Danfoss VACON NXP and VACON NXC AC Drives
Continuous control. Pure power
VACON® NXP is a premium air-cooled AC drive for use in all applications where reliability, robust performance, precision and power are required. These drives are available in the power range from 0.55 kW to 2,000 kW.
Ideal for demanding applications
VACON® NXP range offers the ultimate in motor control, for both induction and permanent magnet (PM) motors, gearless drive applications and paralleling solutions for high power motors. VACON® NXP is the smart drive of choice. With fast fieldbus options and exceptional programming flexibility, your VACON® NXP is easily integrated into any plant’s automation system. Satisfied customers also rely on our enclosed cabinet drive solution, VACON® NXC, to perform in the most challenging industrial environments such as oil and gas, extrusion, mining, pulp and paper, water and wastewater applications. With improved functional safety, extensive approvals in place and comprehensive maintenance tools, you can be sure that your VACON® AC drives will give you the best possible control and ensure high operational quality and availability over the entire lifetime of your system. Our VACON® NXP portfolio fulfills key international standards and global requirements, including safety and EMC and Harmonics approvals.
In harmony with the environment
Our commitment to being a environmentally responsible company is exemplified in our energy-saving products and solutions. We have developed our manufacturing process in order to minimize the impact on the environment. All excess materials in the production and service processes are carefully sorted and recycled.
We continue to develop innovative solutions utilizing regenerative energy and smart grid technology to help customers effectively monitor and control energy use and costs. At your service Whether you are an original equipment manufacturer (OEM), system integrator, brand label customer, distributor or end user, Danfoss Drives provides services to help you meet your business targets. Our global service solutions are available 24/7 throughout the product lifecycle with the intent to minimize the total cost of ownership and environmental load.
VACON® NXP/NXC
Multiple options
- VACON® NXP Control
VACON® NXP offers a high-performance control platform for all demanding drive applications. The microcontroller provides both exceptional processing power and small footprint. The VACON® NXP supports both induction and permanent magnet motors in open and closed loop control modes. It also provides bumpless control for transferring between open loop and closed loop. VACON® Programming tool can be used to improve performance and save costs by integrating customer-specific functionality into the drive. The same control board is used in all VACON® NXP drives, allowing the maximum utilization of VACON® NXP control features over a wide power and voltage range. - Option boards
Our VACON® NXP Control provides exceptional modularity by offering five (A, B, C, D and E) plug-in extension slots. Fieldbus boards, encoder boards as well as wide range of IO boards can simply be plugged-in at any time without the need to remove any other components. A listing of all options boards is provided on page 21. - Fieldbus options
Your VACON® NXP is easily integrated within a plant’s automation system by using plug-in fieldbus option boards including PROFIBUS DP, Modbus RTU, DeviceNet and CANopen. Fieldbus technology ensures increased control and monitoring of the process equipment with reduced cabling – ideal for industries where the need to ensure that products are produced under the right conditions is of paramount importance. An external +24 V supply option enables communication with the control unit even if the main supply is switched off. Fast drive-to-drive communication is possible using our fast SystemBus fiber optic communication. communication is possible using our fast SystemBus fiber optic communication. Profibus DP | DeviceNet | Modbus RTU | CANopen - Ethernet connectivity
VACON® NXP is the smart drive of choice, as there is no need to purchase additional communication tools. Ethernet connectivity allows remote drive access for monitoring, configuring and troubleshooting. Our Ethernet protocols such as PROFINET IO, EtherNet/IP and Modbus/TCP are available for all VACON® NXP drives. New Ethernet protocols are being continuously developed.
Modbus/TCP | PROFINET IO + System Redundancy S2 and PROFISAFE | EtherNet/IP
Functional safety
Advanced Safety Options
The VACON Advanced Safety Options operate the safety functions of an AC drive via the PROFIsafe fieldbus or I/O control. They improve flexibility by connecting safety devices within a plant.
Safe Stop functions
- STO – Safe Torque Off
- SS1 – Safe Stop 1
- SS2 – Safe Stop 2
- SBC – Safe Brake Control
- SQS – Safe Quick Stop
Safe Speed functions
- SLS – Safely-limited Speed
- SSM – Safe Speed Monitor
- SSR – Safe Speed Range
- SMS – Safe Maximum Speed
ATEX certified thermistor input
An ATEX approved thermistor input is available as an integrated option. Certified and compliant with the European ATEX directive 94/9/EC, the integrated thermistor input is specially designed for the temperature supervision of motors that are placed in areas in which potentially explosive gas, vapor, mist or air mixtures are present and areas with combustible dust. Typical industries requiring such supervision include chemical, petrochemical, marine, metal, mechanical, mining, and oil drilling. If oveheating is detected, the drive immediately stops feeding energy to the motor. As no external components are needed, the cabling is minimized, improving reliability and saving on both space and costs.
DC cooling fans
VACON® NXP high-performance air-cooled products are equipped with DC fans. This significantly increases the reliability and lifetime of the fan also fulfilling the ERP2015 directive on decreasing fan losses. Likewise, the DC-DC supply board component ratings fulfill industrial requirement levels.
Conformal coating
To increase performance and durability, conformally coated circuit boards (also known as varnished boards) are provided as standard for power modules (FR7 – FR14). The upgraded boards offer reliable protection against dust and moisture and extend the lifetime of the drive and critical components.
Commissioning made easy
User-friendly keypad
The user interface is intuitive to use. You will enjoy the keypad’s well-structured menu system that allows for fast commissioning and trouble-free operation.
- Removable panel with plug-in connection
- Graphical and text keypad with multiple language support
- Text display multi-monitoring function
- Parameter backup and copy function with the panel’s internal memory
- The startup wizard ensures a hassle-free set up. Choose the language, application type and main parameters during the first power-up.
Documentation wizard
Make use of our VACON® Documentation Wizard and achieve dramatic savings in engineering time. The Documentation Wizard is a technical documentation tool, which creates a complete set of drawings for each VACON® NXC configuration. Just enter the product information, i.e. a type code, required variations and extra equipment (plus codes) into the user interface field, and the tool will automatically generate the documentation in any of the following formats: DWG (AutoCAD) drawings, DXF (AutoCAD) drawings, PDF (Adobe reader) and E-plan project (prj).
VACON® NCDrive
VACON® NCDrive is used for setting, copying, storing, printing, monitoring and controlling parameters. The VACON® NCDrive communicates with the drive via the following interfaces: RS-232, Ethernet TCP/IP, CAN (fast multiple drive monitoring), CAN@Net (remote monitoring). VACON® NCDrive also includes a handy Datalogger function, which offers you the possibility to monitor and analyze data. PC-tools can be downloaded from http://drives.danfoss.com
All-in-one application package
The All-in-One application package has seven built-in software applications, which can be selected with one parameter. In addition to the All-in-One package, we offer several segment specific and advanced applications such as System Interface application, Marine application, Lift application and Shaft Synchronisation application for more demanding uses. VACON® NXP applications can be downloaded from http://drives.danfoss.com
High power and improved redundancy
VACON® DriveSync is our innovative control concept for running standard drives in parallel to control high-power AC motors or increase the redundancy of a system. This concept suits single or multiple winding motors typically above 1 MW.
Powerful AC drives can be built using standard drive components and have the following benefits:
- The system is modular and easy to extend
- High total power can be obtained by combining smaller drives
- System redundancy is higher than in a conventional drive because each unit can run independently
- Individual drive is easy to maintain and service
- Identical units reduce the required amount of spare parts thus reducing overall costs
- No special skills are required for the engineering, installation, commissioning and maintenance of drives as they are comprised of standard modules
- It is possible to run multiple winding motors with a phase shift between the windings
Typical VACON® DriveSynch examples using VACON® NXP/NXC drives
Mains voltage | AC drive type 2 x NXC 1150 5 A 2 L 0 SSF | Loadability | Motor shaft power | Frame size 2 x FR13 | Dimensions and weightW x H x D (mm)/kg 1606 x 2275 x 605/1350 | ||||||
Low (+40°C) | High (+50°C) | Maximum current IS [A] 3492 | 400 V supply | ||||||||
Rated conti- nuous current IL [A]2150 | 10%overload current [A]2365 | Rated conti- nuous current IH [A]1940 | 50%overload current [A]2910 | 10%overload P [kW] 1200 | 50%overload P [kW] 1100 | ||||||
380-500 V50/60 Hz | |||||||||||
2 x NXC 1300 5 A 2 L 0 SSF | 2470 | 2717 | 2185 | 3278 | 3933 | 1350 | 1100 | ||||
2 x NXC 1450 5 A 2 L 0 SSF | 2755 | 3031 | 2470 | 3705 | 4446 | 1500 | 1350 | ||||
3 x NXC 1150 5 A 2 L 0 SSF | 3278 | 3605 | 2936 | 4403 | 5284 | 1800 | 1500 | 3 x FR13 | 1606 x 2275 x 605/1350 | ||
3 x NXC 1300 5 A 2 L 0 SSF | 3705 | 4076 | 3278 | 4916 | 5900 | 2000 | 1800 | ||||
3 x NXC 1450 5 A 2 L 0 SSF | 4133 | 4546 | 3705 | 5558 | 6669 | 2250 | 2000 |
Values are given at switching frequency 2.0 kHz.
