Decoupling Plate Kit VLT® AutomationDrive FC 360

These instructions provide information about replacement of the decoupling plate kit in the VLT® AutomationDrive FC 360. Only Danfoss-authorised, qualified personnel is allowed to repair this equipment. The personnel must be familiar with the instructions and safety measures described in the VLT® AutomationDrive FC 360 Service Manual.
1.1.1 Items Supplied
Items supplied depend on the ordering number and enclosure type of the frequency converter.

Ordering numbers 132B0258
132B0259 132B0260 132B0284
132B0285

Items supplied
· Power decoupling plate, J1 · I/O decoupling plate · Screws (M4x10) · Power decoupling plate, J2/J3 · Screws (M4x10) · Power decoupling plate, J4/J5 · Screws (M4x10) · Power decoupling plate, J6 · Shield plate for line-in and motor · Screws (M4x12) · Earth plates · Power decoupling plate, J7 · Screws (M4x6) · Earth plates

Table 1.1 Ordering Numbers

1.1.2 Tools Required
· Screwdrivers:
- Flat-edged - T10 - T20 - T25 - T30
· N8 socket wrench · N10 socket wrench · N5 Allen key

1.1.3 Safety Instructions
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors, which can remain charged even when the frequency converter is not powered. Failure to wait the specified time after power has been removed before performing service or repair work, could result in death or serious injury.
1. Stop the motor.
2. Disconnect AC mains, permanent magnet type motors, and remote DC-link power supplies, including battery back-ups, UPS, and DC-link connections to other frequency converters.
3. Wait for the capacitors to discharge fully, before performing any service or repair work. The duration of waiting time is specified in Table 1.2.

Voltage [V]

Minimum waiting time (minutes)

4

15

380-480

0.37-7.5 kW

11-75 kW

High voltage may be present even when the warning LEDs are off!

Table 1.2 Discharge Time

Danfoss A/S © Rev. 2014-02-28 All rights reserved.

MI06A302

Installation Instructions

Decoupling Plate Kit VLT® AutomationDrive FC 360

1.1.4 Mounting I/O Decoupling Plate
For J1 Enclosure Type Only
Mount the I/O decoupling bracket on the power decoupling plate with 2 M4x10 screws (supplied). Tightening torque: 1.0~1.2 Nm

Illustration 1.2 Frequency Converter without Decoupling Plate, J1J3

Illustration 1.1 I/O Decoupling Plate, J1

1.1.5 Mounting Power Decoupling Plate
For J1, J2 and J3 Enclosure Types
1. Remove the earth screw (M6x12) from the frequency converter.
2. Mount the power decoupling plate on the frequency converter and fasten it with the 2 supplied screws (M4x10). Tightening torque: 1.0~1.2 Nm
3. Remount the earth screw (M6x12). Tightening torque: 0.5~0.8 Nm

Illustration 1.3 Frequency Converter with Decoupling Plate, J1-J3

2

Danfoss A/S © Rev. 2014-02-28 All rights reserved.

MI06A302

Installation Instructions

Decoupling Plate Kit VLT® AutomationDrive FC 360

For J4 and J5 Enclosure Types
1. Remove the earth plate from the frequency converter (J4 only).
2. Mount the power decoupling plate on the frequency converter and fasten it with the 2 supplied screws (M4x10). Tightening torque: 1.0~1.2 Nm
3. Remount the earth screw (M6x12). Tightening torque: 0.5~0.8 Nm

Illustration 1.4 Remove the Earth Plate, J4

Illustration 1.5 Mount the Decoupling Plate, J4-J5
For J6 Enclosure Type
1. Remove the right earth plate. 2. Fit the snaps of the power decoupling plate into the
slots on the frequency converter and fasten the 2 M4x12 screws, as shown in Illustration 1.6.

MI06A302

Illustration 1.6 Mount the Power Decoupling Plate, J6

Danfoss A/S © Rev. 2014-02-28 All rights reserved.

3

3. Fasten the shield plate to the power decoupling plate with 3 screws, and mount the earth plate, as shown in Illustration 1.7.
Illustration 1.7 Mount the Shield Plate
For J7 Enclosure Type
1. Fit the snaps of the power decoupling plate into the slots and fasten the 2 M4x6 screws, as shown in Illustration 1.8.

Illustration 1.8 Mount the Power Decoupling Plate, J7