Danfoss FC 360 Decoupling Plate Kit Installation Guide
These instructions provide information about replacement of the decoupling plate kit in the VLT® AutomationDrive FC 360.
Only Danfoss-authorised, qualified personnel is allowed to repair this equipment. The personnel must be familiar with the instructions and safety measures described in the VLT® AutomationDrive FC 360 Service Manual.
Items Supplied
Items supplied depend on the ordering number and enclosure type of the frequency converter.
Ordering numbers | Items supplied |
132B0258 |
|
132B0259 |
|
132B0260 |
|
132B0284 |
|
132B0285 |
|
Table 1.1 Ordering Numbers
Tools Required
- Screwdrivers:
- Flat-edged
- T10
- T20
- T25
- T30
- N8 socket wrench
- N10 socket wrench
- N5 Allen key
Safety Instructions
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors, which can remain charged even when the frequency converter is not powered. Failure to wait the specified time after power has been removed before performing service or repair work, could result in death or serious injury.
- Stop the motor.
- Disconnect AC mains, permanent magnet type motors, and remote DC-link power supplies, including battery back-ups, UPS, and DC-link connections to other frequency converters.
- Wait for the capacitors to discharge fully, before performing any service or repair work. The duration of waiting time is specified in Table 1.2.
Voltage [V] | Minimum waiting time (minutes) | |
4 | 15 | |
380-480 | 0.37-7.5 kW | 11-75 kW |
High voltage may be present even when the warning LEDs are off! |
Table 1.2 Discharge Time
Mounting I/O Decoupling Plate
For J1 Enclosure Type Only
Mount the I/O decoupling bracket on the power decoupling plate with 2 M4x10 screws (supplied).
Tightening torque: 1.0~1.2 Nm
Illustration 1.1 I/O Decoupling Plate, J1
Mounting Power Decoupling Plate
For J1, J2 and J3 Enclosure Types
- Remove the earth screw (M6x12) from the frequency converter.
- Mount the power decoupling plate on the frequency converter and fasten it with the 2 supplied screws (M4x10).
Tightening torque: 1.0~1.2 Nm - Remount the earth screw (M6x12).
Tightening torque: 0.5~0.8 Nm
Illustration 1.2 Frequency Converter without Decoupling Plate, J1- J3
Illustration 1.3 Frequency Converter with Decoupling Plate, J1-J3
For J4 and J5 Enclosure Types
- Remove the earth plate from the frequency converter (J4 only).
- Mount the power decoupling plate on the frequency converter and fasten it with the 2 supplied screws (M4x10).
Tightening torque: 1.0~1.2 Nm - Remount the earth screw (M6x12).
Tightening torque: 0.5~0.8 Nm
Illustration 1.4 Remove the Earth Plate, J4
Illustration 1.5 Mount the Decoupling Plate, J4-J5
For J6 Enclosure Type
- Remove the right earth plate.
- Fit the snaps of the power decoupling plate into the slots on the frequency converter and fasten the 2 M4x12 screws, as shown in Illustration 1.6.
Illustration 1.6 Mount the Power Decoupling Plate, J6 - Fasten the shield plate to the power decoupling plate with 3 screws, and mount the earth plate, as shown in Illustration 1.7.
Illustration 1.7 Mount the Shield Plate
For J7 Enclosure Type
- Fit the snaps of the power decoupling plate into the slots and fasten the 2 M4x6 screws, as shown in Illustration 1.8.
Illustration 1.8 Mount the Power Decoupling Plate, J7
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice already on order provided that such alterations can be made without sub sequential changes being necessary in specifications already agreed.