E E ELEKTRONIK EE212D Modular Humidity and Temperature Sensor Instruction Manual
GENERAL INFORMATION
- Date: 02.06.2022
- Vendor Name: E+E Elektronik
- Product Name: EE212D
- Product Model Number: EE212D
This is the generic denomination for EE212 devices with digital output (RS485) and BACnet MS/TP protocol. For type number of specific EE212D devices see the respective data sheet at:
https://www.epluse.com/fileadmin/data/product/ee212/datasheet_EE212.pdf - Application Software Version: 2.0
- Firmware Revision: 2.0
- BACnet Protocol Version: 1
- BACnet Protocol Revision: 14
Product Description:
Humidity and Temperature BACNet MS/TP Smart Sensor Master device EE212D.
BACNET STANDARDIZED DEVICE PROFILE (ANNEX L)
- BACnet Operator Workstation (B-OWS)
- BACnet Advanced Operator Workstation (B-AWS)
- BACnet Operator Display (B-OD)
- BACnet Building Controller (B-BC)
- BACnet Advanced Application Controller (B-AAC)
- BACnet Application Specific Controller (B-ASC)
- BACnet Smart Sensor (B-SS)
- BACnet Smart Actuator (B-SA)
LIST OF ALL SUPPORTED BACNET INTEROPERABILITY BUILDING BLOCKS (ANNEX K)
- DS-RP-B………….Data Sharing – Read Property – B
- DS-RPM-B……….Data Sharing – Read Property Multiple – B
- DS-WP-B …………Data Sharing – Write Property – B
- DS-COVU-B……..Data Sharing – COV-Unsolicited – B
- DM-DDB-B……….Data Management – Dynamic Device Binding – B
- DM-DOB-B……….Data Management – Dynamic Object Binding – B
- DM-DCC-B……….Data Management – Device Communication Control – B
- DM-RD-B …………Data Management – Reinitialize Device – B
SEGMENTATION CAPABILITY
- Able to transmit segmented messages
- Able to receive segmented messages
BACNET STANDARD OBJECT TYPES SUPPORTED
- Accumulator
- Analog Input
- Analog Output
- Analog Value
- Averaging
- Binary Input
- Binary Output
- Binary Value
- Calendar
- Command
- Device
- Event Enrollment
- File
- Group
- Life Safety Point
- Life Safety Zone
- Loop
- Multistate Input
- Multistate Output
- Multistate Value
- Notification Class
- Program
- Pulse Converter
- Schedule
- Trend Log
DATA LINK LAYER OPTIONS
- BACnet IP, (Annex J):
- BACnet IP, (Annex J), Foreign Device:
- ISO 8802-3, Ethernet (Clause 7):
- ATA 878.1, 2.5 Mb. ARCNET (Clause 8):
- ATA 878.1, EIA-485 ARCNET (Clause 8), baud rate(s):
- MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400, 57600, 76800, 115200
- MS/TP slave (Clause 9), baud rate(s):
- Point-To-Point, EIA 232 (Clause 10), baud rate(s):
- Point-To-Point, modem, (Clause 10), baud rate(s):
- LonTalk, (Clause 11), medium:
- BACnet/Zigbee (Annex O):
- Other:
DEVICE ADDRESS BINDING
Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.) Yes No
NETWORKING OPTIONS
- Router, Clause 6 – List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc.
- Annex H, BACnet Tunneling Router over IP
- BACnet/IP Broadcast Management Device (BBMD)
Does the BBMD support registrations by Foreign Devices? Yes No
Does the BBMD support network address translation? Yes No
NETWORK SECURITY OPTIONS
- Non-secure Device – is capable of operating without BACnet Network Security
- Secure Device – is capable of using BACnet Network Security (NS-SD BIBB)
- Multiple Application-Specific Keys
- Supports encryption (NS-ED BIBB)
- Key Server (NS-KS BIBB)
CHARACTER SETS SUPPORTED
Indicating support for multiple character sets does not imply that they can all be supported simultaneously
- ISO 10646 (UTF-8)
- ISO 10646 (UCS-2)
- IBM™ /Microsoft™ DBCS
- SO 10646 (UCS-4)
- ISO 8859-1
- JIS X 0208
TRANSMITTER DIFFERENCES
- BACnet Objects.
