DAUDIN iO-GRID m and FX5U Modbus RTU
Product Information
Part No. |
Specification |
Description |
GFMS-RM01S |
Master Modbus RTU, 1 Port |
Main Controller |
GFDI-RM01N |
Digital Input 16 Channel |
Digital Input |
GFDO-RM01N |
Digital Output 16 Channel / 0.5A |
Digital Output |
GFPS-0202 |
Power 24V / 48W |
Power Supply |
GFPS-0303 |
Power 5V / 20W |
Power Supply Interface Module |
0170-0101 |
8 pin RJ45 female connector/RS-485 Interface |
Interface Module |
Product Usage Instructions
MLESEC-FX5U Connection Setup
- Launch GX Works3 software.
- Select the Parameters menu from the Navigate on the left side.
- Click on 485 Connector under the Module Parameters menu.
FX5U Hardware Connection
- The connector is on the left side of the FX5U and uses RS485 connections.
- Connect the COM (RS485 A, B) on the left of the FX5U to the interface module (1/2) to convert it to a RJ45 connector before connecting it to the main controller.
FX5U Connection Setup
- Set up the communication format in Protocol Format.
- From the drop-down menu, select MODBUS_RTU Communication.
- From the drop-down menu, select None.
- From the drop-down menu, select 1bit.
- From the drop-down menu, select Equipment Baud.
- The communication format setting must be consistent with the device being connected.
- Reading of the communication register:
- Command functions are listed below:
Station No. |
Function code |
Register for reading |
Data Amount for Reading |
Register for storage |
Initial address of the command execution |
01 |
03 |
10 00 |
00 01 |
- Writing of the communication register:
- Command functions are listed below:
Station No. |
Function code |
Register for writing |
Data Amount for Writing |
Register for reading |
Initial address of the command execution |
01 |
10 |
20 00 |
00 02 |
Remote I/O Module System Configuration List
Product Description
- The interface module is used externally to convert FX5U’s communication module (Modbus RTU) to a RJ45 connector
- The main controller is in charge of the management and dynamic configuration of I/O parameters and so on.
- The power module and interface module are standard for remote I/Os and users can choose the model or brand they prefer.
MLESEC-FX5U Connection Setup
This section details how to use the GX Works3 software to connect FX5U. For more details, please refer to the “Commands/Universal FUN/FB” chapter of the MELSEC iQ-F FX5 Programming Manual
FX5U Hardware Connection
- The connector is on the left side of the FX5U and uses RS485 connections

- Connect the COM (RS485 A, B) on the left of the FX5U to the interface module (1/2) to convert it to a RJ45 connector before connecting it to the main controller

FX5U Connection Setup
- Launch GX Works3 and select the “Parameters” menu from the “Navigate” on the left side, then click on “485 Connector” under the “Module Parameters” menu

- Set up the communication format in “Protocol Format”

- Reading of the communication register

- Writing of the communication register
Notes:
- iO-GRID ’s first GFDI-RM01N has the register address at 1000(HEX)
- iO-GRID ’s first GFDO-RM01N has the register address at 2000(HEX).
- Programming Example:
Control with one GFDI-RM01N and one GFDO-RM01N When DI_1000.0 has received a signal and is triggered, DO_2000.0 will output a signal as it is connected