Danfoss ERC 214 Digital Regulator Installation Guide

ERC 214 Digital Regulator

Product Information

Specifications

  • Model: ERC 214
  • Function: Digital regulator for refrigeration and
    defrosting
  • Relays: 4
  • Temperature Sensing: Operating temperature control
  • Applications: Suitable for refrigeration and heating

Product Usage Instructions

1. Installation

Follow the provided dimensions and assembly instructions for
proper installation of the ERC 214 controller.

2. User Interface

Button Functions:

  • Press and hold down on startup: RESET FACTORY SETTINGS (FAC is
    displayed)
  • Press for one second: BACK
  • Press and hold down: PULL-DOWN
  • Press for one second: TEMPERATURE SETPOINT/OK
  • Press and hold down: MENU
  • Press for one second: UP
  • Press and hold down: ON/OFF
  • Press for one second: DOWN
  • Press and hold down: DEFROSTING

Display Icons:

  • Night mode (energy saving)
  • Fan on
  • Compressor on (Blinks in pull-down mode)
  • Alarm activated

3. Quick-Start Configuration

Within 30 seconds of startup, follow the button instructions for
quick-start configuration.

FAQ (Frequently Asked Questions)

Q: How do I reset the factory settings?

A: Press and hold down on startup to reset the factory settings
with ‘FAC’ displayed.

Q: What does the blinking compressor icon indicate?

A: The blinking compressor icon indicates pull-down mode.

Q: How do I activate the alarm?

A: The alarm is activated automatically when triggered by
specific conditions.

“`

520H11068

520H11068

Installation guide
ERC 214 Digital regulator for refrigeration and defrosting, 4 relays.
The ERC 214 is a smart, multipurpose integrated refrigeration controller with temperature and defrost management, available with 4 relays. This controller is for Operating temperature sensing control, suitable for refrigeration and heating applications. Incorporated control has been designed to fulfil today’s requirements for commercial refrigeration applications.

Danfoss 80G8101.01

Dimensions (mm)
83
Assembly

36

61.2 66
Rear mount (clip fixing)

28

71 29
Drilling template

Danfoss 80G8102.01

Assembly

Removal

Danfoss 80G8103.02

Wiring diagram
Sair S5 DO1

DI1 DI2 DO4
DO1 DO2 DO3
Sc DO2 DO3 DO4

12

3L 4N 5 6 7

~~

~~

Electrical input

(on the basis of product code)

Quick programming tool: EKA 183B

GND

GND

8 9 10 11 12 13 14

Sair

S5 Sc/DI1

DI2

Connectors: Max. Torque = 0.4 Nm

© Copyright Danfoss | Published by ADAP-KOOL | 2018.10

Installation guide | ERC 214

DKRCE.PI.RL0.N4.02 | 1

Installation guide – ERC 214

1 – Technical features
· Easy to use: the four buttons, the easy-to-read menu structure and the preinstalled application solutions guarantee optimal usability.
· Simple installation: the 16 A relay means heavy loads can be connected directly without having to use an intermediate relay: compressors up to 2 HP on the basis of the power factor and efficiency of the motor (over 0.65 at 230 V and over 0.85 at 115 V). A vast range of compatible sensor types and screw terminals guarantee highly flexible installation.
· Unit protection: special software functions, protecting the compressor from voltage fluctuations or high condensation temperature, to guarantee optimal unit performance.
· Energy efficiency: defrosting on request, day/night mode and intelligent evaporator fan management guarantee maximum energy efficiency.