- Device Object.
- Analog Input Object: Temperature .
- Analog Input Object: Relative Humidity .
- Analog Input Object: Water Vapor Partial Pressure .
- Analog Input Object: Dew Point temperature .
- Analog Input Object: Absolute humidity .
- Analog Input Object: Mixing Ratio.
- Analog Input Object: Enthalpy.
- Analog Input Object: Frost Point Temperature.
- Analog Input Object: Wet Bulb Temperature.
BACNET OBJECTS
This part describes the various BACnet objects in detail. The main properties of the individual objects are explained in the following sections.
Device Object
Property | Data Type | Initial Value | R/O/P | Persistence |
Object Identifier | BACnetObjectIdentifier | Unique Object Instance (0 – 4194302) | R (W) | Non Volatile |
Object Name | CharacterString[15] | “EE212D_XXXXXXXX”(X … Unique characters) | R (W) | Non Volatile |
Object Type | BACnetObjectType (Enum.) | OBJECT_DEVICE | R (R) | Fixed |
Description | CharacterString[15] | “EE212D” | O (W) | Non Volatile |
System Status | BACnetDeviceStatus (Enum.) | STATUS_OPERATIONAL | R (R) | Volatile |
Vendor Name | CharacterString | “E+E Elektronik” | R (R) | Fixed |
Vendor Identifier | Unsigned16 | 623 | R (R) | Fixed |
Model Name | CharacterString | “EE212D” | R (R) | Fixed |
Firmware Revision | CharacterString | “2.0” | R (R) | Fixed |
Application Software Version | CharacterString | “2.0” | R (R) | Fixed |
Location | CharacterString[15] | “AUT” | O (W) | Non Volatile |
Protocol Version | Unsigned | 1 | R (R) | Fixed |
Protocol Revision | Unsigned | 14 | R (R) | Fixed |
Protocol Services Supported | BACnetProtocolServices Supported (Bit-String) | Read PropertyRead Property Multiple Write PropertyDevice Comm. Control Reinitialize Device Unconfirmed COV Who-IsWho-Has | R (R) | Fixed |
Protocol Object Types Supported | BACnetObjectTypes Supported (Bit-String) | Device Analog Input | R (R) | Fixed |
Object List | BACnetARRAY[N] of BACnetPbjectIdentifier | EE212D:Device ObjectAI0 (Temperature)AI1 (Relative Humidity) AI2 (Water Vap. Press.) AI3 (Dew Point Temp.) AI4 (Absolute Humidity) AI5 (Mixing Ratio)AI6 (Enthalpy)AI7 (Frost Point Temp.) AI8 (Wet Bulb Temp.) | R (R) | Fixed |
Property List | BACnetARRAY[N] of BACnetPropertyIdentifier | System Status, Vendor Name, Vendor Identifier, Model Name, Firmware Revision,Application Software Version, Location,Description, Protocol Version, Protocol Revision,Protocol Services Supported, Protocol Object Types Supported,Object List,Max APDU Length Accepted, APDU Timeout, Segmentation Supported, Number of APDU Retries, Device Address Binding, Database Revision,Max Info Frames, Max Master,512 (proprietary prop.: Comm.Settings) | R (R) | Fixed |
Max APDU Length Accepted | Unsigned16 | 480 | R (R) | Fixed |
Segmentation Supported | BACnetSegmentation (Enum.) | NO_SEGMENTATION | R (R) | Fixed |
APDU Timeout | Unsigned | 3000 | R (R) | Fixed |
Number of APDU Retries | Unsigned | 3 | R (R) | Fixed |
Device Address Binding | List of BACnetAddressBinding | NULL | R (R) | Fixed |
Database Revision | Unsigned | 0 | R (W) | Non Volatile |
Max Info Frames | Unsigned | 1 | O (R) | Fixed |
Max Master | Unsigned | 127 | O (W) | Non Volatile |
Communication Parameter | CharacterString | “38400-8n1” | P (W) | Non Volatile |
- R (R) …………. Required Property (Readable)
- R (W) ………… Required Property (Read-/Writable)
- O (R)…………. Optional Property (Readable)
- O (W) ………… Optional Property (Read-/Writeable)
- P (R) …………. Proprietary Property (Readable)
- P (W)…………. Proprietary Property (Read-/Writeable)
Max Master Property:
The maximum “Max Master” value is 127. This value is writable via BACnet write property.
