Mounting guide Danfoss VHX-MONO valve set for floor connection
VHX-MONO Valve Set For Floor Connection
Free connection (left or right) – return always on thermostat side.
Be aware of measurement B when cutting pipes.
Connect valve housing on pipes.
Dimension | Danfoss code | B (mm) | |
Fittings for soft steel and copper tubes![]() |
8 10 12 14 15 16 |
013G4108 013G4110 013G4112 013G4114 013G4115 013G4116 |
18 18 18 18 24 24 |
Fittings for VPE PEX tubes![]() |
12 x 1.1 12 x 2 14 x 2 15 x 2.5 16 x 2 |
013G4143 013G4142 013G4144 013G4147 013G4146 |
16 16 16 16 16 |
Fittings for AluPEX tubes![]() |
12 x 2 14 x 2 16 x 2 |
013G4172 013G4174 013G4176 |
16 16 16 |
Fix valve flange to radiator connections.
Lower the radiator until the flange is supported by the valve.
Mark position and mount radiator on wall.
Tighten valve to radiator. NB! Remember gaskets.
Presetting and k -values for Xp = 0.5 -2K
Valve setting | 1 | 2 | 3 | 4 | 5 | 6 | 7 | N |
kv-value (m3/h) | 0.12 | 0.15 | 0.20 | 0.25 | 0.30 | 0.36 | 0.38 | 0.40 |
Preset kv on valve and connect thermostat, if not already done.
013R9432 VIUYJ302 © Danfoss 07/2007
Documents / Resources
![]() |
Danfoss VHX-MONO Valve Set For Floor Connection [pdf] User Guide 013G4108, 013G4110, 013G4112, 013G4114, 013G4115, 013G4116, 013G4142, 013G4143, 013G4144, 013G4146, 013G4147, 013G4172, 013G4174, 013G4176, VHX-MONO Valve Set For Floor Connection, VHX-MONO, Valve Set For Floor Connection, For Floor Connection, Floor Connection |