Danfoss-logo

Danfoss Link Connect Thermostat

Danfoss-Link-Connect-Thermostat-product-image

Specifications

  • Product Name: Danfoss LinkTM & Connect Thermostats
  • Application: Heating Control
  • Maximum Coverage Area: Up to 300 m2 for 1 and 2 family houses and flats

Introduction

Segment
This application guide covers the use of Danfoss Link™, Danfoss Link™ Connect Thermostat wireless heating controls and Danfoss Eco™ in 1 and 2 family houses and flats up to 300 m2.

Danfoss Eco™ programmable radiator thermostat
Danfoss Eco™ is a stand-alone intelligent and programmable radiator thermostat* for residential use, where a central control system is not available
It is easy to install and is supplied with adapters for all thermostatic valves manufactured by Danfoss and most other radiator valve manufacturers.

Danfoss-Link-Connect-Thermostat-image (1)

Overview of units in a Danfoss Link™ system
The following units can be used in a Danfoss Link™ wireless system:

  • Danfoss Link™ CC Central Controller is the unit, from which the entire installation can be controlled. One Danfoss Link™ CC is always needed in a system.Danfoss-Link-Connect-Thermostat-image (2)
  • Danfoss Link™ HC Hydronic Controller allows control of hydronic floor heating with a large range of functions.
    Danfoss-Link-Connect-Thermostat-image (3)
  • Danfoss Link™ FT Floor Thermostat is used for measuring and adjusting electrical floor heating. Danfoss-Link-Connect-Thermostat-image (4)
  • Danfoss Link™ RU Repeater Unit is used for extending the wireless transmission range between Danfoss Link™ CC and other units in a system. Danfoss-Link-Connect-Thermostat-image (5)
  • Danfoss Link™ Connect Thermostat is an electronic radiator thermostat* for residential use, which is controlled by a Danfoss Link™ CC. Danfoss-Link-Connect-Thermostat-image (6)
  • Danfoss Link™ RS Room Sensor is used for measuring and adjusting the room temperature. Danfoss-Link-Connect-Thermostat-image (7)
  • Danfoss Link™ BR Boiler Relay is a unit for turning gas and oil boilers ON/OFF, depending on heating demand.

Danfoss-Link-Connect-Thermostat-image (8)

Danfoss recommends using Connect and Eco™ Thermostats together with Danfoss radiator valves with integrated pre-setting in order to achieve optimal performance.

For chaise of adaptor please use the Danfoss adaptor guide, which also includes adaptors for non Danfoss valves.

Number of units in a Danfoss Link™ system
When building a wireless Danfoss Link™ control system it is important to follow these rules:

  1. The total number of units must not exceed 50 (1 Danfoss Link™ Central Controller + 49 units).
  2. The number of each type of unit must not exceed:
  • Danfoss Link™ CC . . . . . . . . . . . . . . . . . . . . . . 1 unit
  • Connect Thermostat . . . . . . . . . . . . . . . . . 30 units
  • Danfoss Link™ HC . . . . . . . . . . . . . . . . . . . . . 3 units
  • Danfoss Link™ RS . . . . . . . . . . . . . . . . . . . . 30 units
  • Danfoss Link™ FT . . . . . . . . . . . . . . . . . . . . . 30 units
  • Danfoss Link™ BR . . . . . . . . . . . . . . . . . . . . . . 1 unit
  • Danfoss Link™ RU . . . . . . . . . . . . . . . . . . . . . 3 units

Best practice

Mains powered units
Avoid disconnecting mains powered units in a Danfoss Link™ system. In the event this happens the system will eventually re-establish the network, when repeater unit is reconnected to the mains power.Danfoss-Link-Connect-Thermostat-image (9)

Danfoss Link™ RU Repeater units
It is always recommended to use Danfoss Link™ RU, when a repeater is needed to extend the radio communication range. Several mains powered units (such as relays) also act as repeaters, but with limited capability to improve the communication range compared to Danfoss Link™ RU.

Danfoss Link™ RU repeaters should always be registered as the first 230 V units in the system.