Communication Parameter:
For changing the RS485 communication parameters it is relevant to observe the character string format.
The character string consists of following parts:
- Baud rate (9600, 19200, 38400, 57600, 76800, 115200)
- “-“
- Number of data bits (8)
- Parity (none)
- Number of stop bits (1)
Example:
- Change parameters to: Baud = 76800, 8 data bits, no parity, 1 stop bit: String: “76800-8n1”
ATTENTION: The character string shall end with the terminating 0.
Analog Input Objects
All analog input object have the same structure:
Property | Data Type | Initial Value | R/O/P | Persistence |
Object Identifier | BACnetObjectIdentifier | 0 … Temperature 1 … Relative Humidity 2 … Water Vap. Press. 3 … Dew Point Temp. 4 … Absolute Humidity 5 … Mixing Ratio 6 … Enthalpy 7 … Frost Point Temp. 8 … Wet Bulb Temp. |
R | Fixed |
Object Name | CharacterString | “T” … Temperature “RH”… Rel. Humidity “e” … Wat. Vap. Press. “Td” … Dew Pnt. Temp. “dv” … Abs. Humidity “r” … Mixing Ratio “h” … Enthalpy “Tf” … Frost Pnt. Temp. “Tw” … Wet Bulb Temp. |
R | Fixed |
Description | CharacterString | (see below) | O | Fixed |
Object Type | BACnetObjectType (Enum.) | OBJECT_ANALOG_INPUT | R | Fixed |
Present Value | Real | 0.0 | R (W)a.) | Volatile |
Status Flags | BACnetStatusFlags (Bit-String) | false, false, false, false | R | Volatile |
Event State | BACnetEventState | NORMAL | R | Volatile |
Out of Service | Boolean | false | R (W) | Volatile |
Units | BACnetEngineeringUnits (Enum.) | (see below) | R (W) | Non Volatile |
Reliability | BACnetReliability (Enum.) | NO_FAULT_DETECTED | R (W)a.) | Volatile |
COV Increment | Real | Not a Number (NaN) | O (W) | Non Volatile |
Property List | BACnetARRAY[N] of BACnetPropertyIdentifier | R (R) | Fixed |
a.) When “Out of Service” flag is true, value is writable.
- R (R) …………. Required Property (Readable)
- R (W) ………… Required Property (Read-/Writable)
- O (R)…………. Optional Property (Readable)
- O (W) ………… Optional Property (Read-/Writeable)
- P (R) …………. Proprietary Property (Readable)
- P (W)…………. Proprietary Property (Read-/Writeable)
Description Property:
The following table lists the possible object descriptions depending on the selected measurement units:
Initial Value | Alternative 1 | Alternative 2 |
“Temperature [deg. C]” | “Temperature [deg. F]” | “Temperature [deg. K]” |
“Relative humidity [%rH]” | ||
“Water vapor partial pressure [mbar]” | “Water vapor partial pressure [psi]” | |
“Dew point temperature [deg. C]” | “Temperature [deg. F]” | “Temperature [deg. K]” |
“Absolute humidity [g/m3]” | “Absolute humidity [g/ft3]” | |
“Mixing ratio [g/kg]” | “Mixing ratio [gr/lb]” | |
“Enthalpy [kJ/kg]” | “Enthalpy [ft lbf/lb]” | “Enthalpy [BTU/lb]” |
“Frost point temperature [deg. C]” | “Temperature [deg. F]” | “Temperature [deg. K]” |
“Wet bulb temperature [deg. C]” | “Wet bulb temperature [deg. F]” | “Wet bulb temperature [deg. K]” |
Present Value Property:
This property represents the actual measured value or actual calculated value. When the “Out of Service” flag is true, the Present Value Property is writable. The default Present Value Property is 50.0 when “Out of Service” is true.
