E E ELEKTRONIK logoQUICK GUIDE
EE355 – Dew Point Sensor down to -60 °C Td (-76 °F Td)
(Full User Manual at www.epluse.com/ee355)

Electrical Connection

E E ELEKTRONIK EE355 Dew Point Sensor - 1

Paulmann Ceiling Lighting Accessories - Icon 1 Please note:
To meet the EMC Directive 2014/30/EU a shielded connection cable must be used.

Pin number Function Wire colours for accessory:
– Connection cable HA010819/20/21
1 Supply voltage brown
2 Output 4 – 20 mA white
3 GND blue
4 RS485 A (D+) black
5 RS485 B (D-) grey

Modbus Setup

Factory default setup:

Baudrate Data Parity Stop bits Modbus adress
9600 8 Even One 243

Device address, baud rate, parity and stop bits can be set via:

  1. EE-PCS, Product Configuration Software and the appropriate configuration cable HA011013.
    The EE-PCS can be downloaded free of charge from www.epluse.com/Configurator.
  2. Modbus protocol in the register 60001 (0x00) and 60002 (0x01).
    See Application Note Modbus AN0103 (available on www.epluse.com/ee355)
INFO (read register):
Parameter Register number1) [DEC] Protocol Address2) [HEX]
Read register: function code 0x03 / 0x04
Serial number (as ASCII) 1 0x00
Firmware version 9 0x08
INTEGER 16 bit
Parameter Register number1) [DEC] Protocol Address2) [HEX]
Write register: function code 0x06
Modbus address (Slave ID) 1 0x00
Modbus protocol settings3) 2 0x01
  1. Register number starts from 1.
  2. Protocol address starts from 0.
  3. For Modbus protocol settings see Application Note Modbus AN0103 (available on www.epluse.com/ee355).

Modbus Register Map

FLOAT 32 bit:
Parameter SI Unit US/GB Unit Register number1) [Dec] Register address2) [HEX]
Read register: function code 0x03 / 0x04
Temperature T °C °F 26 0x19
Relative humidity RH, Uw %RH %RH 28 0x1B
Water vapour partial pressure e’ mbar psi 30 0x1D
Dew point temperature Td °C °F 32 0x1F
Frost point temperature Tf °C °F 42 0x29
Volume concentration Wv ppm ppm 60 0x3B
INTEGER 16 bit:
Parameter Register number1) [Dec] Register address2) [HEX]
Read register: function code 0x03 / 0x04
State of auto-calibration 0 … normal operation
1 … auto-calibration active
 501  0x1F4
Write register: function code 0x06
Modbus address (Slave ID) 1 0x00
RS485 data transmission 2 0x01
  1. Register number starts from 1.
  2. Register address starts from 0.

Installation

E E ELEKTRONIK EE355 Dew Point Sensor - 2

Paulmann Ceiling Lighting Accessories - Icon 1 Please note:
Remove the protection cap just before installation.

E E ELEKTRONIK EE355 Dew Point Sensor - 3

E E ELEKTRONIK logoINFORMATION
+43 7235 605 0 / info@epluse.com
E+E Elektronik Ges.m.b.H.
Langwiesen 7 • 4209 Engerwitzdorf • Austria
Tel: +43 7235 605-0 • Fax: +43 7235 605-8
info@epluse.comwww.epluse.com
LG Linz Fn 165761 t • VAT No. ATU44043101
Place of Jurisdiction: A-4020 Linz • DVR0962759E E ELEKTRONIK EE355 Dew Point Sensor - iconQG_EE355 // v1.4 // Modification rights reserved // 302739

Documents / Resources

E E ELEKTRONIK EE355 Dew Point Sensor [pdf] User Guide
EE355 Dew Point Sensor, EE355, Dew Point Sensor, Point Sensor, Sensor
E E ELEKTRONIK EE355 Dew Point Sensor [pdf] User Manual
EE355 Dew Point Sensor, EE355, Dew Point Sensor, Point Sensor, Sensor

References

Leave a comment

Your email address will not be published. Required fields are marked *