Mains voltage | AC drive type 2 x NXC 0920 6 A 2 L 0 SSF | Loadability | Motor shaft power | Frame size 2 x FR13 | Dimensions and weightW x H x D (mm)/kg 1406 x 2275 x 605/1250 | ||||||
Low (+40°C) | High (+50°C) | Maximum current IS [A] 2679 | 690 V supply | ||||||||
Rated conti- nuous current IL [A]1748 | 10%overload current [A]1920 | Rated conti- nuous current IH [A]1500 | 50%overload current [A]2337 | 10%overload P [kW] 1710 | 50%overload P [kW] 1520 | ||||||
525-690 V50/60 Hz | |||||||||||
2 x NXC 1030 6 A 2 L 0 SSF | 1810 | 2000 | 1500 | 2337 | 2679 | 1710 | 1520 | ||||
2 x NXC 1180 6 A 2 L 0 SSF* | 1950 | 2140 | 1630 | 2500 | 3335 | 1900 | 1610 | ||||
3 x NXC 0920 6 A 2 L 0 SSF | 2622 | 2884 | 2337 | 3490 | 4019 | 2500 | 2200 | 3 x FR13 | 1406 x 2275 x 605/1250 | ||
3 x NXC 1030 6 A 2 L 0 SSF | 2706 | 3000 | 2337 | 3490 | 4019 | 2500 | 2200 | ||||
3 x NXC 1180 6 A 2 L 0 SSF* | 2910 | 3210 | 2500 | 3735 | 5002 | 2800 | 2410 |
*Max. ambient temperature of +35°C.
Values are given at switching frequency 2.0 kHz.
VACON® NXP wall-mounted
The VACON® NXP wall-mounted is one of the most compact and comprehensive drive packages on the market, with all the necessary components integrated in a single frame. For the lower power range, VACON® NXP drives are available in a compact IP21 or IP54 frame.
Fully equipped
VACON® NXP wall-mounted units are equipped with internal EMC filtering and the power electronics are integrated into an all-metal frame. The smaller frame sizes (FR4-FR6) have an integrated brake chopper as standard and the 380-500 V units can be equipped with an integrated brake resistor. The larger frames (FR7-FR12) can be equipped with an integrated brake chopper as an option.
Typical applications
- Elevators and escalators
- Cranes and hoists
- Winches and cargo pumps
- Pumps and fans
- Conveyors
- Machine tools
- Yaw and pitch control
- Oil pumps
- Winders and unwinders
- Pulp dryers
- Tissue machinery
- Extruders
Features
- Complete voltage range 230…690 V AC
- Removable panel with parameter back-up function
- Common control board
- Built-in I/0 expandability, 5 slots available and option boards in all frame sizes
- Marine type approvals and functional safety features
- Integrated brake chopper as standard in FR4-6, 380-500 V units.
Benefits
- One type of drive for wide power and voltage range reduces the complexity and the need for additional training
- Easier commissioning – saves time
- Same software tools and applications for the entire range
- Compact and easy to install –saves time and money
- System complexity can be reduced saving engineering time and costs
Ratings and dimensions
Mains voltage |
AC drive typeNXP 0003 2 A 2 H 1 S S S | Loadability | Motor shaft power | Frame sizeFR4 | Dimensions and weightW x H x D (mm)/ kg128 x 292 x 190/ 5 | ||||||
Low (+40°C) | High (+50°C) | Maximum current IS [A]4.8 | 230 V / 400 V/ 690 V | ||||||||
Rated continuous current IL [A]3.7 | 10%overload current [A]4.1 | Rated continuous current IH [A]2.4 | 50%overload current [A]3.6 | 10%overload P [kW]0.55 | 50%overload P [kW]0.37 | ||||||
208-240 V50/60 Hz3˜ | |||||||||||
NXP 0004 2 A 2 H 1 S S S | 4.8 | 5.3 | 3.7 | 5.6 | 7.4 | 0.75 | 0.55 | ||||
NXP 0007 2 A 2 H 1 S S S | 6.6 | 7.3 | 4.8 | 7.2 | 9.6 | 1.1 | 0.75 | ||||
NXP 0008 2 A 2 H 1 S S S | 7.8 | 8.6 | 6.6 | 9.9 | 13.2 | 1.5 | 1.1 | ||||
NXP 0011 2 A 2 H 1 S S S | 11 | 12.1 | 7.8 | 11.7 | 15.6 | 2.2 | 1.5 | ||||
NXP 0012 2 A 2 H 1 S S S | 12.5 | 13.8 | 11 | 16.5 | 22 | 3 | 2.2 | ||||
NXP 0017 2 A 2 H 1 S S S | 17.5 | 19.3 | 12.5 | 18.8 | 25 | 4 | 3 | FR5 | 144 x 391 x 214/ 8.1 | ||
NXP 0025 2 A 2 H 1 S S S | 25 | 27.5 | 17.5 | 26.3 | 35 | 5.5 | 4 | ||||
NXP 0031 2 A 2 H 1 S S S | 31 | 34.1 | 25 | 37.5 | 50 | 7.5 | 5.5 | ||||
NXP 0048 2 A 2 H 1 S S S | 48 | 52.8 | 31 | 46.5 | 62 | 11 | 7.5 | FR6 | 195 x 519 x 237/ 18.5 | ||
NXP 0061 2 A 2 H 1 S S S | 61 | 67.1 | 48 | 72 | 96 | 15 | 11 | ||||
NXP 0075 2 A 2 H 0 S S S | 75 | 83 | 61 | 92 | 122 | 22 | 15 | FR7 | 237 x 591 x 257/ 35 | ||
NXP 0088 2 A 2 H 0 S S S | 88 | 97 | 75 | 113 | 150 | 22 | 22 | ||||
NXP 0114 2 A 2 H 0 S S S | 114 | 125 | 88 | 132 | 176 | 30 | 22 | ||||
NXP 0140 2 A 2 H 0 S S S | 140 | 154 | 105 | 158 | 210 | 37 | 30 | FR8 | 291 x 758 x 344/ 58 | ||
NXP 0170 2 A 2 H 0 S S S | 170 | 187 | 140 | 210 | 280 | 45 | 37 | ||||
NXP 0205 2 A 2 H 0 S S S | 205 | 226 | 170 | 255 | 336 | 55 | 45 | ||||
NXP 0261 2 A 2 H 0 S S F | 261 | 287 | 205 | 308 | 349 | 75 | 55 | FR9 | 480 x 1150 x 362/ 146 | ||
NXP 0300 2 A 2 H 0 S S F | 300 | 330 | 245 | 368 | 444 | 90 | 75 | ||||
380-500 V50/60 Hz 3˜ | NXP 0003 5 A 2 H 1 S S S | 3.3 | 3,6 | 2,2 | 3,3 | 4,4 | 1,1 | 0,75 | FR4 | 128 x 292 x 190/ 5 | |
NXP 0004 5 A 2 H 1 S S S | 4,3 | 4,7 | 3,3 | 5 | 6,2 | 1,5 | 1,1 | ||||
NXP 0005 5 A 2 H 1 S S S | 5,6 | 6,2 | 4,3 | 6,5 | 8,6 | 2,2 | 1,5 | ||||
NXP 0007 5 A 2 H 1 S S S | 7,6 | 8,4 | 5,6 | 8,4 | 10,8 | 3 | 2,2 | ||||
NXP 0009 5 A 2 H 1 S S S | 9 | 9,9 | 7,6 | 11,4 | 14 | 4 | 3 | ||||
NXP 0012 5 A 2 H 1 S S S | 12 | 13,2 | 9 | 13,5 | 18 | 5,5 | 4 | ||||
NXP 0016 5 A 2 H 1 S S S | 16 | 17,6 | 12 | 18 | 24 | 7,5 | 5,5 | FR5 | 144 x 391 x 214/8.1 | ||
NXP 0022 5 A 2 H 1 S S S | 23 | 25,3 | 16 | 24 | 32 | 11 | 7,5 | ||||
NXP 0031 5 A 2 H 1 S S S | 31 | 34 | 23 | 35 | 46 | 15 | 11 | ||||
NXP 0038 5 A 2 H 1 S S S | 38 | 42 | 31 | 47 | 62 | 18,5 | 15 | FR6 | 195 x 519 x 237/18.5 | ||
NXP 0045 5 A 2 H 1 S S S | 46 | 51 | 38 | 57 | 76 | 22 | 18,5 | ||||
NXP 0061 5 A 2 H 1 S S S | 61 | 67 | 46 | 69 | 92 | 30 | 22 | ||||
NXP 0072 5 A 2 H 0 S S S | 72 | 79 | 61 | 92 | 122 | 37 | 30 | FR7 | 237 x 591 x 257/35 | ||
NXP 0087 5 A 2 H 0 S S S | 87 | 96 | 72 | 108 | 144 | 45 | 37 | ||||
NXP 0105 5 A 2 H 0 S S S | 105 | 116 | 87 | 131 | 174 | 55 | 45 | ||||
NXP 0140 5 A 2 H 0 S S S | 140 | 154 | 105 | 158 | 210 | 75 | 55 | FR8 | 291 x 758 x 344/58 | ||
NXP 0168 5 A 2 H 0 S S S | 170 | 187 | 140 | 210 | 280 | 90 | 75 | ||||
NXP 0205 5 A 2 H 0 S S S | 205 | 226 | 170 | 255 | 336 | 110 | 90 | ||||
NXP 0261 5 A 2 H 0 S S F | 261 | 287 | 205 | 308 | 349 | 132 | 110 | FR9 | 480 x 1150 x 362/146 | ||
NXP 0300 5 A 2 H 0 S S F | 300 | 330 | 245 | 368 | 444 | 160 | 132 | ||||
525-690 V50/60 Hz 3˜ | NXP 0004 6 A 2 L 0 S S S | 4,5 | 5 | 3,2 | 4,8 | 6,4 | 3 | 2,2 | FR6 | 195 x 519 x 237/18.5 | |
NXP 0005 6 A 2 L 0 S S S | 5,5 | 6,1 | 4,5 | 6,8 | 9 | 4 | 3 | ||||
NXP 0007 6 A 2 L 0 S S S | 7,5 | 8,3 | 5,5 | 8,3 | 11 | 5,5 | 4 | ||||
NXP 0010 6 A 2 L 0 S S S | 10 | 11 | 7,5 | 11,3 | 15 | 7,5 | 5,5 | ||||
NXP 0013 6 A 2 L 0 S S S | 13,5 | 14,9 | 10 | 15 | 20 | 11 | 7,5 | ||||
NXP 0018 6 A 2 L 0 S S S | 18 | 19,8 | 13,5 | 20,3 | 27 | 15 | 11 | ||||
NXP 0022 6 A 2 L 0 S S S | 22 | 24,2 | 18 | 27 | 36 | 18,5 | 15 | ||||
NXP 0027 6 A 2 L 0 S S S | 27 | 29,7 | 22 | 33 | 44 | 22 | 18,5 | ||||
NXP 0034 6 A 2 L 0 S S S | 34 | 37 | 27 | 41 | 54 | 30 | 22 | ||||
NXP 0041 6 A 2 L 0 S S S | 41 | 45 | 34 | 51 | 68 | 37,5 | 30 | FR7 | 237 x 591 x 257/35 | ||
NXP 0052 6 A 2 L 0 S S S | 52 | 57 | 41 | 62 | 82 | 45 | 37,5 | ||||
NXP 0062 6 A 2 L 0 S S S | 62 | 68 | 52 | 78 | 104 | 55 | 45 | FR8 | 291 x 758 x 344/58 | ||
NXP 0080 6 A 2 L 0 S S S | 80 | 88 | 62 | 93 | 124 | 75 | 55 | ||||
NXP 0100 6 A 2 L 0 S S S | 100 | 110 | 80 | 120 | 160 | 90 | 75 | ||||
NXP 0125 6 A 2 L 0 S S F | 125 | 138 | 100 | 150 | 200 | 110 | 90 | FR9 | 480 x 1150 x 362/146 | ||
NXP 0144 6 A 2 L 0 S S F | 144 | 158 | 125 | 188 | 213 | 132 | 110 | ||||
NXP 0170 6 A 2 L 0 S S F | 170 | 187 | 144 | 216 | 245 | 160 | 132 | ||||
NXP 0208 6 A 2 L 0 S S F | 208 | 229 | 170 | 255 | 289 | 200 | 160 |
VACON® NXP drive module
VACON® NXP high-power IP00 drive modules are intended for installation into a cabinet, switchgear or any separate enclosure. Module installation in standard enclosures is easy given the compact design.
