ERC 214 Digital Regulator
“
Product Information
Specifications
- Model: ERC 214
- Function: Digital regulator for refrigeration and
defrosting - Relays: 4
- Temperature Sensing: Operating temperature control
- Applications: Suitable for refrigeration and heating
Product Usage Instructions
1. Installation
Follow the provided dimensions and assembly instructions for
proper installation of the ERC 214 controller.
2. User Interface
Button Functions:
- Press and hold down on startup: RESET FACTORY SETTINGS (FAC is
displayed) - Press for one second: BACK
- Press and hold down: PULL-DOWN
- Press for one second: TEMPERATURE SETPOINT/OK
- Press and hold down: MENU
- Press for one second: UP
- Press and hold down: ON/OFF
- Press for one second: DOWN
- Press and hold down: DEFROSTING
Display Icons:
- Night mode (energy saving)
- Fan on
- Compressor on (Blinks in pull-down mode)
- Alarm activated
3. Quick-Start Configuration
Within 30 seconds of startup, follow the button instructions for
quick-start configuration.
FAQ (Frequently Asked Questions)
Q: How do I reset the factory settings?
A: Press and hold down on startup to reset the factory settings
with ‘FAC’ displayed.
Q: What does the blinking compressor icon indicate?
A: The blinking compressor icon indicates pull-down mode.
Q: How do I activate the alarm?
A: The alarm is activated automatically when triggered by
specific conditions.
“`
520H11068
520H11068
Installation guide
ERC 214 Digital regulator for refrigeration and defrosting, 4 relays.
The ERC 214 is a smart, multipurpose integrated refrigeration controller with temperature and defrost management, available with 4 relays. This controller is for Operating temperature sensing control, suitable for refrigeration and heating applications. Incorporated control has been designed to fulfil today’s requirements for commercial refrigeration applications.
Danfoss 80G8101.01
Dimensions (mm)
83
Assembly
36
61.2 66
Rear mount (clip fixing)
28
71 29
Drilling template
Danfoss 80G8102.01
Assembly
Removal
Danfoss 80G8103.02
Wiring diagram
Sair S5 DO1
DI1 DI2 DO4
DO1 DO2 DO3
Sc DO2 DO3 DO4
12
3L 4N 5 6 7
~~
~~
Electrical input
(on the basis of product code)
Quick programming tool: EKA 183B
GND
GND
8 9 10 11 12 13 14
Sair
S5 Sc/DI1
DI2
Connectors: Max. Torque = 0.4 Nm
© Copyright Danfoss | Published by ADAP-KOOL | 2018.10
Installation guide | ERC 214
DKRCE.PI.RL0.N4.02 | 1
Installation guide – ERC 214
1 – Technical features
· Easy to use: the four buttons, the easy-to-read menu structure and the preinstalled application solutions guarantee optimal usability.
· Simple installation: the 16 A relay means heavy loads can be connected directly without having to use an intermediate relay: compressors up to 2 HP on the basis of the power factor and efficiency of the motor (over 0.65 at 230 V and over 0.85 at 115 V). A vast range of compatible sensor types and screw terminals guarantee highly flexible installation.
· Unit protection: special software functions, protecting the compressor from voltage fluctuations or high condensation temperature, to guarantee optimal unit performance.
· Energy efficiency: defrosting on request, day/night mode and intelligent evaporator fan management guarantee maximum energy efficiency.
2 – User interface
Button function
Press and hold down on startup RESET FACTORY SETTINGS (“FAC” is displayed)
Press for one second: BACK Press and hold down: PULL-DOWN
Press for one second: TEMPERATURE SETPOINT/OK Press and hold down: MENU
Display icons
Night mode (energy saving)
Fan on
Compressor on Blinks in pull-down mode
Alarm activated
Press for one second: UP Press and hold down: ON/OFF Press for one second: DOWN Press and hold down: DEFROSTING
Defrosting
Units (°C or °F)
3 – Quick-start configuration
· STEP 1: Startup · STEP 2: Select quick-start configuration menu
Within 30 seconds of startup, press “<” BACK for 3 seconds. The main switch “r12” is automatically set to OFF. · STEP 3: Select the preinstalled application “o61” The display automatically shows the application selection parameter “o61”. Press SET to select the preinstalled application. The display shows the default value (for example “AP0”, blinking). Select the type of application by pressing UP/DOWN and then SET to confirm. The regulator presets the parameter values on the basis of the application selected and hides any irrelevant parameters. Tip: you can easily switch from AP0 to AP6 and therefore select the simplified parameters list by pressing the UP button (circular list).