2 – User interface
Button function

Press and hold down on startup RESET FACTORY SETTINGS (“FAC” is displayed)

Press for one second: BACK Press and hold down: PULL-DOWN

Press for one second: TEMPERATURE SETPOINT/OK Press and hold down: MENU

Display icons

Night mode (energy saving)

Fan on

Compressor on Blinks in pull-down mode

Alarm activated

Press for one second: UP Press and hold down: ON/OFF Press for one second: DOWN Press and hold down: DEFROSTING
Defrosting
Units (°C or °F)

3 – Quick-start configuration

· STEP 1: Startup · STEP 2: Select quick-start configuration menu
Within 30 seconds of startup, press “<” BACK for 3 seconds. The main switch “r12” is automatically set to OFF. · STEP 3: Select the preinstalled application “o61” The display automatically shows the application selection parameter “o61”. Press SET to select the preinstalled application. The display shows the default value (for example “AP0”, blinking). Select the type of application by pressing UP/DOWN and then SET to confirm. The regulator presets the parameter values on the basis of the application selected and hides any irrelevant parameters. Tip: you can easily switch from AP0 to AP6 and therefore select the simplified parameters list by pressing the UP button (circular list).

App

Description

App 0

None (no preset application)

App 1

Medium temperature ventilated ref. units (2 ­ 6 °C), with timed natural defrosting

App 2

Medium temperature ventilated ref. units (0 ­ 4 °C), with timed electric defrosting

App 3

Low temperature ventilated ref. units (-26 ­ -20 °C), with timed electric defrosting

App 4

Medium temperature ventilated ref. units (0 ­ 4 °C), with timed electric defrosting (on the basis of the temperature)

App 5

Low temperature ventilated ref. units (-26 ­ -20 °C), with timed electric defrosting (on the basis of the temperature)

App 6

None (no preset application) with simplified parameters list

· STEP 4: Select the sensor type “o06” The display automatically shows the sensor selection parameter “o06”. Press SET to select the type of sensor. The display shows the default value (for example “n10”, blinking). Select the type of sensor by pressing UP/DOWN (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000) then SET to confirm. NOTE: all the sensors must by the same type.
· STEP 5: Configure output DO4 “o36” The display automatically shows the parameter “o36” to configure the output “DO4”. Select light (“Lig”) or alarm (“ALA”) on the basis of the application and press SET to confirm. The display is reset in normal display mode with the control on.

© Copyright Danfoss | Published by ADAP-KOOL | 2018.10

Installation guide | ERC 214

DKRCE.PI.RL0.N4.02 | 2

Danfoss 80G114.01

Installation guide – ERC 214

4 – Menu structure
SET: press for 3 seconds for state, settings and service 1) Parameters group
Password (if enabled)

Input states Configuration

2) Parameter names SET
Main switch

Application

3) Value
Application 1-2-3-4-5-6 SET Application 0

Sensor type
To scroll the parameter names DO4 configuration

Application 6-5-4-3-2-1

To scroll the parameter groups

5 – Quick configuration with “cFg” menu
· Press SET for three seconds to open the parameter groups. · Select the “cFg” menu and press SET to open. The first menu “r12” (main switch) is displayed. · Set the main switch to OFF (r12=0) to change the preinstalled application. · Press UP/DOWN to scroll through the parameters list. · Configure the parameter “o61” to select a preinstalled application:
– Press SET to open the parameter “o61”. – Press UP/DOWN to select an application (AP0= no application). – Press SET to confirm; “o61” is displayed. · Continue to set the following parameters (sensor type “o06” and configuration “O36” DO4) in the “cFg” menu.

© Copyright Danfoss | Published by ADAP-KOOL | 2018.10

Installation guide | ERC 214

DKRCE.PI.RL0.N4.02 | 3

Installation guide – ERC 214

Danfoss 80G115.01

6 – Basic functions
Adjusting the setpoint temperature (short press) SET: adjust the setpoint temperature.
UP/DOWN: change the temperature setpoint (in setting mode the setpoint flashes).

SET: saves the temperature setpoint.
Initiate a manual defrost DEFROST: press for 3 seconds to initiate a defsost.
DEFROST: press for 3 seconds to stop manual defrost. The DEFROST icon is shown during defrost.
Initiate a pull down PULL DOWN: press for 3 seconds to initiate pull down.

