QUICK GUIDE
EE355 – Dew Point Sensor down to -60 °C Td (-76 °F Td)
(Full User Manual at www.epluse.com/ee355)
Electrical Connection
Please note:
To meet the EMC Directive 2014/30/EU a shielded connection cable must be used.
Pin number | Function | Wire colours for accessory: – Connection cable HA010819/20/21 |
1 | Supply voltage | brown |
2 | Output 4 – 20 mA | white |
3 | GND | blue |
4 | RS485 A (D+) | black |
5 | RS485 B (D-) | grey |
Modbus Setup
Factory default setup:
Baudrate | Data | Parity | Stop bits | Modbus adress |
9600 | 8 | Even | One | 243 |
Device address, baud rate, parity and stop bits can be set via:
- EE-PCS, Product Configuration Software and the appropriate configuration cable HA011013.
The EE-PCS can be downloaded free of charge from www.epluse.com/Configurator. - Modbus protocol in the register 60001 (0x00) and 60002 (0x01).
See Application Note Modbus AN0103 (available on www.epluse.com/ee355)
INFO (read register): | ||
Parameter | Register number1) [DEC] | Protocol Address2) [HEX] |
Read register: function code 0x03 / 0x04 | ||
Serial number (as ASCII) | 1 | 0x00 |
Firmware version | 9 | 0x08 |
INTEGER 16 bit | ||
Parameter | Register number1) [DEC] | Protocol Address2) [HEX] |
Write register: function code 0x06 | ||
Modbus address (Slave ID) | 1 | 0x00 |
Modbus protocol settings3) | 2 | 0x01 |
- Register number starts from 1.
- Protocol address starts from 0.
- For Modbus protocol settings see Application Note Modbus AN0103 (available on www.epluse.com/ee355).
Modbus Register Map
FLOAT 32 bit: | ||||
Parameter | SI Unit | US/GB Unit | Register number1) [Dec] | Register address2) [HEX] |
Read register: function code 0x03 / 0x04 | ||||
Temperature T | °C | °F | 26 | 0x19 |
Relative humidity RH, Uw | %RH | %RH | 28 | 0x1B |
Water vapour partial pressure e’ | mbar | psi | 30 | 0x1D |
Dew point temperature Td | °C | °F | 32 | 0x1F |
Frost point temperature Tf | °C | °F | 42 | 0x29 |
Volume concentration Wv | ppm | ppm | 60 | 0x3B |
INTEGER 16 bit: | ||||
Parameter | Register number1) [Dec] | Register address2) [HEX] | ||
Read register: function code 0x03 / 0x04 | ||||
State of auto-calibration 0 … normal operation 1 … auto-calibration active |
501 | 0x1F4 | ||
Write register: function code 0x06 | ||||
Modbus address (Slave ID) | 1 | 0x00 | ||
RS485 data transmission | 2 | 0x01 |
- Register number starts from 1.
- Register address starts from 0.
Installation
Please note:
Remove the protection cap just before installation.
INFORMATION
+43 7235 605 0 / info@epluse.com
E+E Elektronik Ges.m.b.H.
Langwiesen 7 • 4209 Engerwitzdorf • Austria
Tel: +43 7235 605-0 • Fax: +43 7235 605-8
info@epluse.com • www.epluse.com
LG Linz Fn 165761 t • VAT No. ATU44043101
Place of Jurisdiction: A-4020 Linz • DVR0962759QG_EE355 // v1.4 // Modification rights reserved // 302739