Designed to fit
VACON® NXP drive modules of frame size FR10 – FR12 embody one (FR10 and FR11) or two (FR12) power modules. VACON® NXP frame sizes FR13 – FR14 comprise two to four non-regenerative front-end (NFE) units and one (FR13) or two (FR14) inverter units. External AC chokes are also included in the delivery. The VACON® NXP modules are available as both 6-pulse and
12-pulse supply versions.
Typical applications
- Conveyors
- Cranes and lifts
- High-speed compressors
- Ski lifts
- Main propulsion and bow thrusters
- Extruders
- Winches & cargo pumps
- Oil pumps
- Test benches
- Static power supply
- Grinders and mixers
- Winders and unwinders
- Chippers
- Tunneling Machines
Features
- Easy cabinet integration with additional assembly kits
- One of the smallest on the market
- Extensive marine type approvals
- VACON® DriveSynch features
Benefits
- With optimized module design, less engineering is needed saving time and money
- Compact module size require less cabinet space, while reducing the overall costs
- Improved redundancy and higher powers up to 5 MW
Hardware configurations
Function | Availability |
Integrated control | Standard |
External control | Optional |
Integrated brake chopper | Optional (FR 10-12) |
6-Pulse Supply | Standard |
12-Pulse Supply | Optional |
EMC filtering N | Standard |
EMC filtering T (for IT -networks) AC choke Output filters dU/dt, Sine and common mode | Optional Standard Optional |
Ratings and dimensions
Loadability | Motor shaft power | ||||||||||
Low (+40°C) | High (+40°C) | Maxi- mum current IS[A]540 | 400 V / 690 V | ||||||||
Mains voltage | AC drive type | Rated conti- nuous current IL [A] | 10%over- load current [A] | Rated conti- nuous current IH [A] | 50%over- load current [A] | 10%over- loadP [kW] | 50%over- loadP [kW] | Frame size | Module W x H x D (mm)/ kg | Chokes W x H x D (mm)/ kg | |
NXP 0385 5 A 0 N 0 SSA | 385 | 424 | 300 | 450 | 200 | 160 | 350 x 383 x 262/84 1) | ||||
NXP 0460 5 A 0 N 0 SSA | 460 | 506 | 385 | 578 | 693 | 250 | 200 | FR10 | 500 x 1165 x 506/120 | 497 x 399 x 244/115 1) | |
NXP 0520 5 A 0 N 0 SSA* | 520 | 572 | 460 | 690 | 828 | 250 | 250 | 497 x 399 x 244/115 1) | |||
NXP 0590 5 A 0 N 0 SSA | 590 | 649 | 520 | 780 | 936 | 315 | 250 | FR11 | 709 x 1206 x 506/210 | 2 x (350 x 383 x 262/84) | |
NXP 0650 5 A 0 N 0 SSA | 650 | 715 | 590 | 885 | 1062 | 355 | 315 | ||||
NXP 0730 5 A 0 N 0 SSA | 730 | 803 | 650 | 975 | 1170 | 400 | 355 | ||||
NXP 0820 5 A 0 N 0 SSA | 820 | 902 | 730 | 1095 | 1314 | 450 | 400 | ||||
NXP 0920 5 A 0 N 0 SSA | 920 | 1012 | 820 | 1230 | 1476 | 500 | 450 | FR12 | 2 x (500 x 1165 x 506/120) | 2 x (497 x 399 x 244/115) | |
380-500 V | NXP 1030 5 A 0 N 0 SSA | 1030 | 1133 | 920 | 1380 | 1656 | 560 | 500 | |||
NXP 1150 5 A 0 N 0 SSF | 1150 | 1265 | 1030 | 1545 | 1854 | 630 | 560 | 2 x (497 x 449 x 249/130) | |||
50/60 Hz | 2 x (239 x 1030 x 372/67) + | ||||||||||
3˜ | 1 x (708 x 1030 x 553/302) | ||||||||||
NXP 1300 5 A 0 N 0 SSF | 1300 | 1430 | 1150 | 1725 | 2070 | 710 | 630 | FR13 | 3 x (239 x 1030 x 372/67) +1 x (708 x 1030 x 553/302) 2) | 3 x (497 x 449 x 249/130) 2) | |
NXP 1450 5 A 0 N 0 SSF | 1450 | 1595 | 1300 | 1950 | 2340 | 800 | 710 | 3 x (239 x 1030 x 372/67) + | 3 x (497 x 449 x 249/130) 2) | ||
1 x (708 x 1030 x 553/302) 2) | |||||||||||
NXP 1770 5 A 0 N 0 SSF | 1770 | 1947 | 1600 | 2400 | 2880 | 1000 | 900 | 4 x (239 x 1030 x 372/67) + | 4 x (497 x 449 x 249/130) | ||
FR14 | 2 x (708 x 1032 x 553/302) | ||||||||||
NXP 2150 5 A 0 N 0 SSF | 2150 | 2365 | 1940 | 2910 | 3492 | 1200 | 1100 | 4 x (239 x 1030 x 372/67) + | 4 x (497 x 449 x 249/130) | ||
2 x (708 x 1032 x 553/302) | |||||||||||
NXP 0261 6 A 0 N 0 SSA | 261 | 287 | 208 | 312 | 375 | 250 | 200 | FR10 | 500 x 1165 x 506/120 | 354 x 319 x 230/53 3) | |
NXP 0325 6 A 0 N 0 SSA | 325 | 358 | 261 | 392 | 470 | 315 | 250 | 500 x 1165 x 506/120 | 350 x 383 x 262/84 3) | ||
NXP 0385 6 A 0 N 0 SSA | 385 | 424 | 325 | 488 | 585 | 355 | 315 | 500 x 1165 x 506/120 | 350 x 383 x 262/84 3) | ||
NXP 0416 6 A 0 N 0 SSA* | 416 | 458 | 325 | 488 | 585 | 400 | 315 | 500 x 1165 x 506/120 | 350 x 383 x 262/84 3) | ||
NXP 0460 6 A 0 N 0 SSA | 460 | 506 | 385 | 578 | 693 | 450 | 355 | FR11 | 709 x 1206 x 506/210 | 497 x 399 x 244/115 4) | |
NXP 0502 6 A 0 N 0 SSA | 502 | 552 | 460 | 690 | 828 | 500 | 450 | 709 x 1206 x 506/210 | 497 x 399 x 244/115 4) | ||
NXP 0590 6 A 0 N 0 SSA* | 590 | 649 | 502 | 753 | 904 | 560 | 500 | 709 x 1206 x 506/210 | 2 x (350 x 383 x 262/84) | ||
NXP 0650 6 A 0 N 0 SSA | 650 | 715 | 590 | 885 | 1062 | 630 | 560 | 2 x (500 x 1165 x 506/120) | 2 x (350 x 383 x 262/84) | ||
NXP 0750 6 A 0 N 0 SSA | 750 | 825 | 650 | 975 | 1170 | 710 | 630 | FR12 | 2 x (500 x 1165 x 506/120) | 2 x (350 x 383 x 262/84) | |
525-690 V50/60 Hz3˜ | NXP 0820 6 A 0 N 0 SSA* | 820 | 902 | 650 | 975 | 1170 | 800 | 630 | 2 x (500 x 1165 x 506/120) | 2 x (350 x 383 x 262/84) | |
NXP 0920 6 A 0 N 0 SSF | 920 | 1012 | 820 | 1230 | 1410 | 900 | 800 | FR13 | 2 x (239 x 1030 x 372/67) +1 x (708 x 1030 x 553/302) | 2 x (497 x 449 x 249/130) | |
NXP 1030 6 A 0 N 0 SSF | 1030 | 1133 | 920 | 1380 | 1755 | 1000 | 900 | 2 x (239 x 1030 x 372/67) +1 x (708 x 1030 x 553/302) | 2 x (497 x 449 x 249/130) | ||
NXP 1180 6 A 0 N 0 SSF* | 1180 | 1298 | 1030 | 1463 | 1755 | 1150 | 1000 | 2 x (239 x 1030 x 372/67) + | 2 x (497 x 449 x 249/130) | ||
1 x (708 x 1030 x 553/302) | |||||||||||
NXP 1500 6 A 0 N 0 SSF | 1500 | 1650 | 1300 | 1950 | 2340 | 1500 | 1300 | 3 x (239 x 1030 x 372/67) + | 3 x (497 x 449 x 249/130) 5) | ||
2 x (708 x 103 x 553/302) 3) | |||||||||||
NXP 1900 6 A 0 N 0 SSF | 1900 | 2090 | 1500 | 2250 | 2700 | 1800 | 1500 | FR14 | 4 x(239 x 1030 x 372/67) +2 x (708 x 1030 x 553/302) | 4 x (497 x 449 x 249/130) | |
NXP 2250 6 A 0 N 0 SSF* | 2250 | 2475 | 1900 | 2782 | 3335 | 2000 | 1800 | 4 x (239 x 1030 x 372/67) + | 4 x (497 x 449 x 249/130) | ||
2 x (708 x 1030 x 553/302) |
*Max. ambient temperature of +35°C.