“Pud”: is shown for 3 seconds to indicate pull down. The PULL DOWN icon flashes during pull down. PULL DOWN: press for 3 seconds to stop pull down.
View an active alarm
Temperature and alarm codes alternate flashes until the alarm is resolved. The alarm bell is shown.
Unlock keyboard – After 5 minutes of inactivity, the keypad will be locked (if P76 = YES). – When the keypad is locked, if any key is selected, “LoC” appears on the display. – Press UP and DOWN buttons simultaneously for 3 seconds to unlock the keyboard. “unl” is displayed for 3 seconds.
7 – Default application settings

App Mode Description

Temp. Def. type Def. end

App 0 Cooling None (no preset application)

App 1 Cooling Medium temperature ventilated refrigeration units with timed natural defrost (2 ­ 6 °C) Natural

Time

App 2 Cooling Medium temperature ventilated refrigeration units with timed electrical defrost (0 ­ 4 °C) Electrical Time

App 3 Cooling Low temperature ventilated refrigeration units with timed electrical defrost (-26 ­ -20 °C) Electrical Time

App 4

Cooling

Medium temperature (by temperature)

ventilated

refrigeration

units

with

electrical

defrost

(0 ­ 4 °C) Electrical Temperature

App 5

Cooling

Low temperature (by temperature)

ventilated

refrigeration

units

with

electrical

defrost

(-26 ­ -20 °C) Electrical Temperature

App 6 Cooling None (no preset application) with simplified parameter list

APP 1 DI1 DI2 Sair

APP 2/3 DI1 DI2 Sair

APP 4/5 DI1 DI2 S5 Sair

Danfoss 80G116.01

230 V AC

DO1 DO3 DO4

230 V AC

DO1 DO2 DO3 DO4

230 V AC

DO1 DO2 DO3 DO4

© Copyright Danfoss | Published by ADAP-KOOL | 2018.10

Installation guide | ERC 214

DKRCE.PI.RL0.N4.02 | 4

Installation guide – ERC 214

8 – Technical Data
FEATURES Purpose of control Construction of control Power supply Rated power Inputs
Types of sensors allowed Sensors in “Kit Solution”
Precision
Type of action
Output
Display Operating Conditions Storage conditions Protection Environmental data Overvoltage category Heat and fire resistant EMC category
Certifications

DESCRIPTION Operating temperature sensing control suitable for incorporation into commercial airconditioning and refrigeration applications Incorporated control Low voltage, regulated, galvanically isolated, 115 V AC or 230 V AC, 50/60 Hz input
Less than 0.7 W
Sensor inputs, Digital inputs, Programming key Connected to SELV limited energy <15 W
NTC 5000 Ohms at 25 °C (beta = 3,980 at 25/100 °C – EKS 211 for example) NTC 10000 Ohms at 25 °C (beta = 3,435 at 25/85 °C – EKS 221 for example) PTC 990 Ohms at 25 °C (EKS 111 for example) Pt1000 (AKS 11, AKS 12, AKS 21 for example)
NTC 10000 Ohms at 25 °C, 1.5 m cable
Measuring range: -40 ­ 105 °C (-40 ­ 221 °F)
Regulator precision: +/-1 K below -35 °C, +/-0.5 K between -35 ­ 25 °C, +/-1 K above 25 °C
1B (relay)
Compressor relay DO1: 16 A, 16 (16) A, EN 60730-1 10 FLA / 60 LRA at 230 V, UL60730-1 16 FLA / 72 LRA at 115 V, UL60730-1
Defrosting relay DO2: 8 A, 2 FLA / 12 LRA, UL60730-1 8 A, 2 (2 A), EN60730-1
Fan relay DO3: 3 A, 2 FLA / 12 LRA, UL60730-1 3 A, 2 (2 A), EN60730-1
Alarm / light relay DO4: 2:00 AM
LED 3-figure display, decimal point and multifunction icons, °C + °F scale
-10 ­ 55 °C (14 ­ 131 °F), 90% Rh
-40 ­ 70 °C (-40 ­ 158 °F), 90% Rh
Front: IP65 (with seal) Rear: IP00
Pollution degree II, condensate free
II – 230 V supply version – (ENEC, UL recognized) III – 115 V supply version – (UL recognized)
Category D (UL94-V0) Temperature for ball pressure test statement “According to Annex G” (EN 60730-1)
Category I
UL acknowledgement (USA and Canada) (UL 60730-1) ENEC (EN 60730-1) CQC EC (LVD and EMC Directives) EAC (GHOST) NSF ROHS2.0 HACCP temperature monitoring in compliance with EN134785 Class I if used with sensor AKS 12

