Thank you for choosing Delta’s DVP series PLC. DVP02DA-E2 (DVP04DA-E2) analog output module receives 2 (4) groups of 16-bit digital data from the PLC MPU and converts the digital data into 2 (4) points analog output signals (voltage or current). In addition, you can access the data in the module by applying FROM/TO instructions or write the output value of channels directly by using MOV instruction (Please refer to allocation of special registers D9900 ~ D9999).

  • DVP02DA-E2 (DVP04DA-E2) is an OPEN-TYPE device. It should be installed in a control cabinet free of airborne dust, humidity, electric shock and vibration. To prevent non-maintenance staff from operating DVP02DA-E2 (DVP04DA-E2), or to prevent an accident from damaging DVP02DA-E2 (DVP04DA-E2), the control cabinet in which DVP02DA-E2 (DVP04DA-E2) is installed should be equipped with a safeguard. For example, the control cabinet in which DVP02DA-E2
    (DVP04DA-E2) is installed can be unlocked with a special tool or key.
  • DO NOT connect AC power to any of I/O terminals, otherwise serious damage may occur. Please check all wiring again before DVP02DA-E2 (DVP04DA-E2) is powered up. After DVP02DA-E2 (DVP04DA-E2) is disconnected, Do NOT touch any terminals in a minute. Make sure that the ground terminal on DVP02DA-E2 (DVP04DA-E2) is correctly grounded in order to prevent electromagnetic interference.

Product Profile & Dimension

DELTA DVP02DA-E2 ES2-EX2 Series Analog Input Output Module 1

DELTA DVP02DA-E2 ES2-EX2 Series Analog Input Output Module 2

External Wiring

DELTA DVP02DA-E2 ES2-EX2 Series Analog Input Output Module 3

Note 1: Please isolate analog output and other power wiring.
Note 2: If noise interferes from loaded input wiring terminal is significant, please connect a capacitor with 0.1 ~ 0.47μF 25V for noise filtering.
Note 3: Please connect power module terminal and analog output module terminal to system

I/O Terminal Layout

DELTA DVP02DA-E2 ES2-EX2 Series Analog Input Output Module 4

Electrical Specifications

Digital/Analog module (02D/A & 04D/A)
Power supply voltage 24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%)
Digital/Analog module (02D/A & 04D/A)
Max. rated power consumption  

02DA: 1.5W, 04DA: 3W, supply by external power source.

Connector European standard removable terminal block (Pin pitch: 5mm)
 

Protection

Voltage output is protected by short circuit. Short circuit lasting for too long may cause damage on internal circuits. Current output can

be open circuit.

 

Operation/storage temperature

Operation: 0°C~55°C (temperature), 5~95% (humidity), Pollution degree2

Storage: -25°C~70°C (temperature), 5~95% (humidity)

Vibration/shock immunity International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 & IEC 68-2-27 (TEST Ea)
 

Series connection to DVP-PLC MPU

The modules are numbered from 0 to 7 automatically by their distance from MPU. Max. 8 modules are allowed to connect to MPU and will not occupy any digital I/O points.

Functions Specifications

Digital/Analog module Voltage output Current output
Range of analog output -10V ~ 10V 0 ~ 20mA 4mA ~ 20mA
Range of digital conversion  

-32,000 ~ +32,000

 

0 ~ +32,000

 

0 ~ +32,000

Max./Min. range of digital data  

-32,768 ~ +32,767

 

0 ~ +32,767

 

-6,400 ~ +32,767

Hardware Resolution 14 bits 14 bits 14 bits
Max. output current 5mA
Tolerance load impedance  

1KΩ ~ 2MΩ

 

0 ~ 500Ω

Analog output channel 2 channels or 4 channels / each module
Output impedance 0.5Ω or lower
 

Overall accuracy

±0.5% when in full scale (25°C, 77°F)

±1% when in full scale within the range of 0 ~ 55°C (32 ~ 131°F)

Response time 400μs / each channel
Digital data format 2’s complement of 16 bits
 

 

 

Isolation method

Optical coupler isolation between analog circuits and digital circuits. No isolation among analog channels.

