DELTA logo

DELTA DVP02DA-E2 ES2-EX2 Series Analog Input Output Module

DELTA DVP02DA-E2 ES2-EX2 Series Analog Input Output Module

Thank you for choosing Delta’s DVP series PLC. DVP02DA-E2 (DVP04DA-E2) analog output module receives 2 (4) groups of 16-bit digital data from the PLC MPU and converts the digital data into 2 (4) points analog output signals (voltage or current). In addition, you can access the data in the module by applying FROM/TO instructions or write the output value of channels directly by using MOV instruction (Please refer to allocation of special registers D9900 ~ D9999).

  • DVP02DA-E2 (DVP04DA-E2) is an OPEN-TYPE device. It should be installed in a control cabinet free of airborne dust, humidity, electric shock and vibration. To prevent non-maintenance staff from operating DVP02DA-E2 (DVP04DA-E2), or to prevent an accident from damaging DVP02DA-E2 (DVP04DA-E2), the control cabinet in which DVP02DA-E2 (DVP04DA-E2) is installed should be equipped with a safeguard. For example, the control cabinet in which DVP02DA-E2
    (DVP04DA-E2) is installed can be unlocked with a special tool or key.
  • DO NOT connect AC power to any of I/O terminals, otherwise serious damage may occur. Please check all wiring again before DVP02DA-E2 (DVP04DA-E2) is powered up. After DVP02DA-E2 (DVP04DA-E2) is disconnected, Do NOT touch any terminals in a minute. Make sure that the ground terminal on DVP02DA-E2 (DVP04DA-E2) is correctly grounded in order to prevent electromagnetic interference.

Product Profile & Dimension

DELTA DVP02DA-E2 ES2-EX2 Series Analog Input Output Module 1

DELTA DVP02DA-E2 ES2-EX2 Series Analog Input Output Module 2

External Wiring

DELTA DVP02DA-E2 ES2-EX2 Series Analog Input Output Module 3

Note 1: Please isolate analog output and other power wiring.
Note 2: If noise interferes from loaded input wiring terminal is significant, please connect a capacitor with 0.1 ~ 0.47μF 25V for noise filtering.
Note 3: Please connect power module terminal and analog output module terminal to system

I/O Terminal Layout

DELTA DVP02DA-E2 ES2-EX2 Series Analog Input Output Module 4

Electrical Specifications

Digital/Analog module (02D/A & 04D/A)
Power supply voltage24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%)
Digital/Analog module (02D/A & 04D/A)
Max. rated power consumption 

02DA: 1.5W, 04DA: 3W, supply by external power source.

ConnectorEuropean standard removable terminal block (Pin pitch: 5mm)
 

Protection

Voltage output is protected by short circuit. Short circuit lasting for too long may cause damage on internal circuits. Current output can

be open circuit.

 

Operation/storage temperature

Operation: 0°C~55°C (temperature), 5~95% (humidity), Pollution degree2

Storage: -25°C~70°C (temperature), 5~95% (humidity)

Vibration/shock immunityInternational standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 & IEC 68-2-27 (TEST Ea)
 

Series connection to DVP-PLC MPU

The modules are numbered from 0 to 7 automatically by their distance from MPU. Max. 8 modules are allowed to connect to MPU and will not occupy any digital I/O points.

Functions Specifications

Digital/Analog moduleVoltage outputCurrent output
Range of analog output-10V ~ 10V0 ~ 20mA4mA ~ 20mA
Range of digital conversion 

-32,000 ~ +32,000

 

0 ~ +32,000

 

0 ~ +32,000

Max./Min. range of digital data 

-32,768 ~ +32,767

 

0 ~ +32,767

 

-6,400 ~ +32,767

Hardware Resolution14 bits14 bits14 bits
Max. output current5mA
Tolerance load impedance 

1KΩ ~ 2MΩ

 

0 ~ 500Ω

Analog output channel2 channels or 4 channels / each module
Output impedance0.5Ω or lower
 

Overall accuracy

±0.5% when in full scale (25°C, 77°F)

±1% when in full scale within the range of 0 ~ 55°C (32 ~ 131°F)

Response time400μs / each channel
Digital data format2’s complement of 16 bits
 

 

 

Isolation method

Optical coupler isolation between analog circuits and digital circuits. No isolation among analog channels.