- 12-pulse units, 2 x (354 x 319 x 230/53 kg)
- 12-pulse units, 4 x (497 x 449 x 249/130 kg)
- 12-pulse units, 2 x (354 x 319 x 230/53 kg)
- 12-pulse units, 4 x (239 x 1030 x 372/67) + 2 x (708 x 1030 x 372/302 kg)
- 12-pulse units, 4 x (497 x 449 x 249/130 kg)
VACON® NXP standalone
Premium VACON® NXP drives are also available in standalone IP21 or IP54 enclosures. These units are delivered in a compact enclosure, making them perfect for areas with limited space, while still providing full VACON® NXP control flexibility.
Robust and reliable
VACON® NXP standalone drives are fully enclosed at the factory and ready for immediate installation. The drive is ideal for pumps, fans and other single drive applications. The drive has integrated fuses as standard and no extra protection components are required. It is also possible to equip the drive with an optional integrated load switch, which further simplifies handling in the field.
Typical applications
- Auxiliary equipment
- Pump and fans
- Main propulsion and bow thrusters
- Compressors
- Cranes and lifts
Features
- Extremely compact cabinet enclosure
- Delivered with ultra rapid AC fuses
- Optional built-in brake chopper and
- DC-link connectors
Benefits
- Maximize the utilization of available space while reducing the overall costs
- No need to consider any additional protection components
Hardware configurations
Function | Availability |
IP21 | Standard |
IP54 (FR10 only) | Optional (H: +20mm) |
Integrated ultra rapid fuses | Standard |
Load switch (IEC or UL version) | Optional |
EMC filtering L (EN 61800-3, category C3) | Standard |
EMC filtering T (for IT -networks) | Optional |
Brake chopper (cabling top entry) | Optional(H: +122 mm) |
Ratings and dimensions
Mains voltage |
AC drive type
NXP 0385 5 A 2 L 0 SSA |
Loadability | Motor shaft power |
Frame size
FR10 |
Dimensions and weight W x H x D (mm)/ kg
595 x 2020 x 602/340 |
||||||
Low (+40°C) | High (+40°C) |
Maximum current IS [A]
540 |
400 V / 690 V | ||||||||
Rated conti- nuous current IL [A]
385 |
10%
overload current [A] 424 |
Rated conti- nuous current IH [A]
300 |
50%
overload current [A] 450 |
10% overload P [kW]
200 |
50% overload P [kW]
160 |
||||||
380-500 V 50/60 Hz 3˜ |
|||||||||||
NXP 0460 5 A 2 L 0 SSA | 460 | 506 | 385 | 578 | 693 | 250 | 200 | ||||
NXP 0520 5 A 2 L 0 SSA* | 520 | 572 | 460 | 690 | 828 | 250 | 250 | ||||
NXP 0590 5 A 2 L 0 SSA | 590 | 649 | 520 | 780 | 936 | 315 | 250 |
FR11 |
794 x 2020 x 602/470 |
||
NXP 0650 5 A 2 L 0 SSA | 650 | 715 | 590 | 885 | 1062 | 355 | 315 | ||||
NXP 0730 5 A 2 L 0 SSA | 730 | 803 | 650 | 975 | 1170 | 400 | 355 | ||||
525-690 V 50/60 Hz 3˜ |
NXP 0261 6 A 2 L 0 SSA
NXP 0325 6 A 2 L 0 SSA NXP 0385 6 A 2 L 0 SSA NXP 0416 6 A 2 L 0 SSA* |
261 | 287 | 208 | 312 | 375 | 250 | 200 |
FR10 |
595 x 2020 x 602/340 |
|
325 | 358 | 261 | 392 | 470 | 315 | 250 | |||||
385 | 424 | 325 | 488 | 585 | 355 | 315 | |||||
416 | 458 | 325 | 488 | 585 | 400 | 315 | |||||
NXP 0460 6 A 2 L 0 SSA
NXP 0502 6 A 2 L 0 SSA NXP 0590 6 A 2 L 0 SSA* |
460 | 506 | 385 | 578 | 693 | 450 | 355 |
FR11 |
794 x 2020 x 602/400
794 x 2020 x 602/400 794 x 2020 x 602/470 |
||
502 | 552 | 460 | 690 | 828 | 500 | 450 | |||||
590 | 649 | 502 | 753 | 904 | 560 | 500 |
*Max. ambient temperature of +35°C.
VACON® NXC
Our VACON® NXC is designed to meet the most demanding requirements for flexibility, robustness, compactness and service-friendliness. It is a safe choice for any application and available in the 160 to 2000 kW power range and 380-500 V, 525-690 V voltage range.
- Exceptional performance
Our enclosed VACON® NXC variable speed AC drives are compact and well tested to meet harsh operating conditions. They are typically put to work in segments, such as mining, oil and gas, water and wastewater. The reliable thermal handling of the enclosure guarantees extended lifetime of the frequency converter and trouble-free operation in tough environments. Approved EMC solutions ensure reliable operation of the converter without disturbing other electrical equipment. - User-friendly
VACON® NXC features an easily accessible control compartment for relays, auxiliary terminals and other equipment and ample space around the power terminals allows for easy installation and connection of power cables. Our handy keypad is located on the door with additional door options including indicators, meters and switches. Bottom plates and earthing claps for 360 degree earthing of motor cables are provided as standard. - Service-friendly
VACON® NXC enclosures are easy to install with lifting lugs for easy handling and can be wall-mounted or free-standing. VACON® NXP power units are rail-mounted for easy pull-out, and the optional pull-out jig enables hassle-free servicing of the power unit. No additional cooling fans are required in the enclosure IP21/IP54 and the fans can be easily replaced without having to remove the power unit.
Typical applications
- Pumps and fans
- Extruders
- Main propulsion and bow thrusters
- Wood handling machines
- Conveyors and crushers
- Feeders and mixers
- Test benches
- Water treatment
- Winches
- Compressors
- Static power supply
- Industrial elevators
Features
- Robust and type-tested design
- Wide range of standard options
- One of the most compact on the market
- Welded Rittal TS8 frame
- EMC approved (EN61800-3, 2nd env.)
