Elimko E-96P Series Universal Advanced Digital Controllers User Guide

E-96P Series Universal Advanced Digital Controllers

Specifications

  • Product Name: E-96P Series Universal Process Controller
  • Dimensions: 96×96 mm
  • Control Forms: On/Off, PID, and others
  • Input Types: T/C, R/T, mV, mA
  • Display Range: -1999 to 9999 on two 4-digit displays

Product Usage Instructions

1. Installation

– The E-96P controller is designed for panel mounting in an
industrial environment.

– Ensure the package contains the controller, 2 mounting clamps,
user manual, and guarantee certificate.

– Before installation, thoroughly read the user manual.

2. Configuration

– Configuration and setup should only be performed by a
qualified person in instrumentation.

– Connect the analog inputs, analog outputs, relay/SSR outputs,
and digital inputs as per the connection diagram provided.

3. Operation

– Keep the controller away from flammable gases to prevent
explosions.

– Clean the controller using a clean cloth soaked in water; do
not use alcohol or solvents.

4. Safety

– The controller is not intended for medical applications.

FAQ

Q: What should I do if there are missing items or visible
defects in the delivered product?

A: Contact the vendor from whom you purchased the product.

Q: What are the compliance standards for the E-96P
controller?

A: The controller complies with Low Voltage Directive EN 61010-1
and EMC Directive EN 61326-1.

Q: How should I clean the controller?

A: Use a clean cloth soaked in water to gently wipe the outer
surface of the controller; do not use alcohol or solvents.

KY-96P-0825-1

4. WARNINGS

E-96P Series
200.0 R1 R2 Universal Advanced
R3 Digital Controllers
R4
200.0 PR Quick Start Guide MN

Elimko

Manufacturer / Technical Support

SET

Elimko Elektronik malat ve Kontrol Ltd. ti.

8. Cadde 21. Sokak No:16 Emek 06510 Ankara / TÜRKYE

96P Telefon: + 90 312 212 64 50 Faks: + 90 312 212 41 43

www.elimko.com.tr · e-mail:elimko@elimko.com.tr

1. DESCRIPTION
E-96P Series universal process controllers are industrial devices at 96×96 mm IEC/TR 60668 dimensions designed using new generation microcontrollers with on/off, PID and other control forms, where inputs and outputs can be easily programmed by the user.
In E-96P Series controllers, the set value and measured value can be displayed from -1999 to 9999 on two 4-digit displays; general purpose inputs (T/C, R/T, mV, mA) can be programmed.

2. DIMENSIONS and PANEL CUT-OUT

96 mm
200.0 R1 R2 R3 R4 200.0 PR MN

Elimko

SET 96P

91 mm

1

21

31 11

2

22

32 12

3

23

33 13

4

24

34 14

5

25

35 15

6

26

36 16

7

27

37 17

8

28

38 18

9

29

39 19

10 30

20

91 mm

96 mm

10 mm

100 mm

Elimko
Kontrol Edilmitir
2

TP

: E96P

SKALA :

GR :

ÇIKI :

SER NO : 22/10798

Elimko
Tel: +90 3122126450 Fax: +90 3122124143
TÜRKYE

-0.0 92 x 92 mm
+0.5

35 mm min.

10 mm min.

91 mm 91 mm

100 mm

10 mm

Panel Cut-Out and Minimum Spacing

3. CONNECTION DIAGRAM

Analog Outputs

1

Relay and SSR Outputs

2

3

4

5

6

7

8

Operating voltage

9

suitable for the

device type shall

10

be applied.

Operating

RL4

RL3

RL2

RL1

Voltage

SSR2

SSR1

AO2

21

31

11

22

32

12

Analog Inputs

GND TRX + TRX – DI3 DI2 DI1 COM

Digital Inputs

23

33

13

24

34

14

25

35

15

26

36

16

27

37

17

RS-485

28

38

18

29

39

19

30

20

1st and 2nd control outputs can be selected as either Relay (RL1, RL2) or SSR (SSR1, SSR2).

Analog outputs (AO1, AO2 ) can be selected as either mA or 0-10 V DC.

Digital inputs are used by connecting a dry contact output between the COM terminal and the desired input (DI1, DI2 or DI3).