Danfoss Link™ RS Room Sensor

  • The Danfoss Link™ RS is designed to measure the room temperature and control the Connect Thermostats to reach the set room temperature.
  • The Danfoss Link™ RS is useful in all applications where the actual temperature at the Connect Thermostat is significantly different from the desired room temperature., or if you have multiple radiators in the same room.
  • Best performance of the system with Connect Thermostats and Danfoss Link™ RS is achieved, if the RS is not too far from the radiator, best between 1 and 5 meters.
  • Make sure to select the proper settings for the Connect Thermostat and Danfoss Link™ RS on Danfoss Link™ CC. Choose the “covered radiator” option if the radiator is behind a fixed radiator cover and possibly if the radiator and Connect Thermostat is covered by heavy furniture.Danfoss-Link-Connect-Thermostat-image (10)
  • Do not install Danfoss Link™ RS on outer walls or where it will be subject to direct sunlight.
  • The installation height should typically be between 80-150 cm.
  • In wet rooms Danfoss Link™ RS shall be installed according to local building regulations.
  • At least 50 cm away from windows/doors that will be left open occasionally.

General Guidelines

Heat supply
If the heating system has been optimized for constant set temperature around the clock, you may need to adjust the settings when working with setback periods. When changing the temperature from a low economy setting to a comfort temperature, the system must be able to supply enough heat to raise the room temperature at least 1 °C per hour to perform well. Compared to a steady temperature the heating system must typically be able to supply 25% more heat, but only for a short period of time during heat up.Danfoss-Link-Connect-Thermostat-image (11)

How to achieve 25% extra capacity in a system that should run boost:

Limitations Action
Max. ∆P and temperature reached: Increase valve presetting
Max. temperature and preset reached: Increase pump pressure
Max. preset and ∆P reached: Increase water temperature

Note: Maximum acceptable presetting, water temperature and pump differential pressure settings are different from system to system and depend on the application.

  • For radiator valves with pre-setting, balance the system to allow for enough flow.Danfoss-Link-Connect-Thermostat-image (12)
  • The supply line temperature at the radiator valves should be above 40 °C to ensure optimal control.
  • Make sure that the supply water temperature and flow is adequate to provide enough energy.
  • Increase the temperature or the pump level, if necessary.

Danfoss-Link-Connect-Thermostat-image (13)

Functions

  • Connect Thermostats have a built-in function, which automatically shut off the heat while the room is ventilated. When the thermostat detects a drop in room temperature, it closes the valve.
  • To prevent excessive cooling of the room, the thermostat will automatically open the valve again after 30 minutes, meaning that during longer periods of ventilation you must manually set the temperature down.
  • To prevent multiple detections of ventilation, e.g. caused by opening a door, leading to instability, the thermostat will not detect a new ventilation session in a period of 45 minutes from the previous occurrence.

Danfoss-Link-Connect-Thermostat-image (14)

  • Be aware that a large window sill might prevent the Connect Thermostat from detecting cold air from an open window, and thereby not activate the automatic Open-window function. Danfoss-Link-Connect-Thermostat-image (15)
  • If the radiator is under or oversized in relation to the room, the settings should be changed accordingly.
  • Connect Thermostat: to change the settings, please refer to the Connect Thermostat installation and user guide. Danfoss-Link-Connect-Thermostat-image (16)

The adaptive learning function (Forecast) ensures that the comfort temperature is reached at set time. The warm up time is continuously adjusted according to seasonal temperature changes.

  • Adaptive learning ensures the wanted temperature at the wanted time (here 20 °C at 07:00).
  • Adaptive learning uses data from the previous 7 days to be able to reach the correct temperature at the right time.
  • Adaptive learning is sensitive to large, rapid temperature changes.

Danfoss-Link-Connect-Thermostat-image (17)

Rooms
Covering the radiator – e.g. with furniture, curtains or a radiator cover – might cause heat to be accumulated around the thermostat.

Danfoss-Link-Connect-Thermostat-image (18)

Light curtain/furniture:

  • Connect Thermostat: can be used, but function is improved by using a RS room sensor.
  • Danfoss Eco™: can be used, but it might be necessary to raise the set temperature.