- Service concept with pullout jig
- No additional fans in IP54 enclosure
Benefits
- Trouble free installation and operation
- Adapts to your needs w/o engineering
- Easy to fit into small spaces
- Global enclosure availability
- Easy to extend
- Fast service and easy maintenance
Ratings and dimensions
VACON® NXC, 6-pulse supply
Loadability | Motor shaft power |
Frame size
FR9 |
Dimensions and weight W x H x D (mm)/ kg
606 x 2275 x 605/371 |
||||||||
Low (+40°C) | High (+40°C) | 400 V / 690 V | |||||||||
Mains voltage |
AC drive type |
Rated conti- nuous current IL [A] | 10%
overload current [A] |
Rated conti- nuous current IH [A] | 50%
overload current [A] |
Maximum current IS [A] |
10% overload P [kW] |
50% overload P [kW] |
|||
NXC 0261 5 A 2 H 0 SSF | 261 | 287 | 205 | 308 | 349 | 132 | 110 | ||||
NXC 0300 5 A 2 H 0 SSF | 300 | 330 | 245 | 368 | 444 | 160 | 132 | ||||
NXC 0385 5 A 2 L 0 SSF | 385 | 424 | 300 | 450 | 540 | 200 | 160 |
FR10 |
606 x 2275 x 605/403 |
||
NXC 0460 5 A 2 L 0 SSF | 460 | 506 | 385 | 578 | 693 | 250 | 200 | ||||
NXC 0520 5 A 2 L 0 SSF* | 520 | 572 | 460 | 690 | 828 | 250 | 250 | ||||
NXC 0590 5 A 2 L 0 SSF | 590 | 649 | 520 | 780 | 936 | 315 | 250 | ||||
380-500 V | NXC 0650 5 A 2 L 0 SSF | 650 | 715 | 590 | 885 | 1062 | 355 | 315 | FR11 | 806 x 2275 x 605/577 | |
NXC 0730 5 A 2 L 0 SSF | 730 | 803 | 650 | 975 | 1170 | 400 | 355 | ||||
50/60 Hz
3˜ |
|||||||||||
NXC 0820 5 A 2 L 0 SSF
NXC 0920 5 A 2 L 0 SSF |
820
920 |
902
1012 |
730
820 |
1095
1230 |
1314
1476 |
450
500 |
400
450 |
FR12 |
1206 x 2275 x 605/810 |
||
NXC 1030 5 A 2 L 0 SSF | 1030 | 1133 | 920 | 1380 | 1656 | 560 | 500 | ||||
NXC 1150 5 A 2 L 0 SSF | 1150 | 1265 | 1030 | 1545 | 1854 | 630 | 560 | 1406 x 2275 x 605/1000 | |||
NXC 1300 5 A 2 L 0 SSF | 1300 | 1430 | 1150 | 1725 | 2070 | 710 | 630 | FR13 | 1606 x 2275 x 605/1150 | ||
NXC 1450 5 A 2 L 0 SSF | 1450 | 1595 | 1300 | 1950 | 2340 | 800 | 710 | 1606 x 2275 x 605/1150 | |||
NXC 1770 5 A 2 L 0 SSF | 1770 | 1947 | 1600 | 2400 | 2880 | 1000 | 900 | FR14 | 2806 x 2275 x 605/2440 | ||
NXC 2150 5 A 2 L 0 SSF | 2150 | 2365 | 1940 | 2910 | 3492 | 1200 | 1100 | ||||
NXC 0125 6 A 2 L 0 SSF | 125 | 138 | 100 | 150 | 200 | 110 | 90 |
FR9 |
606 x 2275 x 605/371 |
||
NXC 0144 6 A 2 L 0 SSF | 144 | 158 | 125 | 188 | 213 | 132 | 110 | ||||
NXC 0170 6 A 2 L 0 SSF | 170 | 187 | 144 | 216 | 245 | 160 | 132 | ||||
NXC 0208 6 A 2 L 0 SSF | 208 | 229 | 170 | 255 | 289 | 200 | 160 | ||||
NXC 0261 6 A 2 L 0 SSF | 261 | 287 | 208 | 312 | 375 | 250 | 200 | ||||
NXC 0325 6 A 2 L 0 SSF
NXC 0385 6 A 2 L 0 SSF |
325
385 |
358
424 |
261
325 |
392
488 |
470
585 |
315
355 |
250
315 |
FR10 | 606 x 2275 x 605/371 | ||
NXC 0416 6 A 2 L 0 SSF* | 416 | 458 | 325 | 488 | 585 | 400 | 315 | ||||
525-690 V
50/60 Hz |
NXC 0460 6 A 2 L 0 SSF | 460 | 506 | 385 | 578 | 693 | 450 | 355 |
FR11 |
806 x 2275 x 605/524 | |
NXC 0502 6 A 2 L 0 SSF | 502 | 552 | 460 | 690 | 828 | 500 | 450 | ||||
NXC 0590 6 A 2 L 0 SSF* | 590 | 649 | 502 | 753 | 904 | 560 | 500 | 806 x 2275 x 605/577 | |||
3˜ | |||||||||||
NXC 0650 6 A 2 L 0 SSF | 650 | 715 | 590 | 885 | 1062 | 630 | 560 |
FR12 |
1206 x 2275 x 605/745 |
||
NXC 0750 6 A 2 L 0 SSF | 750 | 825 | 650 | 975 | 1170 | 710 | 630 | ||||
NXC 0820 6 A 2 L 0 SSF* | 820 | 902 | 650 | 975 | 1170 | 800 | 630 | ||||
NXC 0920 6 A 2 L 0 SSF | 920 | 1012 | 820 | 1230 | 1410 | 900 | 800 |
FR13 |
1406 x 2275 x 605/1000 |
||
NXC 1030 6 A 2 L 0 SSF | 1030 | 1133 | 920 | 1380 | 1755 | 1000 | 900 | ||||
NXC 1180 6 A 2 L 0 SSF* | 1180 | 1298 | 1030 | 1463 | 1755 | 1150 | 1000 | ||||
NXC 1500 6 A 2 L 0 SSF | 1500 | 1650 | 1300 | 1950 | 2340 | 1500 | 1300 |
FR14 |
2406 x 2275 x 605/2350 | ||
NXC 1900 6 A 2 L 0 SSF | 1900 | 2090 | 1500 | 2250 | 2700 | 1800 | 1500 | 2806 x 2275 x 605/2440 | |||
NXC 2250 6 A 2 L 0 SSF* | 2250 | 2475 | 1900 | 2782 | 3335 | 2000 | 1800 | 2806 x 2275 x 605/2500 |
*Max. ambient temperature of +35°C.
Ratings and dimensions
VACON® NXC, 12 -pulse supply
Loadability | Motor shaft power | ||||||||||
Low (+40°C) | High (+40°C) | 400 V / 690 V | |||||||||
Mains voltage | AC drive type | Rated conti- nuous current IL [A] | 10%overload current [A] | Rated conti- nuous current IH [A] | 50%overload current [A] | Maximum current IS [A] | 10%overload P [kW] | 50%overload P [kW] | Frame size | Dimensions and weightW x H x D (mm)/ kg | |
NXC 0385 5 A 2 L 0 TSF | 385 | 424 | 300 | 450 | 540 | 200 | 160 | 606 x 2275 x 605/371 | |||
NXC 0460 5 A 2 L 0 TSF | 460 | 506 | 385 | 578 | 693 | 250 | 200 | FR10 | 606 x 2275 x 605/403 | ||
NXC 0520 5 A 2 L 0 TSF* | 520 | 572 | 460 | 690 | 828 | 250 | 250 | 606 x 2275 x 605/403 | |||
NXC 0590 5 A 2 L 0 TSF | 590 | 649 | 520 | 780 | 936 | 315 | 250 | 806 x 2275 x 605/ 577 | |||
NXC 0650 5 A 2 L 0 TSF | 650 | 715 | 590 | 885 | 1062 | 355 | 315 | FR11 | 806 x 2275 x 605/577 | ||
380-500 V | NXC 0730 5 A 2 L 0 TSF | 730 | 803 | 650 | 975 | 1170 | 400 | 355 | 806 x 2275 x 605/577 | ||
NXC 0820 5 A 2 L 0 TSF | 820 | 902 | 730 | 1095 | 1314 | 450 | 400 | 1206 x 2275 x 605/810 | |||
50/60 Hz3˜ | FR12 | ||||||||||
NXC 0920 5 A 2 L 0 TSF | 920 | 1012 | 820 | 1230 | 1476 | 500 | 450 | 1206 x 2275 x 605/810 | |||
NXC 1030 5 A 2 L 0 TSF | 1030 | 1133 | 920 | 1380 | 1656 | 560 | 500 | 1206 x 2275 x 605/810 | |||
NXC 1150 5 A 2 L 0 TSF | 1150 | 1265 | 1030 | 1545 | 1854 | 630 | 560 | 1406 x 2275 x 605/1000 | |||
NXC 1300 5 A 2 L 0 TSF | 1300 | 1430 | 1150 | 1725 | 2070 | 710 | 630 | FR13 | 2006 x 2275 x 605/1150 | ||
NXC 1450 5 A 2 L 0 TSF | 1450 | 1595 | 1300 | 1950 | 2340 | 800 | 710 | 2006 x 2275 x 605/1150 | |||
NXC 1770 5 A 2 L 0 TSF | 1770 | 1947 | 1600 | 2400 | 2880 | 1000 | 900 | FR14 | 2806 x 2275 x 605/2440 | ||
NXC 2150 5 A 2 L 0 TSF | 2150 | 2365 | 1940 | 2910 | 3492 | 1200 | 1100 | 2806 x 2275 x 605/2500 | |||
525-690 V50/60 Hz3˜ | NXC 0261 6 A 2 L 0 TSF | 261 | 287 | 208 | 312 | 375 | 250 | 200 | FR10 | 606 x 2275 x 605/341 | |
NXC 0325 6 A 2 L 0 TSF | 325 | 358 | 261 | 392 | 470 | 315 | 250 | 606 x 2275 x 605/371 | |||
NXC 0385 6 A 2 L 0 TSF | 385 | 424 | 325 | 488 | 585 | 355 | 315 | 606 x 2275 x 605/371 | |||
NXC 0416 6 A 2 L 0 TSF* | 416 | 458 | 325 | 488 | 585 | 400 | 315 | 606 x 2275 x 605/403 | |||
NXC 0460 6 A 2 L 0 TSF | 460 | 506 | 385 | 578 | 693 | 450 | 355 | FR11 | 806 x 2275 x 605/524 | ||
NXC 0502 6 A 2 L 0 TSF | 502 | 552 | 460 | 690 | 828 | 500 | 450 | 806 x 2275 x 605/524 | |||
NXC 0590 6 A 2 L 0 TSF* | 590 | 649 | 502 | 753 | 904 | 560 | 500 | 806 x 2275 x 605/577 | |||
NXC 0650 6 A 2 L 0 TSF | 650 | 715 | 590 | 885 | 1062 | 630 | 560 | FR12 | 1206 x 2275 x 605/745 | ||
NXC 0750 6 A 2 L 0 TSF | 750 | 825 | 650 | 975 | 1170 | 710 | 630 | 1206 x 2275 x 605/745 | |||
NXC 0820 6 A 2 L 0 TSF* | 820 | 902 | 650 | 975 | 1170 | 800 | 630 | 1206 x 2275 x 605/745 | |||
NXC 0920 6 A 2 L 0 TSF | 920 | 1012 | 820 | 1230 | 1410 | 900 | 800 | FR13 | 1406 x 2275 x 605/1000 | ||
NXC 1030 6 A 2 L 0 TSF | 1030 | 1133 | 920 | 1380 | 1755 | 1000 | 900 | 1406 x 2275 x 605/1000 | |||
NXC 1180 6 A 2 L 0 TSF* | 1180 | 1298 | 1030 | 1463 | 1755 | 1150 | 1000 | 1406 x 2275 x 605/1000 | |||
NXC 1500 6 A 2 L 0 TSF | 1500 | 1650 | 1300 | 1950 | 2340 | 1500 | 1300 | FR14 | 2806 x 2275 x 605/2440 | ||
NXC 1900 6 A 2 L 0 TSF | 1900 | 2090 | 1500 | 2250 | 2700 | 1800 | 1500 | 2806 x 2275 x 605/2440 | |||
NXC 2250 6 A 2 L 0 TSF* | 2250 | 2475 | 1900 | 2782 | 3335 | 2000 | 1800 | 2806 x 2275 x 605/2500 |
*Max. ambient temperature of +35°C.
