Overview

UNOlite is an indoor air quality monitor to measure the space temperature / humidity / CO2 / PM2.5 / PM10 / PM1 / TVOC and expose the measurements directly onto a BACnet MS/TP or Modbus RTU network. Moreover, the measurements are also accessible with UNO apps through BLE or UNO web through Wi-Fi (Wi-Fi model). Please refer to UNOlite official website for more information. This document is primarily concerned how to add UNOlite to Modbus/RTU network.

Hardware Interface

Buttons 

Key Description
Hardware reset Push this button will trigger a power cycle.
 

 

Factory reset

After booting, press this button three times within 2 seconds will trigger factory reset. The values below will be restored to default:

s   Modbus baudrate

s   BACnet saved mac address

s   Wi-Fi MQTT broker setting (Wi-Fi model)

NOTE: /t’s recommended to use a paper clip to press the keys.

Terminal block 

Terminal Description
V+ Power input. For more information, please refer to production specification.
V- Power input. For more information, please refer to production specification.
A+ RS485(+) data pin. For Modbus/BACnet network.
B- RS485(-) data pin. For Modbus/BACnet network.
 

GND

Ground terminal. Each RS485 driver in an installation is recommended to connect to the same ground to get a common reference.

DIP switch 

DIPs Description ON OFF
1 – 6 Refer to the later sections for the definition of each pin   n
 

7

BACnet mode switch. ON : BACnet mode OFF : Modbus mode    

n

8 RS485 terminator resistor (120 ohm)   n

NOTE The dips should be adjusted to proper position in power off state. Adjust the dips, then power on device.

Modbus Mode
UNOlite follows Modbus over serial line specification and will run on Modbus/RTU mode if the 7th pin is set to OFF state. The definition of the dips in Modbus mode as listed below:

DIP Description ON OFF
1 Modbus slave address (check address table)   n
2 Modbus slave address (check address table)   n
3 Modbus slave address (check address table)   n
4 Modbus slave address (check address table)   n
5 Modbus slave address (check address table)   n
  • NOTE: The definitions of dip are different from Modbus mode. Please make sure which mode is chosen.
  • NOTE: Pin6 is not defined in Modbus mode

Serial Configuration

UNOlite can directly connect to a controller with RS485 interface, up to 32 UNOlite devices can be joined to a Modbus serial bus.DELTA-uno-Lite-Modbus-fig-2

NOTE: Suggestion to use 22AWG shielded twisted pair cable to connect devices in sequence

Default Serial Configuration: 

  • Baud: 9600
  • Data-Bit: 8
  • Parity: None
  • Stop-Bit: 1

Note: perform factory reset to restore default value if the configuration is missing

Modbus Slave Address
The DIP pins 1~5 represent for binary number 0~31, pin 1 is most significant bit (MSB) and pin 5 is least significant bit (LSB). Notice that Modbus slave address starts from 208, therefore, UNOlite can be configured address from 208 to 239:

Modbus Slave Address Table 

DIP pin Modbus Slave

Addr

  DIP pin Modbus Slave

Addr

1 2 3 4 5 1 2 3 4 5
208 (0xD0) 224 (0xE0)
209 (0xD1) 225 (0xE1)
210 (0xD2) 226 (0xE2)
211 (0xD3) 227 (0xE3)
212 (0xD4) 228 (0xE4)
213 (0xD5) 229 (0xE5)
214 (0xD6) 230 (0xE6)
215 (0xD7) 231 (0xE7)
216 (0xD8) 232 (0xE8)
217 (0xD9) 233 (0xE9)
218 (0xDA) 234 (0xEA)
219 (0xDB) 235 (0xEB)
220 (0xDC) 236 (0xEC)
221 (0xDD) 237 (0xED)
222 (0xDE) 238 (0xED)
223 (0xDF) 239 (0xEF)

Modbus Read Data

UNOlite supports function code both 0x03 and 0x04 to read following registers

  • 0x03: read holding registers
  • 0x04: read input registers
    Request
    Slave Address

    1 byte

    Function code

    1 byte

    Register

    2 bytes

    Length [N]

    2 bytes

    CRC16

    2 bytes

    Response
    Slave Address

    1 byte

    Function code

    1 byte

    Count [2*N]

    1 byte

    Data

    N * 2 bytes

    CRC16

    2 bytes

    Sensor Measurement
    Register Name Description
     

     

     

     

    30001

     

     

     

     

    0x0000

     

     

     

     

    IAQ index

    Give an index according to current PM2.5, PM10, and CO2 concentration. The index also be referenced by IAQ LED:

    GREEN: 0~80 YELLOW: 81~100 RED: 101~400 PURPLE: 401~

    30002 0x0001 Concentration of PM2.5 Unit: μg/m3
    30003 0x0002 Concentration of PM10 Unit: μg/m3
    30004 0x0003 Concentration of carbon

    dioxide (formula CO2)

    Unit: ppm
    30005 0x0004 Concentration of total volatile

    organic compound (TVOC)

    Unit: ppb
    30006 0x0005 Concentration of total volatile

    organic compound (TVOC)

    Unit: μg/m3 (factor 1 ppb = 4.5 μg/m3)
    30009 0x0008 Humidity Unit: 0.01%
    30011 0x000A Celsius temperature Real Temp = (Value – 4500) * 0.01

    Unit: °C

    30018 0x0011 Fahrenheit temperature Real Temp = (Value – 4500) * 0.01

    Unit: °F

    30020 0x0013 Concentration of PM1 Unit: μg/m3
    Sensor State
    Register Name Description
     

    30033

     

    0x0020

     

    PM2.5 sensor

     

     

     

     

    State of sensor hardware module 0x0000: Power off or does not exist 0x0001: Sensor Ready

    0x0002: Warming up 0x0003: Busy 0x00FE: CSERROR

    0x00FF: FAIL

     

    30034

     

    0x0021

     

    PM10 sensor

     

    30035

     

    0x0022

     

    CO2 sensor

     

    30036

     

    0x0023

     

    TVOC sensor

     

    30037

     

    0x0024

     

    Humidity sensor

     

    30038

     

    0x0025

     

    Temperature sensor

     

    30042

     

    0x0029

     

    PM1 sensor

     

    30044

     

    0x002B

     

    IAQ LED state

    0x0000: LED off

    0x0001: LED on

    Device Information
    Register Name Description
     

    30145

    0x0090-

    0x009F

    Model and Product Serial Number An ASCII string consists model name and serial

    number, separated by a comma. For example: “UNO-L,2250L01F9999”

    30209 0x00D0 Main firmware version Number 1 to 65535

    0x0000: device is initializing

    30257 0x0100-

    0x0102

    BT MAC address 6 groups of two hexadecimal digits, e.g.

    F2:11:8F:36:F6:93

    30260 0x0103-

    0x0105

    WIFI MAC address 6 groups of two hexadecimal digits

Modbus Write Command

UNOlite supports function code 0x06 and 0x10 to write request

0x06: write single register

Request
Address

1 byte

Function code

1 byte

Register

2 bytes

Data

2 bytes

CRC16

2 bytes

Response
Address

1 byte

Function code

1 byte

Register

2 bytes

Data

2 bytes

CRC16

2 bytes

0x10: write multiple registers

Request
Address

1 byte

Fn. Code

1 byte

Register

2 bytes

Length[N]

2 bytes

Count[2*N]

1 byte

Data

N * 2 bytes

CRC16

2 bytes

Response
Address

1 byte

Function code

1 byte

Register

2 bytes

Length [N]

2 bytes

CRC16

2 bytes

DELTA-uno-Lite-Modbus-fig-2DELTA-uno-Lite-Modbus-fig-4

Modbus Examples

  1. Read all sensor status from device 208 (0xD0)
    Request D0 03 00 20 00 0B 17 86
    Response D0 03 16 00 01 00 01 00 01 00 01 00 01 00 01 00 FE 00 FE 00 FF 00

    00 00 01 60 8F

  2. Read firmware version from device 208 (0xD0)
    Request D0 03 00 D0 00 01 97 B2
    Response D0 03 02 00 04 45 95
  3. Set rs485 serial configuration, 115200-8-N-1
    Request D0 10 00 60 00 03 06 00 01 C2 00 84 00 BB 56
    Response D0 10 00 60 00 03 92 57

Modbus Exception Response

If device receives a request message without a communication error, but cannot handle the query. It will reply with requested function code plus 0x80. Example, function code 0x3 becomes 0x83

Response format 

Address 1 byte Function code 1 byte Code 1 bytes CRC16

2 bytes

Code list 

Code Name
0x01 ILLEGAL FUNCTION
0x02 ILLEGAL DATA ADDRESS
0x03 ILLEGAL DATA VALUE
0x04 SERVER DEVICE FAILURE
0x05 ACKNOWLEDGE
0x06 SERVER DEVICE BUSY
0x08 MEMORY PARITY ERROR
0x0A GATEWAY PATH UNAVAILABLE
0x0B GATEWAY TARGET DEVICE FAILED TO RESPOND

Note: Please refer to “ModbUs Application_Protocol_V1_1b3” from www.modbus.org