© Copyright Danfoss | Published by ADAP-KOOL | 2018.10

Installation guide | ERC 214

DKRCE.PI.RL0.N4.02 | 5

Installation guide – ERC 214

9 – Parameters

Parameter name – ERC 214

Code

Configuration

cFg

Main switch -1=service, 0=OFF, 1=ON

r12

Predefined applications AP0, AP1, AP2, AP3, AP4, AP5, AP6

o61

Sensor type selection

n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, o06

Pt1=Pt1000

DO4 configuration Lig=light, ALA=alarm

o36

Reference / thermostat

r–

Temperature setpoint

r00

Differential

r01

Min set point limitation

r02

Max set point limitation

r03

Offset display

(temperature correction shown on

r04

display)

Display units (°C / °F)

r05

Sair calibration (offset for air temperature calibration)

r09

Main switch -1=service, 0=OFF, 1=ON

r12

Night setback

(offset temperature during night

r13

mode)

Thermostat reference displacement (temperature offset)

r40

Pull-down duration

r96

Pull-down temperature limit

r97

Alarm

A–

Delay for temperature alarm during normal conditions

A03

Temperature alarm delay

pull-down / startup / defrosting

A12

duration

High temperature alarm limit (Cabinet / Ambient)

A13

Low temperature alarm limit

A14

DI1 delay (delay for selected function DI1)

A27

DI2 delay (delay for selected function DI2)

A28

Condenser high alarm limit

A37

Condenser high block limit

A54

Voltage protection enable

A72

Minimum cut-in voltage

A73

Minimum cut-out voltage

A74

Maximum voltage

A75

Defrost

d–

Defrosting method

no=no defrost, nAt=natural,

d01

EL=electric, gAS=hot gas

Defrost stop temperature

d02

Defrost interval

d03

N.B.: hidden parameters are greyed out

Min.
-1 AP0
n5
Lig
-100 0.1 -100 -100 -10 -C -20 -1
-50
-50 0 -100
0
0
-100 -100
0 0 0 0 no 0 0 0
no 0 0

Max.
1 AP6
Pt1
ALA
200 20 200 200 10 -F 20 1
50
50 960 200
240
240
200 200 240 240 200 200 yes 270 270 270
gAS 50 240

Unit

App. 0 (Def.)

App. 1

App. 2

App. 3

App. 4

App. 5

App. 6

1

1

1

1

1

1

1

AP0 AP1 AP2 AP3 AP4 AP5 AP6

n10 n10 n10 n10 n10 n10 n10

Lig Lig Lig Lig Lig Lig Lig

C/F 2

4

K

2

2

C/F -35 2

C/F 50

6

2

-24

2

-24

2

2

2

2

2

2

0

-26

0

-26 -35

4

-20

4

-20 50

K

0

0

0

0

0

0

0

-C

-C

-C

-C

-C

-C

-C

K

0

0

0

0

0

0

1

1

1

1

1

1

K

0

0

0

0

0

0

0

K

0

0

0

0

0

0

min. 0

0

0

0

0

0

C/F 0

0

0

0

0

0

min 30 45 30 30 30 30 30

min 60 90 60 60 60 60 60

C/F 8

10

8

-15

8

-15

8

C/F -30 0

-2 -30 -2 -30 -30

min 30 30 30 30 30 30 30

min 30 30 30 30 30 30 30

C/F 80 80 80 80 80 80

C/F 85 85 85 85 85 85

no no no no no no no

V

0

0

0

0

0

0

0

V

0

0

0

0

0

0

0

V 270 270 270 270 270 270 270

EL nAt EL

EL

EL

EL

EL

C/F 6

6

6

6

hours 8

6

8

12

8

12

8

© Copyright Danfoss | Published by ADAP-KOOL | 2018.10

Installation guide | ERC 214

DKRCE.PI.RL0.N4.02 | 6

Installation guide – ERC 214

Parameter name – ERC 214

Code

Max. defrost time

d04

Defrost delay at power up (or DI signal)

d05

Drip delay

d06

Fan delay after defrost

d07

Fan start temperature after defrost d08

Fan during defrost

d09

Defrost stop sensor non=timed, Air=Sair (air temperature), d10 dEF=S5 (defrost sensor)