Thermocouple / miliVolt 0-20 mA / 4-20 mA
Resistance Thermometer 2-Wire Transmitter Volt
External Set Input (mA)

Analog Input 1

13

13

14

14

15

15

16

16

17

17

18

18

13

13

14

14

15

15

16

16

17

17

18

18

Analog Input 2

13

13

14

14

15

15

16

16

17 V

17

18

18

AO1 Valve Pot. Feedback (Note 2)
1-5 kOhm Valve mA Feedback (Note 2)
0-20 / 4-20 mA

E-96P controller is designed for panel mounting and should be used in an industrial environment.
m The package of E-96P controller contans; Controller, 2 peces of mountng clamps, User manual and Guarantee certfcate.
m After openng the package, please check the contents wth the above lst. If the delvered product s wrong type, any tem s mssng or there are vsble defects, contact the vendor from whch you purchased the product.
m Before nstallng and operatng the controller, please read the user manual thoroughly.
m The nstallaton and confguraton of the controller must only be performed by a person qualfed n nstrumentaton.
m Keep the unt away from flamable gases, that could cause exploson.
m Do not use alcohol or other solvents to clean the controller. Use a clean cloth soaked n water tghtly squeezed to gently wpe the outer surface of the controller.
m It s not used n medcal applcatons.

EU DIRECTIVE COMPLIANCE
Low Voltage Drectve EN 61010-1 EMC Drectve EN 61326-1

K – Q TSE-ISO-EN
9000
TS EN ISO 9001 Quality Management System Certificate

5. TYPE CODING
E-96P Series Universal Advanced Controller

E-96P – W – X – Y – Z

Relay Outputs

2 relays (RL1, RL2)

2

3 relays (RL1, RL2, RL3)

3

4 relays (RL1, RL2, RL3, RL4)

4

1 SSR (SSR1) + 1 relay (RL2)

5

1 SSR (SSR1) + 2 relays (RL2, RL3)

6

1 SSR (SSR1) + 3 relays (RL2, RL3, RL4)

7

2 SSR (SSR1, SSR2) + 1 relay (RL3)

8

2 SSR (SSR1, SSR2) + 2 relays (RL3, RL4)

9

Analog Outputs *

1 x 0-20 / 4-20 mA (AO1)

1

2 x 0-20 / 4-20 mA (AO1, AO2)

2

1 x 0-10 V DC (AO1)

3

2 x 0-10 V DC (AO1, AO2)

4

1 x 0-20 / 4-20 mA (AO1) + 1 x 0-10 V DC (AO2)

5

Communication

None

0

RS-485 **

1

Operating Voltage

85-265 V AC / 85-375 V DC

0

20-60 V AC / 20-60 V DC

1

* Analog outputs are isolated from each other. ** When E-96P Series devices are ordered with communication, the E-IB-11 USB-RS485 converter can be used for PC connection. There are various control and monitoring software provided by Elimko.

6. TECHNICAL SPECIFICATIONS

Parameter

Description

Control Type

On/Off, PID, Heat/Cool, Floating and Feedback Control of Valves

Operating Voltage

20..60 V AC / 20..60 V DC or 85..265 V AC / 85..375 V DC

Relays / SSR

4 pieces SPST – NO 250 V AC 5A relays or 24 V DC 25 mA (SSR) drives

Dimensions (mm)

96 (Lenght) x 96 (Height) x 100 (Width)

Panel Cut-Out (mm)

92 (Lenght) x 92 (Height)

Analog Output

2 x 0..20 / 4..20 mA or 0..10 V DC optional

Analog Input

Universal (Note 1), 1 x External set (mA)

Communication (RS-485) Available (optional)

Digital Input

3 inputs

Valve Feedback

Available (Note 2)

Transmitter Supply

Available

Weight

430 g

Power Consumption Max. 7 W (10 VA)

Operating Temperature – 10 °C … 55 °C

Storage Temperature – 25 °C … 65 °C

Memory

Max. 100.000 write

Protection Class

IP-65 Front Panel, IP-20 Rear Case

Notes:

(1) Universal Input :

Thermocouple

: B, E, J, K, L, N, R, S, T, U

Resistance Thermometer : Pt-100

Current

: 0-20 mA, 4-20 mA (Linear)

Voltage

: 0-50 mV, 0-1 V, 0.2- 1 V (Linear),

0-10 V DC, must be specified in the order.

Resolution

: 16 bit

Accuracy

: Thermocouple, Max. ±1.0 °C (Conversion and CJC error)

Resistance Thermometer, Max. ±0.5 °C

(Conversion and wire resistance compensation)

Linear Input, Max. % 0.1

(2) Valve Feedback are supplied as potentiometer input in standard controllers. If the feedback type is requested as mA, it must be specified in the order.