500VDC between digital circuits and Ground 500VDC between analog circuits and Ground 500VDC between analog circuits and digital circuits

500VDC between 24VDC and Ground

Control Register

CR#Attrib.Register nameExplanation
 

#0

 

O

 

R

 

Model name

Set up by the system, model code:

DVP02DA-E2 = H’0041; DVP04DA-E2 = H’0081

#1ORFirmware versionDisplay the current firmware version in hex.
 

#2

 

O

 

R/W

 

CH1 output mode setting

Output mode: Default = H’0000. Take CH1 for example:
CR#Attrib.Register nameExplanation
 

#3

 

O

 

R/W

 

CH2 output mode setting

Mode 0 (H’0000): Voltage output (±10V) Mode 1 (H’0001): Current output (0~+20mA)

Mode 2 (H’0002): Current output (+4~+20mA)

Mode -1 (H’FFFF): All channels are unavailable

 

#4

 

O

 

R/W

 

CH3 output mode setting

 

#5

 

O

 

R/W

 

CH4 output mode setting

#16XR/WCH1 output signal valueVoltage output range: K-32,000~K32,000. Current output range: K0~K32,000.

Default: K0.

CR#18~CR#19 of DVP02DA-E2 are

reserved.

#17XR/WCH2 output signal value
#18XR/WCH3 output signal value
#19XR/WCH4 output signal value
#28OR/WAdjusted Offset value of CH1Set the adjusted Offset value of CH1 ~ CH4. Default = K0

Definition of Offset:

The corresponding voltage (current) input value when the digital output value = 0

#29OR/WAdjusted Offset value of CH2
#30OR/WAdjusted Offset value of CH3
#31OR/WAdjusted Offset value of CH4
#34OR/WAdjusted Gain value of CH1Set the adjusted Gain value of CH1 ~ CH4. Default = K16,000.

Definition of Gain:

The corresponding voltage (current) input value when the digital output value = 16,000

#35OR/WAdjusted Gain value of CH2
#36OR/WAdjusted Gain value of CH3
#37OR/WAdjusted Gain value of CH4
Adjusted Offset Value, Adjusted Gain Value:

Note1: When using Mode 2, the channel do NOT provide setups for adjusted Offset or Gain value.

Note2: When input mode changes, the adjusted Offset or Gain value automatically returns to defaults.

#40OR/WFunction: Set value changing prohibitedProhibit set value changing in CH1 ~ CH4. Default= H’0000.
#41XR/WFunction: Save all the set valuesSave all the set values. Default =H’0000.
#43XRError statusRegister for storing all error status. Refer to table of error status for more information.
 

#100

 

O

 

R/W

Function: Enable/Disable limit detectionUpper and lower bound detection, b0~b3 corresponds to CH1~CH4 (0: Disable/ 1: Enable). Default= H’0000.
 

 

#101

 

 

X

 

 

R/W

 

 

Upper and lower bound status

Display the upper and lower bound status. (0: Not exceed /1: Exceeds upper or lower bound value), b0~b3 corresponds to Ch1~Ch4 for lower bound detection result; b8~b11 corresponds to CH1~CH4 for upper

bound detection result..

#102OR/WSet value of CH1 upper bound 

 

Set value of CH1~CH4 upper bound. Default

= K32000.

#103OR/WSet value of CH2 upper bound
#104OR/WSet value of CH3 upper bound
#105OR/WSet value of CH4 upper bound
#108OR/WSet value of CH1 lower bound 

 

Set value of CH1~CH4 lower bound. Default

= K-32000.

#109OR/WSet value of CH2 lower bound
#110OR/WSet value of CH3 lower bound
#111OR/WSet value of CH4 lower bound
#114OR/WOutput update time of CH1Set value of CH1~CH4 lower bound. Setting
CR#Attrib.Register nameExplanation
#115OR/WOutput update time of CH2range:K0~K100. Default =H’0000.
#116OR/WOutput update time of CH3
#117OR/WOutput update time of CH4
 

#118

 

O

 

R/W

 

LV output mode setting

Set the output mode of CH1~CH4 when the power is at LV (low voltage) condition.