Hardware configurations, 6-pulse supply
6-pulse | Enclosure | EMC | Brake chopper | Cabling | Input device | Output filters | ||||||||||
380-500 V | IP21 | IP54 | L | T | H | Bottom | Top
+CIT/+COT |
+IFU | +ILS | +IFD | +ICO | +ICB | +OCM/
+OCH |
+ODU | +OSI | |
FR9 | S | O (H: +130) | S | O | – | O | S | O (W: +400) | O | O | O | O | O | O | O | O (W: +600) |
FR10 | S | O (H: +130) | S | O | – | O | S | O (W: +400) | O | O | O | O | O | O | O (W: +400) | O (W: +600) |
FR11 | S | O (H: +130)* | S | O | – | O | S | O (W: +400) | O | O | O | O | O | O | O (W: +400) | O (W: +600-800) |
FR12 | S | O (H: +130) | S | O | – | O | S | O (W: +400) | O | O | O | O | O | O | O (W: +400) | O (W: +1200) |
FR13 | S | O (H: +170) | S | O | – | 1 | S | O (W: +400) | – | – | S | – | O | O | O | O (W: +800) |
FR14 | S | O (H: +170) | S | O | – | 1 | S | O (W: +600) | – | – | – | – | S | O | S | O (W: +1600) |
500-690 V | ||||||||||||||||
FR9 | S | O (H: +130) | S | O | – | O | S | O (W: +400) | O | O | O | O | O | O | O | O (W: +600) |
FR10 | S | O (H: +130) | S | O | – | O | S | O (W: +400) | O | O | O | O | O | O | O (W: +400) | O (W: +600) |
FR11 | S | O (H: +130)* | S | O | – | O | S | O (W: +400) | O | O | O | O | O | O | O (W: +400) | O (W: +600-800) |
FR12 | S | O (H: +130) | S | O | – | O | S | O (W: +400) | O | O | O | O | O | O | O (W: +400) | O (W: +1200) |
FR13 | S | O (H: +170) | S | O | – | 1 | S | O (W: +400) | – | – | S | – | O | O | O | O (W: +800) |
FR14 | S | O (H: +170) | S | O | – | 1 | S | O (W: +600) | – | – | – | – | S | O | S | O (W: +1600) |
S = Standard O = Optional
1)(W: +400) = Contact factory*NXC07305 and NXC05906, H: +170 mm
Hardware configurations, 12-pulse supply
12-pulse | Enclosure | EMC | Brake chopper | Cabling | Input device | Output filters | ||||||||||
380-500 V | IP21 | IP54 | L | T | H | Bottom | Top
+CIT/+COT |
+IFU | +ILS | +IFD | +ICO | +ICB | +OCM/
+OCH |
+ODU | +OSI | |
FR10 | S | O (H: +130) | S | O | – | – | S | O (W: +400) | O | – | – | – | O | O | O (W: +400) | O (W: +600) |
FR11 | S | O (H: +130)* | S | O | – | O | S | O (W: +400) | O | O | O | O | O | O | O (W: +400) | O (W: +600) |
FR12 | S | O (H: +130) | S | O | – | O | S | O (W: +400) | O | O | O | O | O | O | O (W: +400) | O (W: +1200) |
FR13 | S | O (H: +170) | S | O | – | 1 | S | O (W: +400) | – | – | – | – | S | O | O | O (W: +800) |
FR14 | S | O (H: +170) | S | O | – | 1 | S | O (W: +800) | – | – | – | – | S | O | S | O (W: +1600) |
500-690 V | ||||||||||||||||
FR10 | S | O (H: +130) | S | O | – | – | S | O (W: +400) | O | – | – | – | O | O | O (W: +400) | O (W: +600) |
FR11 | S | O (H: +130)* | S | O | – | O | S | O (W: +400) | O | O | O | O | O | O | O (W: +400) | O (W: +600-800) |
FR12 | S | O (H: +130) | S | O | – | O | S | O (W: +400) | O | O | O | O | O | O | O (W: +400) | O (W: +1200) |
FR13 | S | O (H: +170) | S | O | – | 1 | S | O (W: +400) | – | – | – | – | S | O | O | O (W: +800) |
S = Standard O = Optional
1)(W: +400) = Contact factory
*NXC07305 and NXC05906, H: +170 mm
Pure performance
Rising energy prices, environmental legislation and process improvement are key issues when designing water handling systems. Use of VACON® AC drives for flow and pressure control instead of dampers or valves gives substantial energy savings resulting in quick ROI.
VACON® NXC Low Harmonic
The VACON® NXC Low Harmonic drive is the perfect choice for applications where low harmonics are required. This drive not only meets the most demanding requirements for clean power but also provides other important benefits such as regenerative braking and voltage boost for maximum output power.
Clean power saves money
The low harmonic cabinet drive offers an excellent total solution to meet even the most demanding power quality requirements. The drive also complies with the IEEE-519, G5/4 harmonic standards. The low THDi reduces supply currents and allows supply transformers, protection devices and power cables to be dimensioned according to the actual active power. It creates savings for both new and retrofit projects as there’s no need to invest in expensive 12- or 18-pulse transformers.
Typical applications
- Pumps and fans
- Water treatment
- Thrusters and main propulsion
- Crushers and conveyors and mills
- Industrial elevators
- Test benches
- Sugar refineries
Features
- Clean power with total current harmonics THDi < 5 %
- Over-dimensioning of power transformer or input cables is not required
- Regenerative function available
- Reducing system complexity
- No need for special 12-pulse transformers
- Well-suited for retrofit projects
- Increased flexibility with a wide range of standard options
Benefits
- Over-dimensioning of input components is not needed, reducing the total costs
- Voltage boost function for maximum output power
- Braking energy can be fed back to network saving energy costs
- Reduces overall investment costs and optimizes the use of available space
Ratings and dimensions
Mains voltage |
Low harmonic drive type
NXC 0261 5 A 2 L 0 RSF |
Loadability | Motor shaft power | Frame size
AF9 |
Dimensions and weightW x H x D (mm)/ kg
1006 x 2275 x 605/680 |
||||||
Low (+40°C) | High (+40°C) | Maximum current IS [A] 349 |
400 V / 690 V | ||||||||
Rated conti- nuous current IL [A]261 | 10%overload current [A]287 | Rated conti- nuous current IH [A]205 | 50%overload current [A]308 | 10%overload P [kW] 132 |
50%overload P [kW] 110 |
||||||
380-500 V50/60 Hz | |||||||||||
NXC 0300 5 A 2 L 0 RSF | 300 | 330 | 245 | 368 | 444 | 160 | 132 | ||||
NXC 0385 5 A 2 L 0 RSF | 385 | 424 | 300 | 450 | 540 | 200 | 160 | AF10 | 1006 x 2275 x 605/700 | ||
NXC 0460 5 A 2 L 0 RSF | 460 | 506 | 385 | 578 | 693 | 250 | 200 | ||||
NXC 0520 5 A 2 L 0 RSF* | 520 | 572 | 460 | 690 | 828 | 250 | 250 | ||||
NXC 0650 5 A 2 L 0 RSF | 650 | 715 | 590 | 885 | 1062 | 355 | 315 | AF12 | 2006 x 2275 x 605/1400 | ||
NXC 0730 5 A 2 L 0 RSF | 730 | 803 | 650 | 975 | 1170 | 400 | 355 | ||||
NXC 0820 5 A 2 L 0 RSF | 820 | 902 | 730 | 1095 | 1314 | 450 | 400 | ||||
NXC 0920 5 A 2 L 0 RSF | 920 | 1012 | 820 | 1230 | 1476 | 500 | 450 | ||||
NXC 1030 5 A 2 L 0 RSFNXC 1150 5 A 2 L 0 RSFNXC 1300 5 A 2 L 0 RSFNXC 1450 5 A 2 L 0 RSFNXC 1770 5 A 2 L 0 RSF | 10301150130014501770 | 11331265143015951947 | 9201030115013001600 | 13801545172519502400 | 16561854207023402880 | 5606307108001000 | 500560630710900 | AF13 | 2206 x 2275 x 605/1950 | ||
NXC 2150 5 A 2 L 0 RSF | 2150 | 2365 | 1940 | 2910 | 3492 | 1200 | 1100 | AF14 | 4406 x 2275 x 605/3900 | ||
NXC 2700 5 A 2 L 0 RSFNXC 0125 6 A 2 L 0 RSFNXC 0144 6 A 2 L 0 RSFNXC 0170 6 A 2 L 0 RSFNXC 0208 6 A 2 L 0 RSF* | 2700125144170208 | 2970138158187229 | 2300100125144170 | 3278150188216255 | 3933200213245289 | 1500110132160200 | 120090110132160 | AF9 | 1006 x 2275 x 605/680 | ||
525-690 V50/60 Hz | |||||||||||
NXC 0261 6 A 2 L 0 RSF | 261 | 287 | 208 | 312 | 375 | 250 | 200 | AF10 | 1006 x 2275 x 605/700 | ||
NXC 0325 6 A 2 L 0 RSF | 325 | 358 | 261 | 392 | 470 | 315 | 250 | ||||
NXC 0385 6 A 2 L 0 RSF | 385 | 424 | 325 | 488 | 585 | 355 | 315 | ||||
NXC 0416 6 A 2 L 0 RSF*NXC 0460 6 A 2 L 0 RSFNXC 0502 6 A 2 L 0 RSFNXC 0590 6 A 2 L 0 RSFNXC 0650 6 A 2 L 0 RSFNXC 0750 6 A 2 L 0 RSFNXC 0820 6 A 2 L 0 RSF* | 416460502590650750820 | 416506552649715825902 | 325385460502590650650 | 488578690753885975975 | 585693828904106211701170 | 400450500560630710750 | 315355450500560630650 | AF12 | 2006 x 2275 x 605/1400 | ||
NXC 0920 6 A 2 L 0 RSF | 920 | 1012 | 820 | 1230 | 1476 | 900 | 800 | AF13 | 2206 x 2275 x 605/1950 | ||
NXC 1030 6 A 2 L 0 RSF | 1030 | 1133 | 920 | 1380 | 1656 | 1000 | 900 | ||||
NXC 1180 6 A 2 L 0 RSF* | 1180 | 1298 | 1030 | 1463 | 1755 | 1150 | 1000 | ||||
NXC 1500 6 A 2 L 0 RSF | 1500 | 1650 | 1300 | 1950 | 2340 | 1500 | 1300 | AF14 | 4406 x 2275 x 605/3900 | ||
NXC 1900 6 A 2 L 0 RSF | 1900 | 2090 | 1500 | 2250 | 2700 | 1800 | 1500 | ||||
NXC 2250 6 A 2 L 0 RSF* | 2250 | 2475 | 1900 | 2782 | 3335 | 2000 | 1800 |
*Max. ambient temperature of +35°C.
