 R/W
119 OUT 39-40 R/W 151 OUT 103-104 R/W
120 OUT 41-42 R/W 152 OUT 105-106 R/W
121 OUT 43-44 R/W 153 OUT 107-108 R/W
122 OUT 45-46 R/W 154 OUT 109-110 R/W
123 OUT 47-48 R/W 155 OUT 111-112 R/W
124 OUT 49-50 R/W 156 OUT 113-114 R/W
125 OUT 51-52 R/W 157 OUT 115-116 R/W
126 OUT 53-54 R/W 158 OUT 117-118 R/W
127 OUT 55-56 R/W 159 OUT 119-120 R/W
128 OUT 57-58 R/W 160 OUT 121-122 R/W
129 OUT 59-60 R/W 161 OUT 123-124 R/W
130 OUT 61-62 R/W 162 OUT 125-126 R/W
131 OUT 63-64 R/W 163 OUT 127-128 R/W

Tablo 4.3. Output Configuration Parameters Modbus Address Table
NOTE1: Parameters, that shown in Table 4.3 are 16-bits. For example low 8-bits of OUT1-2 parameter shows first output, high 8-bit of OUT1-2 parameter shows second output. In below example, output 5 is powered firstly, output3 is powered secondly according to OUT1-2 parameter. Other parameters are configured the same method.

OUT1-2 = 773
son 8-bit = 3 ilk 8-bit = 5

NOTE2: Low and High 8-bits of parameters must be set between 1 and 128. Otherwise, sent values of these parameters aren’t saved according to protocol.

OUTPUT UNITS

Each output unit has 16 outputs. Output units communicate with control unit over DATA terminal. If this connection breaks, output unit doesn’t work. Power supply of output units are supplied with (+VSUP-) terminals. Each output unit, that is connected to control unit has an address. These adresses are configured via jumpers on output unit cards. More than one unit mustn’t have same adresses. Jumper configuration of addresses are shown in . Table 5.1
(+VIN-) terminals of output units must be connected to (-VOUT+) terminals of control unit. If any problem on that connection occurs, all of the selonoids are measured open circuit and any output isn’t powered. If filtering system has more than one group, one output unit must be used for group selction unit. Selonoid supply of this unit must be connected (+VSIN-) terminals of control unit.

Jumper Explanations Jumper Explanations
Elimko FT 10 Series Filter Timer - icon122 1. Output Card Elimko FT 10 Series Filter Timer - icon130 9. Output Card
Elimko FT 10 Series Filter Timer - icon123 2. Output Card Elimko FT 10 Series Filter Timer - icon131 10. Output Card
Elimko FT 10 Series Filter Timer - icon124 3. Output Card Elimko FT 10 Series Filter Timer - icon132 11. Output Card
Elimko FT 10 Series Filter Timer - icon125 4. Output Card Elimko FT 10 Series Filter Timer - icon133 12. Output Card
Elimko FT 10 Series Filter Timer - icon126 5. Output Card Elimko FT 10 Series Filter Timer - icon134 13. Output Card
Elimko FT 10 Series Filter Timer - icon127 6. Output Card Elimko FT 10 Series Filter Timer - icon135 14. Output Card
Elimko FT 10 Series Filter Timer - icon128 7. Output Card Elimko FT 10 Series Filter Timer - icon136 15. Output Card
Elimko FT 10 Series Filter Timer - icon129 8. cikic Karti Elimko FT 10 Series Filter Timer - icon137 Group Selection Card

Table 5.1. Configurations of Jumper

COMMUNICATION ADRESSES

Address Parameter Explanation Property Min. Max.
0 Alarm Data 1 See Table1 R
1 Alarm Data 2 See Table1 R
2 Alarm Data 3 See Table1 R
3 Alarm Data 4 See Table1 R
4 Alarm Data 5 See Table1 R
5 Alarm Data 6 See Table1 R
6 Alarm Data 7 See Table1 R
7 Alarm Data 8 See Table1 R
8 Alarm Data 9 See Table1 R
9 Alarm Data 10 See Table1 R
10 Alarm Data 11 See Table1 R
11 Alarm Data 12 See Table1 R
12 Alarm Data 13 See Table1 R
13 Alarm Data 14 See Table1 R
14 Alarm Data 15 See Table1 R
15 Alarm Data 16 See Table1 R
16 Alarm Data 17 See NOTE2 R
17 Elimko FT 10 Series Filter Timer - icon3 R
18 Elimko FT 10 Series Filter Timer - icon4 R/W -1999 SE H
19 Elimko FT 10 Series Filter Timer - icon5 R/W SE L 9999
20 Elimko FT 10 Series Filter Timer - icon6 R/W -1999 9999
21 Elimko FT 10 Series Filter Timer - icon178 Elimko FT 10 Series Filter Timer - icon143  

R/W

 

0

 