500VDC between digital circuits and Ground 500VDC between analog circuits and Ground 500VDC between analog circuits and digital circuits

500VDC between 24VDC and Ground

Control Register

CR# Attrib. Register name Explanation
 

#0

 

O

 

R

 

Model name

Set up by the system, model code:

DVP02DA-E2 = H’0041; DVP04DA-E2 = H’0081

#1 O R Firmware version Display the current firmware version in hex.
 

#2

 

O

 

R/W

 

CH1 output mode setting

Output mode: Default = H’0000. Take CH1 for example:
CR# Attrib. Register name Explanation
 

#3

 

O

 

R/W

 

CH2 output mode setting

Mode 0 (H’0000): Voltage output (±10V) Mode 1 (H’0001): Current output (0~+20mA)

Mode 2 (H’0002): Current output (+4~+20mA)

Mode -1 (H’FFFF): All channels are unavailable

 

#4

 

O

 

R/W

 

CH3 output mode setting

 

#5

 

O

 

R/W

 

CH4 output mode setting

#16 X R/W CH1 output signal value Voltage output range: K-32,000~K32,000. Current output range: K0~K32,000.

Default: K0.

CR#18~CR#19 of DVP02DA-E2 are

reserved.

#17 X R/W CH2 output signal value
#18 X R/W CH3 output signal value
#19 X R/W CH4 output signal value
#28 O R/W Adjusted Offset value of CH1 Set the adjusted Offset value of CH1 ~ CH4. Default = K0

Definition of Offset:

The corresponding voltage (current) input value when the digital output value = 0

#29 O R/W Adjusted Offset value of CH2
#30 O R/W Adjusted Offset value of CH3
#31 O R/W Adjusted Offset value of CH4
#34 O R/W Adjusted Gain value of CH1 Set the adjusted Gain value of CH1 ~ CH4. Default = K16,000.

Definition of Gain:

The corresponding voltage (current) input value when the digital output value = 16,000

#35 O R/W Adjusted Gain value of CH2
#36 O R/W Adjusted Gain value of CH3
#37 O R/W Adjusted Gain value of CH4
Adjusted Offset Value, Adjusted Gain Value:

Note1: When using Mode 2, the channel do NOT provide setups for adjusted Offset or Gain value.

Note2: When input mode changes, the adjusted Offset or Gain value automatically returns to defaults.

#40 O R/W Function: Set value changing prohibited Prohibit set value changing in CH1 ~ CH4. Default= H’0000.
#41 X R/W Function: Save all the set values Save all the set values. Default =H’0000.
#43 X R Error status Register for storing all error status. Refer to table of error status for more information.
 

#100

 

O

 

R/W

Function: Enable/Disable limit detection Upper and lower bound detection, b0~b3 corresponds to CH1~CH4 (0: Disable/ 1: Enable). Default= H’0000.
 

 

#101

 

 

X

 

 

R/W

 

 

Upper and lower bound status

Display the upper and lower bound status. (0: Not exceed /1: Exceeds upper or lower bound value), b0~b3 corresponds to Ch1~Ch4 for lower bound detection result; b8~b11 corresponds to CH1~CH4 for upper

bound detection result..

#102 O R/W Set value of CH1 upper bound  

 

Set value of CH1~CH4 upper bound. Default

= K32000.

#103 O R/W Set value of CH2 upper bound
#104 O R/W Set value of CH3 upper bound
#105 O R/W Set value of CH4 upper bound
#108 O R/W Set value of CH1 lower bound  

 

Set value of CH1~CH4 lower bound. Default

= K-32000.