Medium curtain/furniture:

  • Connect Thermostat: use with Danfoss Link™ RS room sensor.
  • Danfoss Eco™: can be used, but it might be necessary to raise the set temperature.

Radiator cover:

  • Connect Thermostat: use with Danfoss Link™ RS room sensor.
  • Danfoss Eco™: not recommended in this situation.

If two radiators are placed within 40 cm of each other, the heat emission from one radiator can affect the thermostat on the other radiator.

  • Connect Thermostat: use with Danfoss Link™ RS room sensor.
  • Danfoss Eco™: balance the two radiators by adjusting the set temperature on the affected radiator.

Danfoss-Link-Connect-Thermostat-image (19)

  • Direct heat radiation from large radiators may disturb the Connect Thermostats ability to measure the room temperature correctly.
  • To avoid this, mount the thermostat pointing away from the radiator.
  • The optimal solution is a Connect Thermostat with a Danfoss Link™ RS room sensor.

Danfoss-Link-Connect-Thermostat-image (20)

Danfoss do not recommend to use an angle adapter, instead the valve should be turned or replaced.

  • A fireplace in the room can affect the adaptive learning function of the Connect Thermostat and disturb the heating control.
  • If you use your fireplace regularly it is recommended to deactivate the adaptive learning.
  • By deactivating the adaptive learning function, Connect will work as a traditional thermostat, but with a delay in heating up the room after the fire has burned out.

Note: If the valve has been closed for a longer period there may be a delay in heating up the room.

Danfoss-Link-Connect-Thermostat-image (21)

  • Sunlight from large windows in the room can affect the adaptive learning function of the Connect Thermostat and disturb the heating control. Then it is recommended to deactivate the adaptive learning.
  • By deactivating the adaptive learning function, Connect will work as a traditional thermostat, but with a delay in heating up the room after the heating from the sunlight has stopped. Danfoss-Link-Connect-Thermostat-image (22)

Continuous draft from a leaky window or garden door directly on the Connect Thermostat will disturb the heating control.

  • Connect Thermostat: use with Danfoss Link™ RS room sensor.
  • Danfoss Eco™ : We do not recommend using Danfoss Eco™ in installations where temperature measurement at the thermostat is not representative of the room temperature. In an installation with frequent draft, the regulation may become instable and lead to fluctuating temperature and reduced battery life.

Danfoss-Link-Connect-Thermostat-image (23)

  • Connect Thermostats are primarily designed to be used with supply valves.
  • But Connect Thermostats can also be used with return valves on small radiators (smaller than 120 cm diagonally, rule of thumb).
  • On larger radiators with return valves Connect Thermostats are not recommended.Danfoss-Link-Connect-Thermostat-image (24)
  • Neither Connect Thermostat nor Danfoss Eco™ should be used on convectors placed in floor trenches. Danfoss-Link-Connect-Thermostat-image (25)

Applications

Heating System with Boiler

Description

  • A boiler with build-in or external domestic hot water tank can provide instant heat for the heating system, as well as for the domestic hot water.
  • The system can be operated with or without a Danfoss Link™ BR (Boiler Relay).

Minimum requirements

  • minimum 40 °C supply temperature at the valve.
  • sufficient heating capacity to increase the room temperature with 1 °C per hour.
  • only radiator valves approved for Danfoss adapters.

Note! Bypass valve is recommended.

Danfoss-Link-Connect-Thermostat-image (26)

Recommendations

Central room temperature with night setback
If a central room temperature controller is used in combination with Connect Thermostats, it must only be as temperature limiter.

Danfoss-Link-Connect-Thermostat-image (27)

Boiler turned off at night
If the boiler is turned off or has reduced temperature during the night, then make sure that it is active when the Connect Thermostat is programmed to warm. In a system with Danfoss Link™ CC and Connect Thermostat, this can be controlled automatically by adding a boiler relay Danfoss-Link-Connect-Thermostat-image (28)

  • With Forecast: The Forecast period should vary over the year, but typically the boiler will start up to 3 hours before the comfort period.
  • Without Forecast: The boiler should typically start up ½ hour before the comfort period.