Hardware configurations
Active front- end | Enclosure | EMC | Brake chopper | Cabling | Input device | Output filters | |||||
380-500 V | IP21 | IP54 | L | T | Bottom | Top+CIT/+COT | +ILS & +ICB | +OCM/+OCH | +ODU | +OSI | |
AF9 | S | O (H: +130) | S | O | * (W: +400) | S | O (W: +400) | S | O | O (W:+400) | O (W: +600) |
AF10 | S | O (H: +130) | S | O | * (W: +400) | S | O (W: +400) | S | O | O (W:+400) | O (W: +600) |
AF12 | S | O (H: +130) | S | O | * (W: +400) | S | O (W: +400) | S | O | O (W:+400) | O (W: +1200) |
AF13 | S | O (H: +170) | S | O | * (W: +400) | S | O (W: +400) | S | O | O | O (W: +800) |
AF14 | S | O (H: +170) | S | O | * (W: +400) | S | O (W: +600) | S | O | S | O (W: +1600) |
525-690 V | |||||||||||
AF9 | S | O (H: +130) | S | O | * (W: +400) | S | O (W: +400) | S | O | O (W:+400) | O (W: +600) |
AF10 | S | O (H: +130) | S | O | * (W: +400) | S | O (W: +400) | S | O | O (W:+400) | O (W: +600) |
AF12 | S | O (H: +130) | S | O | * (W: +400) | S | O (W: +400) | S | O | O (W:+400) | O (W: +1200) |
AF13 | S | O (H: +170) | S | O | * z(W: +400) | S | O (W: +400) | S | O | O | O (W: +800) |
AF14 | S | O (H: +170) | S | O | * (W: +400) | S | O (W: +600) | S | O | S | O (W: +1600) |
S = Standard O = Optional *Contact factory
Technical data
Option boards
Type | Description | Card slot | I / O signal | |||||||||||||||||||||||||
A |
B |
C |
D |
E |
DI | DO | DI DO | AI (mA/V/±V) | AI (mA) isolated | AO (mA/V) | AO (mA) isolated | RO (NO/NC) | RO (NO) | +10Vref | Therm | +24V/ EXT +24 V | pt100 | KTY84 | 42-240 VAC input | DI/DO (10…24 V) | DI/DO (RS422) | DI ~ 1Vp-p | Resolver | Out +5 V/+15 V/+24 V | Out +15 V/+24 V | Out +5 V/+12 V/+15 V | ||
Basic I/O cards (OPTA) | ||||||||||||||||||||||||||||
OPTA1 | DI/DO/AI/AO/ 10V/ 24V | 6 | 1 | 2 | 1 | 1 | 2 | |||||||||||||||||||||
OPTA2 | Relay output (NO/NC) | 2 | ||||||||||||||||||||||||||
OPTA3 | Relay output + Thermistor input | 1 | 1 | 1 | ||||||||||||||||||||||||
OPTA4 | Encoder TTL type | 2 | 3/0 | 1 | ||||||||||||||||||||||||
OPTA5 | Encoder HTL type | 2 | 3/0 | 1 | ||||||||||||||||||||||||
OPTA7 | Double encoder HTL type | 6/2 | 1 | |||||||||||||||||||||||||
OPTA8 | “OPTA1 + Analogue signals galvanically isolated as a group” | 6 | 1 | 2 | 1 | 1 | 2 | |||||||||||||||||||||
OPTA9 | OPTA1 + 2,5mm2 connectors | 6 | 1 | 2 | 1 | 1 | 2 | |||||||||||||||||||||
OPTAE | Encoder HTL type (Divider + direction) | 2 | 3/0 | 1 | ||||||||||||||||||||||||
OPTAF | STO, ATEX therm | 2 | 1 | 1 | 1 | |||||||||||||||||||||||
OPTAK | Sin/Cos encoder interface | 3 | 1 | |||||||||||||||||||||||||
OPTAN | DI/AI/AO | 6 | 2 | 2 | ||||||||||||||||||||||||
I/O expander cards (OPTB) | ||||||||||||||||||||||||||||
OPTB1 | Programmable I/O | 6 | 1 | |||||||||||||||||||||||||
OPTB2 | Relay output + Thermistor input | 1 | 1 | 1 | ||||||||||||||||||||||||
OPTB4 | “Analog input/output Analogue signals galvanically isolated separately” | 1 | 2 | 1 | ||||||||||||||||||||||||
OPTB5 | Relay output | 3 | ||||||||||||||||||||||||||
OPTB8 | “Temperature Measurement option PT100” | 1 | 3 | |||||||||||||||||||||||||
OPTB9 | DI + Relay output | 2 | 1 | 5 | ||||||||||||||||||||||||
OPTBH | “Temperature Measurement option pt100, pt1000, Ni1000, KTY84” | 3 | 3 | |||||||||||||||||||||||||
OPTBB | EnDat + Sin/Cos 1 Vp-p | 2 | 0/2 | 2 | 1 | |||||||||||||||||||||||
OPTBC | Resolver, 3xDO (Wide range) | 3/3 | 1 | |||||||||||||||||||||||||
OPTBE | EnDat/SSI/BiSS C | |||||||||||||||||||||||||||
OPTBL | Advanced safety option | 4 | 2 | 1 | ||||||||||||||||||||||||
OPTBM | OPTBL+ HTL/TTL encoder | 4 | 2 | 1 | ||||||||||||||||||||||||
OPTBN | OPTBL+ Sin/Cos encoder | 4 | 2 | 1 | ||||||||||||||||||||||||
Fieldbus cards (OPTC and OPTE)* | ||||||||||||||||||||||||||||
OPTE2 | RS485 with screw terminal | RS485 with screw terminal | ||||||||||||||||||||||||||
OPTE3 | PROFIBUS DP with screw terminal | PROFIBUS DP with screw terminal | ||||||||||||||||||||||||||
OPTE5 | PROFIBUS DP with D9-connector | PROFIBUS DP with D9-connector | ||||||||||||||||||||||||||
OPTE6 | CANopen | CANopen | ||||||||||||||||||||||||||
OPTE7 | DeviceNet | DeviceNet | ||||||||||||||||||||||||||
OPTE8 | RS485 with D9-connector | RS485 with D9-connector | ||||||||||||||||||||||||||
OPTE9 | Dual-port Ethernet | Dual-port Ethernet | ||||||||||||||||||||||||||
OPTEA | Advanced Dual-port Ethernet | Advanced Dual-port Ethernet | ||||||||||||||||||||||||||
OPTC2 | RS485 with screw terminal | RS485 with screw terminal | ||||||||||||||||||||||||||
OPTC3 | PROFIBUS DP with screw terminal | PROFIBUS DP with screw terminal | ||||||||||||||||||||||||||
OPTC4 | LonWorks | LonWorks | ||||||||||||||||||||||||||
OPTC5 | PROFIBUS DP with D9-connector | PROFIBUS DP with D9-connector | ||||||||||||||||||||||||||
OPTC6 | CANopen | CANopen | ||||||||||||||||||||||||||
OPTC7 | DeviceNet | DeviceNet | ||||||||||||||||||||||||||
OPTC8 | RS485 with D9-connector | RS485 with D9-connector | ||||||||||||||||||||||||||
OPTCI | Modbus/TCP | Modbus TCP | ||||||||||||||||||||||||||
OPTCJ | BACnet MS/TP | BACnet MS/TP | ||||||||||||||||||||||||||
OPTCP | PROFINET IO | PROFINET IO | ||||||||||||||||||||||||||
OPTCQ | EtherNet/IP | EtherNet/IP | ||||||||||||||||||||||||||
Communication cards (OPTD) | ||||||||||||||||||||||||||||
OPT-D1 | SystemBus adapt, 2xfibre-optic | System Bus adapter (2 x fiber optic pairs) | ||||||||||||||||||||||||||
OPT-D2 | SystemBus (1xfiber), isol. CAN | System Bus adapter (1 x fiber optic pair) & CAN-bus adapter (galvanically decoupled) | ||||||||||||||||||||||||||
OPT-D3 | RS232 adapter (no galv.isol.) | RS232 adapter card (galvanically decoupled), used mainly for application engineering to connect another keypad | ||||||||||||||||||||||||||
OPT-D6 | CAN-Bus (galv. decoupled) | CAN-bus adapter (galvanically decoupled) | ||||||||||||||||||||||||||
OPT-D7 | Line voltage measurement | Line voltage measurement |
*) OPTE series fieldbus cards provide most recent features on market and they are recommended for new installation
- Analogue signals galvanically isolated as a group
- Analogue signals galvanically isolated separately
VACON® NXC options
Control terminal options (T group) | |
+TIO | Basic I/O wired to external single-tier terminals |
+TID | Basic I/O wired to external two-tier terminals
+ additional terminals |
+TUP* | Terminals for 230 VAC control voltage |
Input device options (I group) | |
+ILS* | Load switch |
+IFD | Switch fuse and fuses |
+ICB* | Circuit breaker |
+ICO | Input contactor |
+IFU | Input fuses |
Main circuit options (M group) | |
+MDC | Terminals in cabinet for DC / brake chopper |
Output filter options (O group) | |
+OCM | Common mode filters |
+OCH | Common mode filters with output terminals |
+ODU | du/dt filter |
+OSI | Sine wave filter |
Protection devices (P group) | |
+PTR | External thermistor relay |
+PES | Emergency stop (cat 0) |
+PED | Emergency stop (cat 1) |
+PAP | Arc protection |
+PIF | Insulation fault sensor |
General options | |
+G40 | 400 mm empty cabinet |
+G60 | 600 mm empty cabinet |
+G80 | 800 mm empty cabinet |
+GPL | 100 mm base |
+GPH | 200 mm base |
+FAT | Factory acceptance tests |
+MAR | Marine construction |
+SWP | Seaworthy packing |
Cabling options (C group) | |
+CIT | Input (mains) cabling from top |
+COT | Output (motor) cabling from top |
Auxiliary equipment (A group) | |
+AMF | Motor fan control |
+AMH | Motor heater feeder |
+AMB | Mechanical brake control |
+AMO* | Motor operator for +ICB |
+ACH | Cabinet heater |
+ACL | Cabinet light |
+ACR | Control relay |
+AAI | Analogue signal isolator |
+AAA | Auxiliary contact (control voltage devices) |
+AAC | Auxiliary contact (input device) |
+AT1 | Auxiliary voltage transformer 200 VA |
+AT2* | Auxiliary voltage transformer 750 VA |
+AT3 | Auxiliary voltage transformer 2500 VA |
+AT4 | Auxiliary voltage transformer 4000 VA |
+ADC* | Power supply 24 VDC 2.5 A |
+ACS | 230 VAC customer socket |
Door-mounted options (D group) | |
+DLV | Pilot light (Control voltage on) |
+DLD | Pilot light (DO1) |
+DLF | Pilot light (FLT) |
+DLR | Pilot light (RUN) |
+DCO* | Main contactor operation switch |
+DRO* | Local / Remote operation switch |
+DEP | Emergency stop push-button |
+DRP | Reset push-button |
+DAM | Analogue meter (AO1) |
+DAR | Potentiometer for reference |
+DCM | Analogue meter & current transformer |
+DVM | Analogue voltage meter with selection switch |
EMC selection table
The product family standard