Compressor accumulated

runtime to start defrost

d18

0=OFF

Defrost on demand 20.0=OFF

d19

Defrost delay after pull-down 0=OFF

d30

Fan control

F–

Fan at compressor cutout

FFc=fan follow compressor, FAo=fan always ON,

F01

FPL= fan pulsation

Fan stop evaporator temperature 50.0=OFF

F04

Fan cycle ON

F07

Fan cycle OFF

F08

Compressor

c–

Compressor minimum ON time

C01

Compressor minimum OFF time

C02

Compressor OFF delay with door open

C04

Zero crossing selection

C70

Others

o–

Delay of outputs at startup

o01

DI1 configuration

oFF=not used,

Sdc=status display output,

doo=door alarm with resumption,

doA=door alarm without resumption,

SCH = main switch, nig=day / night mode,

o02

rFd=reference displacement,

EAL=external alarm,

dEF=defrost,

Pud=pull-down,

Sc=condenser sensor

Serial address

o03

Password

o05

Select sensor type

n5=NTC 5 K, n10=NTC 10 K,

o06

Ptc=PTC, Pt1=Pt1000

Display resolution

0.1=steps of 0.1 °C, 0.5=steps of 0.5 °C,

o15

1.0=steps of 1.0 °C

Relay 1 counter (1 count = 100 operating cycles)

o23

N.B.: hidden parameters are greyed out

Min. 0 0 0 0 -50 oFF
non
0 0 0
FFc
-50 0 0 0 0 0 no 0
oFF
0 no n5
0.1
0

Max. 480 240.0 60 60 0 on dEF
96 20 960
FPL
50 15 15 30 30 15 yes 600
Sc
247 999 Pt1
1
999

Unit

App. 0 (Def.)

App. 1

App. 2

App. 3

App. 4

App. 5

App. 6

min 30 45 15 15 30 30 30

min 0

0

0

0

0

0

min 0

0

0

0

0

0

5

min 0

0

0

0

0

0

5

C/F -5

-5

-5

on on on on on on on

non non non non dEF dEF non

hours 0

0

0

0

0

0

K

20

20 20

min 0

0

0

0

0

0

FAo FAo FAo FAo FAo FAo FAo

C/F 50

50 50

min 2

2

2

2

2

2

2

min 2

2

2

2

2

2

2

min 0

0

0

0

0

0

0

min 2

2

2

2

2

2

2

min 0

0

0

0

0

0

1

yes yes yes yes yes yes yes

min 5

5

5

5

5

5

5

oFF oFF oFF oFF oFF oFF oFF

0

0

0

0

0

0

no no no no no no

0

n10 n10 n10 n10 n10 n10 –

0.1 0.1 0.1 0.1 0.1 0.1 0.1

0

0

0

0

0

0

© Copyright Danfoss | Published by ADAP-KOOL | 2018.10

Installation guide | ERC 214

DKRCE.PI.RL0.N4.02 | 7

Installation guide – ERC 214

Parameter name – ERC 214

Code

Relay 2 counter (1 count = 100 operating cycles)

o24

Relay 3 counter (1 count = 100 operating cycles)

o25

Relay 4 counter (1 count = 100 operating cycles)

o26

DO4 configuration ALA=alarm, Lig=light

o36

DI2 configuration

oFF=not used, Sdc=status display output,

doo=door alarm with resumption,

doA=door alarm without resumption, SCH=main switch, nig=day / night mode,

o37

rFd=reference displacement,

EAL=external alarm, dEF=defrost,

Pud=pull-down

Lights control

on=always on, dAn=day / night,

o38

doo=on basis of door action

Predefined applications

o61

Save settings as default WARNING: previous default settings o67 will be overwritten