Weather compensation
If the boiler’s heating curve is set to have the radiator thermostats on comfort temperature constantly, the curve must be increased in order to be able to raise the room temperature after a setback period.

  • If the setback periods are long, further increase might be necessary.
  • If the economy periods are short, less increase can be sufficient.

Danfoss-Link-Connect-Thermostat-image (29)

Boiler relay
Set Danfoss Link™ BR boiler relay to automatic ON/OFF in the Danfoss Link™ set-up menu.

Heating System with Central Boiler

Description
A large gas, oil or pallet boiler which provides hot water to several households.

Danfoss-Link-Connect-Thermostat-image (30)

Min. requirements

  • min. 40 °C supply temperature at the valve.
  • sufficient heating capacity to increase the room temperature with 1 °C per hour.
  • only radiator valves approved for Danfoss adapters.

Recommendations

Boiler turned off at night
If the boiler is turned off or has reduced temperature during the night, then make sure that it is active when the Connect Thermostat is programmed to warm. In a system with Danfoss Link™ CC and Connect Thermostat, this can be controlled automatically by adding a boiler relay

Danfoss-Link-Connect-Thermostat-image (31)

  • With Forecast: The Forecast period should vary over the year, but typically the boiler will start up to 3 hours before the comfort period.
  • Without Forecast: The boiler should typically start up ½ hour before the comfort period.

Weather compensation
If the boiler’s heating curve is set to have the radiator thermostats on comfort temperature constantly, the curve must be increased in order to be able to raise the room temperature after a setback period.

  • If the setback periods are long, further increase might be necessary.
  • If the economy periods are short, less increase can be sufficient.

Danfoss-Link-Connect-Thermostat-image (32)

District Heating

Description
District heating is generated in a centralized location and distributed to residential and commercial use.

Danfoss-Link-Connect-Thermostat-image (33)

Min. requirements

  •  min. 40 °C supply temperature at the valve.
  • sufficient heating capacity to increase the room temperature with 1 °C per hour.
  • only radiator valves approved for Danfoss adapters.

Recommendations

Weather compensation / ECL
If the boiler’s heating curve is set to have the radiator thermostats on comfort temperature constantly, the curve must be increased in order to be able to raise the room temperature after a setback period.

  • If the setback periods are long, further increase might be necessary.
  • If the economy periods are short, less increase can be sufficient.

Danfoss-Link-Connect-Thermostat-image (34)

Heat Pump

Description
|A heat pump is generating heating by transferring heat from a relatively low-temperature reservoir, such as air or ground, to one at a higher temperature.Danfoss-Link-Connect-Thermostat-image (35)

Min. requirements

  • min. 40 °C supply temperature at the valve.
  • sufficient heating capacity to increase the room temperature with 1 °C per hour.
  • only radiator valves approved for Danfoss adapters.

Recommendations

Weather compensation
If the heat pump’s heating curve is set to have the radiator thermostats on comfort temperature constantly, the curve must be increased in order to be able to raise the room temperature after a setback period.Danfoss-Link-Connect-Thermostat-image (36)

  • If the setback periods are long, further increase might be necessary.
  • If the economy periods are short, less increase can be sufficient.

If system is installed during period with outside temperature > 10° C opening point will not be found untill temperature drops below 7-8° C. Can be solved by manually setting the heating curve higher during the run in period (approx. 1 week).

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its without notice. This also applies to already on order provided that such alterations can be made without sub sequential changes being necessary in specifications already agreed,

All trademarks in this material are property Of the respective companies. Danfoss and the Danfoss logotype are trademarks Of Danfoss A1’S. All rights reserved.

FAQ

  • Q: Can I exceed the recommended number of units in a Danfoss LinkTM system?
    • A: It is not recommended to exceed the specified limits to maintain system efficiency and performance.
  • Q: How do I reset the network if mains powered units are disconnected?
    • A: Reconnect the repeater unit to allow the system to re-establish the network automatically.

Documents / Resources

Danfoss Link Connect Thermostat [pdf] User Guide
Link Connect Thermostat, Connect Thermostat, Thermostat

References

Leave a comment

Your email address will not be published. Required fields are marked *