7. PARAMETER TABLE

INPUT SETTINGS
gcnf

Description INP1 Analog Input 1 Type
DP Decimal Point SCLO Analog Input 1 Linear Scale Lower Value SCHI Analog Input 1 Linear Scale Upper Value UNIT Temperature Unit OFST Analog Input 1 Offset Value FLTR Analog Input 1 Filter SNBR Analog Input 1 Sensor Broken Behaviour INP2 Analog Input 2 Type S2LO Analog Input 2 Linear Scale Lower Value S2HI Analog Input 2 Linear Scale Upper Value S2BR Analog Input 2 Sensor Broken Behaviour ADRS Modbus Adress BAUD Modbus Baud Rate [4.8, 9.6, 19.2, 38.4 kbaud] PRTY Modbus Parity [None, ODD, Even]

CONTROL SET SETTINGS
SETP

SPSR Control Set Point Source SPLL Control Set Point Lower Limit SPHL Control Set Point Upper Limit SPRR Control Set Point Ramping Rate S-1 1. Step Set Value T-1 1. Step Time S-2 2. Step Set Value T-2 2. Step Time S-3 3. Step Set Value T-3 3. Step Time SET1 Digital Input Selectable Set 1 SET2 Digital Input Selectable Set 2 SET3 Digital Input Selectable Set 3 SET4 Digital Input Selectable Set 4

ALARM SETTINGS
ACNF

A1TP Alarm 1 Type A1SP Alarm 1 Set Point A1HY Alarm 1 Hysteresis A1LT Alarm 1 Lock A2TP Alarm 2 Type A2SP Alarm 2 Set Point A2HY Alarm 2 Hysteresis A2LT Alarm 2 Lock A3TP Alarm 3 Type A3SP Alarm 3 Set Point A3HY Alarm 3 Hysteresis A3LT Alarm 3 Lock A4TP Alarm 4 Type A4SP Alarm 4 Set Point A4HY Alarm 4 Hysteresis A4LT Alarm 4 Lock

OUTPUTS
OCNF

CTYP CFRM CPRD MNPR TRTM DBND OLL OHL OMR PONC TRLL TRHL RL1D RL2D RL3D RL4D AO1D AO1R AO2D AO2R SRVL SRVH

Control Type Control Form [DIR, REV] Control Period Manual Mode Selection Floating Control Valve Travel Time Dead Band Control Output Lower Limit Control Output Upper Limit Control Output Manual Reset PID Power On Behaviour Retransmission Scale Lower Value Retransmission Scale Upper Value
Relay 1 Function Relay 2 Function Relay 3 Function Relay 4 Function Analog Output 1 Function Analog Output 1 Type Analog Output 2 Function Analog Output 2 Type Feedback Valve Fully-Closed Position Feedback Valve Fully-Open Position

PID SETTINGS
tUNE

AT PID PB-1 PB-2 ITH ITC DTH DTC HYS

PID Auto Tune PID Parameter Type
Proportional Band + Proportional Band Integral Time + Integral Time Derivative Time + Derivative Time Hysteresis

SECURITY
PRTC

SCOD DPRL APRL FCST

Security Code Parameter Access Level Parameter Setting Level Factory Settings [OFF, LOAD, SAVE, DFLT]

Min Maks Unit

Table 1

0

3

-199.9 999.9 EU

-199.9 999.9 EU

*C *F

-100.0 100.0 EU 1 15 s

LO HI

0-20 4-20

-199.9 999.9 EU

-199.9 999.9 EU

LO HI

1 127

4.8 38.4

Table 2 -199.9 SPHL EU SPLL 999.9 EU
OFF 60.0 EU/min SPLL SPHL EU
OFF 999.9 min SPLL SPHL EU
OFF 999.9 min SPLL SPHL EU
OFF 999.9 min SPLL SPHL EU SPLL SPHL EU SPLL SPHL EU SPLL SPHL EU

Table 3 -199.9 999.9 EU
0.0 999.9 EU DSB ENB
Table 3 -199.9 999.9 EU
0.0 999.9 EU DSB ENB
Table 3 -199.9 999.9 EU
0.0 999.9 EU DSB ENB
Table 3 -199.9 999.9 EU
0.0 999.9 EU DSB ENB

Table 4

DIR REV 1 250 s

DSB ENB

10 2500 s

0.1 25.0 %

0.0 OHL %

OLL 100.0 %

OLL OHL %

0

4

-199.9 TRHL EU

TRLL 999.9 EU

Table 5

Table 5

Table 5

Table 5

Table 6

Table 7.1 ve Table 7.2

Table 6

Table 7.1 ve Table 7.2

OFF ON
STD ADV
0.1 999.9 EU 0.1 999.9 EU OFF 9999 s OFF 9999 s OFF 2500 s OFF 2500 s 0.0 999.9 EU

0 9999

0

9

0

9

8. ACCESSING PARAMETERS

STEP 1:

STEP 2:

Security Code Configuration

Entry Page Selection

(Default: 10) and Entry

STEP 3: Parameter Selection and Configuration

Process Screen
199.8 200.0

Selected Page

12 12

43 SCOD

3 PAGE

3 3 Parameters . . .