2

22 Elimko FT 10 Series Filter Timer - icon11 R/W 0 3
23 Elimko FT 10 Series Filter Timer - icon145 R/W -1999 9999
24 Elimko FT 10 Series Filter Timer - icon146 R/W -1999 9999
25 Elimko FT 10 Series Filter Timer - icon148 R/W 0 3
26 Elimko FT 10 Series Filter Timer - icon149 R/W -1999 9999
27 Elimko FT 10 Series Filter Timer - icon150 R/W 0 9999
28 Elimko FT 10 Series Filter Timer - icon151 Elimko FT 10 Series Filter Timer - icon152 R/W 0 1
29 Elimko FT 10 Series Filter Timer - icon153 R/W 0 15
30 Elimko FT 10 Series Filter Timer - icon154 Elimko FT 10 Series Filter Timer - icon155 R/W 0 1
31 Elimko FT 10 Series Filter Timer - icon156 Elimko FT 10 Series Filter Timer - icon157 R/W 0 1
32 Elimko FT 10 Series Filter Timer - icon158 R/W 0 15
33 Elimko FT 10 Series Filter Timer - icon159 Elimko FT 10 Series Filter Timer - icon160 R/W 0 1
34 Elimko FT 10 Series Filter Timer - icon161 R/W 1 9999
35 Elimko FT 10 Series Filter Timer - icon162 R/W 1 1000
36 Elimko FT 10 Series Filter Timer - icon163 R/W 1 9999
37 Elimko FT 10 Series Filter Timer - icon164 R/W 1 9999
38 Elimko FT 10 Series Filter Timer - icon165 R/W 1 128
39 Elimko FT 10 Series Filter Timer - icon166 R/W 1 16
40 Elimko FT 10 Series Filter Timer - icon167 R/W 0 50
41 Elimko FT 10 Series Filter Timer - icon168 R/W 0 OU H
42 Elimko FT 10 Series Filter Timer - icon169 R/W OU L 3000
43 Elimko FT 10 Series Filter Timer - icon170 Elimko FT 10 Series Filter Timer - icon171 R/W 0 1
 

44

Elimko FT 10 Series Filter Timer - icon172 Elimko FT 10 Series Filter Timer - icon173  

R/W

 

0

 

3

45 Elimko FT 10 Series Filter Timer - icon174 Elimko FT 10 Series Filter Timer - icon175  

R/W

 

0

 

2

46 Elimko FT 10 Series Filter Timer - icon176 R/W 1 127
47 Elimko FT 10 Series Filter Timer - icon177 R/W 1 16

NOTE1: Device supports 03, 06 and 16 number function of modbus protocol. 03 Read Holding Registers, 06 Write Single Register and 16 Write Multiple Registers.
NOTE2: No Selonoid Voltage alarm is saved in first bit of Alarm Data 17, high pressure alarm is saved in second bit of Alarm Data 17.
NOTE3: In table, parameters, whose address is between 17 and 47 is explained in 3.1 PARAMETERS EXPLANATION.

TABLES

Table1: Bits of Alarm Data

S O S O S O S O S O S O S O S O
Bit Number 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Alarm Data 1 O8 O7 O6 O5 O4 O3 O2 O1
Alarm Data 2 O16 O15 O14 O13 O12 O11 O10 O9
Alarm Data 3 O24 O23 O22 O21 O20 O19 O18 O17
Alarm Data 4 O32 O31 O30 O29 O28 O27 O26 O25
Alarm Data 5 O40 O39 O38 O37 O36 O35 O34 O33
Alarm Data 6 O48 O47 O46 O45 O44 O43 O42 O41
Alarm Data 7 O56 O55 O54 O53 O52 O51 O50 O49
Alarm Data 8 O64 O63 O62 O61 O60 O59 O58 O57
Alarm Data 9 O72 O71 O70 O69 O68 O67 O66 O65
Alarm Data 10 O80 O79 O78 O77 O76 O75 O74 O73
Alarm Data 11 O88 O87 O86 O85 O84 O83 O82 O81
Alarm Data 12 O96 O95 O94 O93 O92 O91 O90 O89
Alarm Data 13 O104 O103 O102 O101 O100 O99 O98 O97
Alarm Data 14 O112 O111 O110 O109 O108 O107 O106 O105
Alarm Data 15 O120 O119 O118 O117 O116 O115 O114 O113
Alarm Data 16 O128 O127 O126 O125 O124 O123 O122 O121

NOTE: In table, S letter is shown short circuit state, O letter is shown open circuit state.
Table2: Elimko FT 10 Series Filter Timer - icon10

Elimko FT 10 Series Filter Timer - icon192 No Control
Elimko FT 10 Series Filter Timer - icon180 ON/OFF Control
Elimko FT 10 Series Filter Timer - icon181 Proportional Control

Table3: Elimko FT 10 Series Filter Timer - icon184

Elimko FT 10 Series Filter Timer - icon182 0-20 mA
Elimko FT Series Filter Timer - 20-0 mA
Elimko FT 10 Series Filter Timer - icon183 4-20 mA
Elimko FT 10 Series Filter Timer - icon185 20-4 mA

Table4: Elimko FT 10 Series Filter Timer - icon186

Elimko FT 10 Series Filter Timer - icon36 Normally open
Elimko FT 10 Series Filter Timer - icon111 Normally closed

Table5: Elimko FT Series Filter Timer -1

Elimko FT 10 Series Filter Timer - icon36 Acknowledge alarm is active
Elimko FT 10 Series Filter Timer - icon23 Acknowledge alarm isn’t active

Table6:  Elimko FT 10 Series Filter Timer - icon189

Elimko FT 10 Series Filter Timer - icon36 Wait break and pulse time
Elimko FT 10 Series Filter Timer - icon23 Not wait break and pulse time

Table7: Elimko FT 10 Series Filter Timer - icon191

Elimko FT 10 Series Filter Timer - icon179 No parity
Elimko FT 10 Series Filter Timer - icon193 Odd parity
Elimko FT 10 Series Filter Timer - icon194 Even parity

Manufacturer / Technical Support:

Elimko Elektronic Production and Control Co. Ltd.
8. Cadde 21. Sokak No:16 Emek- Ankara / TURKEY
Phone: + 90 312 212 64 50 Fax: + 90 312 212 41 43