#109 O R/W Set value of CH2 lower bound
#110 O R/W Set value of CH3 lower bound
#111 O R/W Set value of CH4 lower bound
#114 O R/W Output update time of CH1 Set value of CH1~CH4 lower bound. Setting
CR# Attrib. Register name Explanation
#115 O R/W Output update time of CH2 range:K0~K100. Default =H’0000.
#116 O R/W Output update time of CH3
#117 O R/W Output update time of CH4
 

#118

 

O

 

R/W

 

LV output mode setting

Set the output mode of CH1~CH4 when the power is at LV (low voltage) condition.

Default= H’0000.

Symbols:

O: When CR#41 is set to H’5678, the set value of CR will be saved. X: set value will not be saved.

R: able to read data by using FROM instruction.

W: able to write data by using TO instruction.

Description
 

bit0

 

K1 (H’1)

 

Power supply error

 

bit11

 

K2048(H’0800)

Upper / lower bound setting error
 

bit1

 

K2 (H’2)

 

Reserved

 

bit12

 

K4096(H’1000)

Set value changing prohibited
 

bit2

 

K4 (H’4)

 

Upper / lower bound error

 

bit13

 

K8192(H’2000)

Communication breakdown on next module
bit9 K512(H’0200) Mode setting error  
$Note: Each error status is determined by the corresponding bit (b0 ~ b13) and there may be more than 2 errors occurring at the same time. 0 = normal; 1 = error

Module Reset (available for firmware V1.12 or above): When modules need reset, write H’4352 to CR#0, then wait for one second and then power off and restart. The instruction initializes all parameter setups. To avoid the resetting process affecting the normal operation of other modules, it is recommended to connect only one module at a time.

Explanation on Special Registers D9900~D9999

When DVP-ES2 MPU is connected with modules, registers D9900~D9999 will be reserved for storing values from modules. You can apply MOV instruction to operate values in D9900~D9999.
When ES2 MPU is connected with DVP02DA-E2/DVP04DA-E2, the configuration of special registers is as below:

Module #0 Module #1 Module #2 Module #3 Module #4 Module #5 Module #6 Module #7  

Description

D1320 D1321 D1322 D1323 D1324 D1325 D1326 D1327 Model Code
D9900 D9910 D9920 D9930 D9940 D9950 D9960 D9970 CH1 output value
D9901 D9911 D9921 D9931 D9941 D9951 D9961 D9971 CH2 output value
D9902 D9912 D9922 D9932 D9942 D9952 D9962 D9972 CH3 output value
D9903 D9913 D9923 D9933 D9943 D9953 D9963 D9973 CH4 output value

Adjust D/A Conversion Curve

Users can adjust the conversion curves according to the actual needs by changing the Offset value (CR#28 ~ CR#31) and Gain value (CR#34 ~ CR#37).
Gain: The corresponding voltage/current input value when the digital output value = 16,000.
Offset: The corresponding voltage/current input value when the digital output value = 0.

  • Equation for voltage output Mode0: 0.3125mV = 20V/64,000

DELTA DVP02DA-E2 ES2-EX2 Series Analog Input Output Module 5

Mode 0 (CR#2 ~ CR#5) -10V ~ +10V,Gain = 5V (16,000),Offset = 0V (0)
Range of digital data -32,000 ~ +32,000
Max./Min. range of digital data -32,768 ~ +32,767
  • Current output – mode 1:DELTA DVP02DA-E2 ES2-EX2 Series Analog Input Output Module 6
Mode 1 (CR#2 ~ CR#5) 0mA ~ +20mA,Gain = 10mA (16,000),Offset = 0mA (0)
Range of digital data 0 ~ +32,000
Max./Min. range of digital data 0 ~ +32,767

Current output – mode 2:

DELTA DVP02DA-E2 ES2-EX2 Series Analog Input Output Module 7

Mode 2 (CR#2 ~ CR#5) 4mA ~ +20mA,Gain = 12mA (19,200),Offset = 4mA (6,400)
Range of digital data 0 ~ +32,000
Max./Min. range of digital data -6400 ~ +32,767