DAUDIN Beijer HMI Modbus RTU Connection
Product Information
The 2302EN V2.0.0 Beijer HMI Modbus RTU Connection Operating Manual provides instructions on how to connect Beijer HMI with iO-GRID using the iX Developer program. The system includes a main controller, digital input and output modules, a power supply, and an interface module to convert Beijer RS-485’s communication port
(Modbus RTU) to an 8-pin RJ45 female connector/RS-485 interface.
Remote I/O Module System Configuration List
Part No. | Specification |
---|---|
GFMS-RM01S | Master Modbus RTU, 1 Port |
GFDI-RM01N | Digital Input 16 Channel |
GFDO-RM01N | Digital Output 16 Channel / 0.5A |
GFPS-0202 | Power 24V / 48W |
GFPS-0303 | Power 5V / 20W |
0170-0101 | 8 pin RJ45 female connector/RS-485 Interface |
Product Description
- The interface module converts Beijer RS-485’s communication port (Modbus RTU) to an 8-pin RJ45 female connector/RS-485 interface.
- The main controller manages and dynamically configures I/O parameters.
- The power module and interface module are standard for remote I/Os, and users can choose the model or brand they prefer.
Product Usage Instructions
Beijer HMI Hardware Connection
- Locate the connection port on the right at the bottom of the Beijer HMI machine.
- Connect the COM (RS485 A/B) at the bottom of the machine to the interface module (1/2) to convert it into an RJ45 connector, which will be connected to the main controller.
Beijer HMI Connection Setup
- Launch iX Developer and select MODICON and Modbus Master to add a new controller.
- Click on the Controller tab to enter the controller setup page. Select the controller and then click on Settings.
- Under Connection Method Setup:
- From the Communication mode drop-down menu, select Serial.
- Set up the default station number.
- From the Modbus protocol drop-down menu, select RTU.
- From the 32-bit World mapping drop-down menu, select
Little-endian. - From the Force function code 0x10 drop-down menu, select
Enable. - From the String swap drop-down menu, select Disable.
- Under Serial Settings:
- Set the Port to COM2 or COM3.
- From the Baud drop-down menu, select 115200.
- From the Parity drop-down menu, select None.
- From the Data Bits drop-down menu, select 8.
- From the Stop Bits drop-down menu, select 1.
- For using 485 pin with COM2 and COM3, please refer to 2.1
Beijer HMI Hardware Connection.
- Click on Tab to enter the tab setting page. Next, click on New and set up the tab register’s location.
- iO-GRIDM’s first GFDI-RM01N has the initial address at 44096.
- iO-GRIDM’s first GFDO-RM01N has the initial address at 48192.
Remote I/O Module System Configuration List
Part No. | Specification | Description |
GFMS-RM01S | Master Modbus RTU, 1 Port | Main Controller |
GFDI-RM01N | Digital Input 16 Channel | Digital Input |
GFDO-RM01N | Digital Output 16 Channel / 0.5A | Digital Output |
GFPS-0202 | Power 24V / 48W | Power Supply |
GFPS-0303 | Power 5V / 20W | Power Supply |
0170-0101 | 8 pin RJ45 female connector/RS-485 Interface | Interface Module |
Product Description
- The interface module is used externally to convert Beijer RS-485’s communication port (Modbus RTU) to a RJ45 connector
- The main controller is in charge of the management and dynamic configuration of I/O parameters and so on.
- The power module and interface module are standard for remote I/Os and users can choose the model or brand they prefer.
Beijer HMI Connection Setup
This chapter explains how to use the iX Developer program to connect Beijer HMI with iO-GRID. For detailed information, please refer to iX Developer User Manual
Beijer HMI Hardware Connection
- The connection port is on the right at the bottom of the machine. Take X2 control for example. It uses RS485 COM2 or COM3
Beijer HMI Connection Setup
- Launch iX Developer and select “MODICON” and “Modbus Master” to add a new controller
- Click on the “Controller” tab to enter the controller setup page. Select the controller and then click on “Settings”
- Connection method setup
- Ⓐ From the “Communication mode” drop-down menu, select “Serial”
- Ⓑ Setup the default station number
- Ⓒ From the “Modbus protocol” drop-down menu, select “RTU”
- Ⓓ From the “32-bit World mapping” drop-down menu, select “Little-endian”
- Ⓔ From the “Force function code 0x10” drop-down menu, select “Enable”
- Ⓕ From the “String swap” drop-down menu, select “Disable”
- Serial Settings
- Ⓐ Set Port to COM2 or COM3
- Ⓑ From the “Baud” drop-down menu, select “115200”
- Ⓒ From the “Parity” drop-down menu, select “None”
- Ⓓ From the “Data bits” drop-down menu, select “8”
- Ⓔ From the “Stop bits” drop-down menu, select “1
Notes:
The demonstration in the Connection Operating Manual uses COM3
For using 485 pin with COM2 and COM3, please refer to2.1 Beijer HMI Hardware Connection
- Ⓐ Set Port to COM2 or COM3
- Click on “Tab” to enter the tab setting page. Next, click on “New” and set up the tab register’s location
※ iO-GRIDM ’s first GFDI-RM01N has the initial address at 44096
※ iO-GRIDM ’s first GFDO-RM01N has the initial address at 48192
Documents / Resources
![]() |
DAUDIN Beijer HMI Modbus RTU Connection [pdf] User Manual Beijer HMI Modbus RTU Connection, Beijer HMI, Modbus RTU Connection |