Display at defrost

Air=effective air temperature, FrE=freezing temperature,

o91

-d-=”-d-” is displayed

Polarity

P–

DI1 input polarity

nc=normally closed,

P73

no=normally open

DI2 input polarity

nc=normally closed,

P74

no=normally open

Invert alarm relay 0=normal, 1=relay action inversion

P75

Keyboard lock enable

P76

Readouts

u–

Controller status

S0=cooling ON/Heating ON,

S2=wait for compressor ON time to elapse,

S3=wait for compressor OFF time to

elapse-restart time, S4=drip OFF

delay after defrost, S10=cooling stop,

S11=cooling stopped by thermostat / heating OFF, S14=defrosting state,

u00

S15=fan delay state after defrost,

S17=door open (DI input),

S20=emergency cooling, S25=manual

control of outputs, S30=continous

cycle/Pull-down, S32=delay of outputs

at power up

Air temperature (Sair)

U01

Read the present regulation reference

u02

Defrost temperature (S5)

u09

N.B.: hidden parameters are greyed out

Min. 0 0 0
ALA
oFF
on AP0 no Air
nc nc 0 no
S0
-100 -100 -100

Max. 999 999 999 Lig
Pud
doo AP6 yes -d-
no no 1 yes
S32
200 200 200

Unit

App. 0 (Def.)

App. 1

App. 2

App. 3

App. 4

App. 5

App. 6

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Lig Lig Lig Lig Lig Lig

oFF oFF oFF oFF oFF oFF oFF

on on on on on on on

AP0 AP1 AP2 AP3 AP4 AP5

no no no no no no

-d- -d- -d- -d- -d- -d- -d-

no no no no no no no

no no no no no no no

0

0

0

0

0

0

no no no no no no

C/F —

C/F —

C/F —

© Copyright Danfoss | Published by ADAP-KOOL | 2018.10

Installation guide | ERC 214

DKRCE.PI.RL0.N4.02 | 8

Installation guide – ERC 214

Parameter name – ERC 214

Code

DI1 input

u10

Status of night operation

u13

DI2 input

u37

Condenser temperature (Sc)

U09

Compressor relay status

u58

Fan relay status

u59

Defrost relay status

u60

Alarm relay status

u62

Light relay status

u63

Firmware version readout

u80

Alarm status

Sair air temperature sensor error

E29

S5 defrost sensor error

E27

Sc condenser sensor error

E30

High temperature alarm

A01

Low temperature alarm

A02

High voltage alarm

A99

Low voltage alarm

AA1

Condenser alarm

A61

Door alarm

A04

Standby alarm

A45

DI external alarm

A15

N.B.: hidden parameters are greyed out

Min.
oFF oFF oFF -100 oFF oFF oFF oFF oFF 0

Max.
on on on 200 on on on on on 999

Unit

App. 0 (Def.)

App. 1

App. 2

App. 3

App. 4

App. 5

App. 6

C/F —

Safety standards
Check the input voltage is correct before connecting the instrument. Do not expose to water or damp: only use the regulator within the design operating limits, avoiding sudden temperature changes with high atmospheric humidity to prevent condensate forming.
Product disposal
The device (or product) must be disposed of in compliance with local waste disposal legislation.
EU design registration
002566703-0001

Contact info.: www.danfoss.com/erc

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice.This also applies to products

already on order provided that such alterations can be made without subsequential changes being necessary

eady agreed.

All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

© Copyright Danfoss | Published by ADAP-KOOL | 2018.10

Installation guide | ERC 214

DKRCE.PI.RL0.N4.02 | 9

Documents / Resources

Danfoss ERC 214 Digital Regulator [pdf] Installation Guide
80G8101.01, 80G8102.01, 80G8103.02, ERC 214 Digital Regulator, ERC 214, Digital Regulator, Regulator

References

Leave a comment

Your email address will not be published. Required fields are marked *