Default= H’0000.

Symbols:

O: When CR#41 is set to H’5678, the set value of CR will be saved. X: set value will not be saved.

R: able to read data by using FROM instruction.

W: able to write data by using TO instruction.

Description
 

bit0

 

K1 (H’1)

 

Power supply error

 

bit11

 

K2048(H’0800)

Upper / lower bound setting error
 

bit1

 

K2 (H’2)

 

Reserved

 

bit12

 

K4096(H’1000)

Set value changing prohibited
 

bit2

 

K4 (H’4)

 

Upper / lower bound error

 

bit13

 

K8192(H’2000)

Communication breakdown on next module
bit9K512(H’0200)Mode setting error 
$Note: Each error status is determined by the corresponding bit (b0 ~ b13) and there may be more than 2 errors occurring at the same time. 0 = normal; 1 = error

Module Reset (available for firmware V1.12 or above): When modules need reset, write H’4352 to CR#0, then wait for one second and then power off and restart. The instruction initializes all parameter setups. To avoid the resetting process affecting the normal operation of other modules, it is recommended to connect only one module at a time.

Explanation on Special Registers D9900~D9999

When DVP-ES2 MPU is connected with modules, registers D9900~D9999 will be reserved for storing values from modules. You can apply MOV instruction to operate values in D9900~D9999.
When ES2 MPU is connected with DVP02DA-E2/DVP04DA-E2, the configuration of special registers is as below:

Module #0Module #1Module #2Module #3Module #4Module #5Module #6Module #7 

Description

D1320D1321D1322D1323D1324D1325D1326D1327Model Code
D9900D9910D9920D9930D9940D9950D9960D9970CH1 output value
D9901D9911D9921D9931D9941D9951D9961D9971CH2 output value
D9902D9912D9922D9932D9942D9952D9962D9972CH3 output value
D9903D9913D9923D9933D9943D9953D9963D9973CH4 output value

Adjust D/A Conversion Curve

Users can adjust the conversion curves according to the actual needs by changing the Offset value (CR#28 ~ CR#31) and Gain value (CR#34 ~ CR#37).
Gain: The corresponding voltage/current input value when the digital output value = 16,000.
Offset: The corresponding voltage/current input value when the digital output value = 0.

  • Equation for voltage output Mode0: 0.3125mV = 20V/64,000

DELTA DVP02DA-E2 ES2-EX2 Series Analog Input Output Module 5

Mode 0 (CR#2 ~ CR#5)-10V ~ +10V,Gain = 5V (16,000),Offset = 0V (0)
Range of digital data-32,000 ~ +32,000
Max./Min. range of digital data-32,768 ~ +32,767
  • Current output – mode 1:DELTA DVP02DA-E2 ES2-EX2 Series Analog Input Output Module 6
Mode 1 (CR#2 ~ CR#5)0mA ~ +20mA,Gain = 10mA (16,000),Offset = 0mA (0)
Range of digital data0 ~ +32,000
Max./Min. range of digital data0 ~ +32,767

Current output – mode 2:

DELTA DVP02DA-E2 ES2-EX2 Series Analog Input Output Module 7

Mode 2 (CR#2 ~ CR#5)4mA ~ +20mA,Gain = 12mA (19,200),Offset = 4mA (6,400)
Range of digital data0 ~ +32,000
Max./Min. range of digital data-6400 ~ +32,767

Documents / Resources

DELTA DVP02DA-E2 ES2-EX2 Series Analog Input Output Module [pdf] Instruction Manual
DVP02DA-E2 ES2-EX2 Series Analog Input Output Module, DVP02DA-E2, ES2-EX2 Series Analog Input Output Module, Analog Input Output Module, Input Output Module, Output Module, Module

References

Leave a comment

Your email address will not be published. Required fields are marked *