Status Flags Property:
The following table describes the possible states of the “Status Flags” property:
Flag | State | Reason |
IN_ALARM | false | Value of “Event State” property is NORMAL (0) |
true | Value of “Event State” property is not NORMAL (0) | |
FAULT | false | Value of “Reliability” property is NO_FAULT_DETECTED |
true | Value of “Reliability” property is not NO_FAULT_DETECTED | |
OVERRIDDEN | false | Always false |
OUT_OF_SERVICE | false | “Present Value” and “Reliability” properties are not writeable via BACnet |
true | “Present Value” and “Reliability” properties are writeable via BACnet |
Event State Property:
The following table describes the possible states of the “Event State” property:
State | Reason |
NORMAL (0) | Value of “Reliability” property is NO_FAULT_DETECTED |
FAULT (1) | Value of “Reliability” property is not NO_FAULT_DETECTED |
Units Property:
The following table lists the possible units for each analog input object:
Initial Value | Alternative 1 | Alternative 2 |
Degrees Celsius (62) | Degrees Fahrenheit (64) | Degrees Kelvin (63) |
Relative Humidity (29) | – | – |
Millibars (134) | Pounds Force per Square Inch (56) | – |
Degrees Celsius (62) | Degrees Fahrenheit (64) | Degrees Kelvin (63) |
Grams per Cubic Meter (217) | Grains per Cubic Foot (256)a.) | – |
Grams per Kilogram (210) | Grains per Pound (257)a.) | – |
Kilojoules per Kilogram Dry Air (149) | Footpound per Pound Dry Air (258)a.) | BTU per Pound Dry Air (24) |
Degrees Celsius (62) | Degrees Fahrenheit (64) | Degrees Kelvin (63) |
Degrees Celsius (62) | Degrees Fahrenheit (64) | Degrees Kelvin (63) |
a.) Not an ASHRAE defined unit.
Reliability Property:
The following table describes the possible states of the “Reliability” property:
State | Reason |
NO_FAULT_DETECTED (0) | No fault detected |
NO SENSOR (1) | Sensor is damaged or not connected |
COV Increment Property:
Default value is NaN (not a number). When the “COV Increment Property” is NaN or greater than 1000,000,000.0 then COV reporting is disabled.
MISCELLANEOUS INFORMATION
Reinitialize Device (RD):
The RD function is used to restart/ reboot the entire transmitter via BACnet. To use reinitialize device functionality a password is needed. The password is: “BACnet123”.
Device Communication Control (DCC):
The DCC functionality is used to stop initiating messages on the BACnet network. After receiving a DCC stop initiate message, the device does not respond to a request any more, except to RD or DCC requests. The use of the device communication control functionality is password protected. The password is: “BACnet123”.
Unsolicited COV Reporting:
When COV reporting is activated, a BACnet message is broadcasted every time when the difference between actual “Present Value” and the previous measured “Present Value” since last COV message exceeds the “COV Increment” value. Since no subscription list is supported, the COV message is always broadcasted. This function is useful for many BACnet clients which need the same information of one BACnet device (e.g. outdoor temperature)
HEADQUARTERS
E+E Elektronik Ges.m.b.H.
Langwiesen 7 4209 Engerwitzdorf Austria
Tel.: +43 7235 605-0
E-mail: info@epluse.com
Web: www.epluse.com
SUBSIDIARIES
E+E Elektronik China
18F, Kaidi Financial Building,
No.1088 XiangYin Road 200433 Shanghai
Tel.: +86 21 6117 6129
E-mail: info@epluse.cn
E+E Elektronik France
47 Avenue de l‘Europe 92310 Sèvres
Tel.: +33 4 74 72 35 82
E-mail: info@epluse.fr
E+E Elektronik Germany
Obere Zeil 2 61440 Oberursel
Tel.: +49 6171 69411-0
E-mail: info@epluse.de
E+E Elektronik India
801, Sakhi Vihar Road 400072 Mumbai
Tel.: +91 990 440 5400
E-mail: info.in@epluse.com
E+E Elektronik Italy
Via Alghero 17/19 20128 Milano (MI)
Tel.: +39 02 2707 86 36
E-mail: info@epluse.it
E+E Elektronik Korea
Suite 2001, Heungdeok IT Valley Towerdong, 13,
Heungdeok 1-ro, Giheung-gu 16954 Yongin-si, Gyeonggi-do
Tel.: +82 31 732 6050
E-mail: info@epluse.co.kr
E+E Elektronik USA
333 East State Parkway Schaumburg, IL 60173
Tel.: +1 847 490 0520
E-mail: office@epluse.com