EN 61800-3 sets limits for both emissions and immunity to radio frequency disturbances. The environment has been divided into the first and second environments; in practice, public and industrial networks, respectively. Radio Frequency Interference (RFI) filters are typically required to meet the EN 61800-3 standard. These filters are integrated in the VACON® NXP as standard. The 208-240 V and 380 500 V ranges of the VACON® NXP (FR4-FR9) meet the requirements of the first and second environments (H level: EN 61800-3 (2004), category C2). No additional RFI filters or cabinets are required. The FR10-FR14 and the 500-690 V ranges of the VACON® NXP meet the requirements of the second environment (L-level: EN 61800-3(2004), category C3). The units in the frame sizes FR4, FR5 and FR6 (with a voltage range from 380 to 500 V) are also available with extremely low-emission integrated EMC filters (C level: EN 61800-3 (2004), category C1). This is sometimes required in very sensitive locations, such as hospitals.
Type code key
NXC 0520 5 A 2 L O S S F A1 A2 00 00 00 + IFD
- NXC Product Range
- NXP = Wall-mounted / standalone / module
- NXC = Cabinet
- 0520 Nominal current voltage
- 0520 = 520 A
- 5 Nominal mains voltage
- 2 = 208-240 V
- 5 = 380-500 V
- 6 = 525-690 V
- A Control keypad
- A = Standard alphanumeric
- B = No local keypad
- F = Dummy keypad
- G = Graphic display
- 2 Enclosure class
- 5 = IP54, FR4-10; NXC FR9-FR14; AF9-14
- 2 = IP21, FR4-11; NXC FR9-FR14; AF9-14
- 0 = IP00, NXP FR10-14
- L EMC emission levels
- C = Category C1, EN 61800-3
- H = Category C2, EN 61800-3
- L = Category C3, EN 61800-3
- T = For IT networks
- N = Enclosure required (FR10-FR14) 0 Brake chopper 0 = No brake chopper 1 = Integrated brake chopper S Supply S = 6-pulse
- T = 12-pulse
O = 6-pulse + load switch (standalone) - R = Low Harmonic S Cooling
- S = standard air-cooled
- T = through-hole mounting FR4-FR9
- F Control
- S = Standard FR4-FR8
- F = Standard FR9 and NXC
- A = Standard NXP FR10-FR12
- N = Standard IP00 FR10 & NXC with IP54 control unit enclosure
- V = As S, but varnished
- G = As F, but varnished boards
- O = As N, but varnished boards
- B = As A, but varnished boards
- A1 Option boards; each slot is represented by two characters:
- Ax = Basic I/O boards,
- Bx = Expander I/O boards
- Cx = Fieldbus boards,
- Dx = Special boards A2 00 00 00 + IFD NXC options, see tables page 22
DrivePro® Life Cycle services
Delivering a customized service experience! We understand that every application is different. Having the ability to build a customized service package to suit your specific needs is essential. DrivePro® Life Cycle Services is a collection of tailormade products designed around you. Each one engineered to support your business through the different stages of your AC drive’s life cycle. From optimized spare-part packages to condition-monitoring solutions, our products can be customized to help you achieve your business goals. With the help of these products, we add value to your application by ensuring you get the most out of your AC drive. When you deal with us, we also offer you access to training, as well as the application knowledge to help you in planning and preparation. Our experts are at your service.
You’re covered
with DrivePro® Life Cycle service products
DrivePro® Retrofit
Minimize the impact and
maximize the benefit
Manage the end of product lifecycle efficiently, with professional help to replace your legacy drives.
The DrivePro® Retrofit service ensures optimal uptime and productivity during the smooth replacement process.
DrivePro® Spare Parts
Plan ahead with your spare part package
In critical situations, you want no delays. With DrivePro® Spare Parts you always have the right parts on hand, on time. Keep
your drives running at top efficiency, and optimize system performance.
DrivePro® Extended Warranty
Long-term peace of mind
Get the longest coverage available in the industry, for peace of mind, a strong business case and a stable, reliable budget. You know the annual cost of maintaining your drives, up to six years in advance.
DrivePro® Exchange
The fast, most cost-efficient alternative to repair
You obtain the fastest, most cost-efficient alternative to repair, when time is critical. You increase uptime, thanks to quick and correct replacement of the drive.
DrivePro® Upgrade
Maximize your AC drive investment
Use an expert to replace parts or software in a running unit, so your drive is always up-to-date. You receive an on-site evaluation, an upgrade plan and recommendations for future improvements.
DrivePro® Start-up
Fine-tune your drive for optimal performance today
Save on installation and commissioning time and cost. Get help from professional drives experts during start-up, to optimize drives safety, availability and performance.
DrivePro® Preventive Maintenance
Take preventive action
You receive a maintenance plan and budget, based on an audit of the installation. Then our experts perform the maintenance tasks for you, according to the defined plan.
DrivePro® Remote Expert Support
You can rely on us every step of the way
DrivePro® Remote Expert Support offers speedy resolution of on-site issues thanks to timely access to accurate information. With the secure connection, our drives experts analyze issues remotely reducing the time and cost involved in unnecessary service visits.
DrivePro® Remote Monitoring
Fast resolution of issues DrivePro® Remote Monitoring offers you a system that provides online information available for monitoring in real time. It collects all the relevant data and analyzes it so that you can resolve issues before they affect your processes.
To learn which products are available in your region, please reach out to your local Danfoss Drives sales office or visit our website http://drives.danfoss.com/danfoss-drives/local-contacts/
Stay calm. You’re covered.
Stay calm. You’re covered.
Use the DrivePro® app for fast access to the DrivePro® services, for improved productivity, performance and uptime of your systems. Find your closest service partner, place a service request, and register your AC drives. You can also look up product information, specifications and manuals for your specific drive.
Quick, simple, reliable. Giving you complete control.
Follow us and learn more about AC drives
Danfoss Drives
Danfoss Drives is a world leader in variable speed control of electric motors. We aim to prove to you that a better tomorrow is driven by drives. It is as simple and as ambitious as that.
We offer you unparalleled competitive edge through quality, application-optimized products targeting your needs – and a comprehensive range of product lifecycle services. You can rely on us to share your goals. Striving for the best possible performance in your applications is our focus. We achieve this by providing the innovative products and application know-how required to optimize efficiency, enhance usability, and reduce complexity.
From supplying individual drive components to planning and delivering complete drive systems; our experts are ready to support
you all the way.
We draw on decades of experience within industries that include:
- Chemical
- Cranes and Hoists
- Food and Beverage
- HVAC
- Lifts and Escalators
- Marine and Offshore
- Material Handling
- Mining and Minerals
- Oil and Gas
- Packaging
- Pulp and Paper
- Refrigeration
- Water and Wastewater
- Wind
You will find it easy to do business with us. Online, and locally in more than 50 countries, our experts are never far away, reacting fast when you need them. Since 1968, we have been pioneers
in the drives business. In 2014, Vacon and Danfoss merged, forming one of the largest companies in the industry. Our AC drives can adapt to any motor technology and we supply products in a power range from 0.18 kW to 5.3 MW.
Frequently Asked Questions
- Q: What industries can benefit from this product?
A: This product is ideal for industries such as mining, compressors, marine, cranes, metals, chemical, water treatment, oil & gas, pulp & paper, cement, and general process industries. - Q: How can I access support for this product?
A: Danfoss Drives provides global service solutions available 24/7 to assist original equipment manufacturers (OEMs), system integrators, distributors, and end users throughout the product lifecycle.
Documents / Resources
![]() |
Danfoss VACON NXP and VACON NXC AC Drives [pdf] User Guide 0.55 kW, 2 MW, VACON NXP and VACON NXC AC Drives, and VACON NXC AC Drives, NXC AC Drives, AC Drives |