0

GCNF

4

4

4

Adjustment
12
Enter
3
Return
4
Menu Access
43

9. APPLICATION EXAMPLES
1) Input: Pt-100 Relay / Alarm1: 50 °C Low, Relay2 / Alarm2: 55 °C High AO1: 4-20 mA PID Control Output inp1 a1tp a1sp a2tp a2sp ctyp rl1D rl2D ao1D ao1r pt lo 50.0 hi 55.0 sco al-1 al-2 co-1 4-20
2) Input: TC Type J, Relay1: On-Off Control Output, Relay2 / Alarm2: 350 °C High inp1 a2tp a2sp ctyp rl1D rl2D
j hi 350.0 sco Do-1 al-2
3) Input: TC Type K, Profile Control (Ramp up to 400°C in 10 minutes and wait for 60 minutes), Relay1: PID Control Output, AO1: Retransmission Output (4-20 mA, 0-1200 °C)
inp1 spsr s-1 t-1 s-2 t-2 ctyp trll trhl rl1D rl2D ao1D ao1r k prfl 400 10.0 400 60.0 sco 0 1200 co-1 al-2 pvtr 4-20
4) Input: 4-20 mA, Scale: 0-600, External Set Point: 4-20 mA, Scale: 0-600, Floating Valve Control (Travel Time 30 s), Relay1: Valve Open, Relay2: Valve Close
inp1 sclo schi inp2 s2lo s2hi ctyp trtm rl1D rl2D 4-20 0.0 600.0 4-20 0.0 600.0 bnD 30 co-1 co-2

Table 1. Input Type Options b Type B Thermocouple e Type E Thermocouple

j Type J Thermocouple

k Type K Thermocouple l Type L Thermocouple

n Type N Thermocouple

r Type R Thermocouple s Type S Thermocouple

t Type T Thermocouple u Type U Thermocouple pt Pt-100

0-20 0-20 mA

4-20 0-50 0.0-1 0.2-1

4-20 mA 0-50 mV 0-1 V 0.2-1 V

0-10 0-10 V (*)

2-10 2-10 V (*)

(*) Custom specified volt input

Table 2. Control Set Options int Internal adjustment with
keys prfl With Profile Control e/t External adjustment with
AIN2 external input DINP With Digital Input
Table 3. Alarm Options off Off lo Low Alarm hi High Alarm loD Low Deviation hiD High Deviation lob Band Alarm (In) hib Band Alarm (Out)

Table 4. Control Type Options off No Control sco Single (Heat) Dco Double (Heat/Cool) bnD Floating Control of Valve pfb Feedback Control of Valve
Tablo 5. Relay Output Options co-1 PID + (Heating) co-2 PID – (Cooling) Do-1 On-Off + (Heating) Do-2 On-Off – (Cooling) al-1 Alarm 1 al-2 Alarm 2 al-3 Alarm 3 al-4 Alarm 4
Table 6. Analog Output Options co-1 PID + (Heating) co-2 PID – (Cooling) pvtr Process Value sptr Control Set Value
Table 7.1. Analog Output Range 0-20 0-20 mA 20-0 20-0 mA 4-20 4-20 mA 20-4 20-4 mA
Table 7.2. Analog Output Range 0-10 0-10 V 10-0 10-0 V 2-10 2-10 V 10-2 10-2 V

For detailed information, you can access the comprehensive user manual of the device under the heading “User Manuals” at www.elimko.com.tr. You can also use the QR Code on the front for this.
Elimko Elektronik malat ve Kontrol Ticaret Ltd. ti. Ankara Sanayi Odasi 2. Organize Sanayi Bölgesi Alci OSB Mahallesi 2001. Cad. No:14 Temelli 06909 Ankara / TURKYE Tel: +90 312 212 64 50 (Pbx) · Fax: +90 312 212 41 43 E-mail: elimko@elimko.com.tr · www.elimko.com.tr

Documents / Resources

Elimko E-96P Series Universal Advanced Digital Controllers [pdf] User Guide
E-96P Series, E-96P Series Universal Advanced Digital Controllers, Universal Advanced Digital Controllers, Advanced Digital Controllers, Digital Controllers, Controllers

References

Leave a comment

Your email address will not be published. Required fields are marked *