App
Description
App 0
None (no preset application)
App 1
Medium temperature ventilated ref. units (2 6 °C), with timed natural defrosting
App 2
Medium temperature ventilated ref. units (0 4 °C), with timed electric defrosting
App 3
Low temperature ventilated ref. units (-26 -20 °C), with timed electric defrosting
App 4
Medium temperature ventilated ref. units (0 4 °C), with timed electric defrosting (on the basis of the temperature)
App 5
Low temperature ventilated ref. units (-26 -20 °C), with timed electric defrosting (on the basis of the temperature)
App 6
None (no preset application) with simplified parameters list
· STEP 4: Select the sensor type “o06” The display automatically shows the sensor selection parameter “o06”. Press SET to select the type of sensor. The display shows the default value (for example “n10”, blinking). Select the type of sensor by pressing UP/DOWN (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000) then SET to confirm. NOTE: all the sensors must by the same type.
· STEP 5: Configure output DO4 “o36” The display automatically shows the parameter “o36” to configure the output “DO4”. Select light (“Lig”) or alarm (“ALA”) on the basis of the application and press SET to confirm. The display is reset in normal display mode with the control on.
© Copyright Danfoss | Published by ADAP-KOOL | 2018.10
Installation guide | ERC 214
DKRCE.PI.RL0.N4.02 | 2
Danfoss 80G114.01
Installation guide – ERC 214
4 – Menu structure
SET: press for 3 seconds for state, settings and service 1) Parameters group
Password (if enabled)
Input states Configuration
2) Parameter names SET
Main switch
Application
3) Value
Application 1-2-3-4-5-6 SET Application 0
Sensor type
To scroll the parameter names DO4 configuration
Application 6-5-4-3-2-1
To scroll the parameter groups
5 – Quick configuration with “cFg” menu
· Press SET for three seconds to open the parameter groups. · Select the “cFg” menu and press SET to open. The first menu “r12” (main switch) is displayed. · Set the main switch to OFF (r12=0) to change the preinstalled application. · Press UP/DOWN to scroll through the parameters list. · Configure the parameter “o61” to select a preinstalled application:
– Press SET to open the parameter “o61”. – Press UP/DOWN to select an application (AP0= no application). – Press SET to confirm; “o61” is displayed. · Continue to set the following parameters (sensor type “o06” and configuration “O36” DO4) in the “cFg” menu.
© Copyright Danfoss | Published by ADAP-KOOL | 2018.10
Installation guide | ERC 214
DKRCE.PI.RL0.N4.02 | 3
Installation guide – ERC 214
Danfoss 80G115.01
6 – Basic functions
Adjusting the setpoint temperature (short press) SET: adjust the setpoint temperature.
UP/DOWN: change the temperature setpoint (in setting mode the setpoint flashes).
SET: saves the temperature setpoint.
Initiate a manual defrost DEFROST: press for 3 seconds to initiate a defsost.
DEFROST: press for 3 seconds to stop manual defrost. The DEFROST icon is shown during defrost.
Initiate a pull down PULL DOWN: press for 3 seconds to initiate pull down.
“Pud”: is shown for 3 seconds to indicate pull down. The PULL DOWN icon flashes during pull down. PULL DOWN: press for 3 seconds to stop pull down.
View an active alarm
Temperature and alarm codes alternate flashes until the alarm is resolved. The alarm bell is shown.
Unlock keyboard – After 5 minutes of inactivity, the keypad will be locked (if P76 = YES). – When the keypad is locked, if any key is selected, “LoC” appears on the display. – Press UP and DOWN buttons simultaneously for 3 seconds to unlock the keyboard. “unl” is displayed for 3 seconds.
7 – Default application settings
App Mode Description
Temp. Def. type Def. end
App 0 Cooling None (no preset application)
App 1 Cooling Medium temperature ventilated refrigeration units with timed natural defrost (2 6 °C) Natural
Time
App 2 Cooling Medium temperature ventilated refrigeration units with timed electrical defrost (0 4 °C) Electrical Time
App 3 Cooling Low temperature ventilated refrigeration units with timed electrical defrost (-26 -20 °C) Electrical Time
App 4
Cooling
Medium temperature (by temperature)
ventilated
refrigeration
units
with
electrical
defrost
(0 4 °C) Electrical Temperature
App 5
Cooling
Low temperature (by temperature)
ventilated
refrigeration
units
with
electrical
defrost
(-26 -20 °C) Electrical Temperature
App 6 Cooling None (no preset application) with simplified parameter list
APP 1 DI1 DI2 Sair
APP 2/3 DI1 DI2 Sair
APP 4/5 DI1 DI2 S5 Sair
Danfoss 80G116.01
230 V AC
DO1 DO3 DO4
230 V AC
DO1 DO2 DO3 DO4
230 V AC
DO1 DO2 DO3 DO4
© Copyright Danfoss | Published by ADAP-KOOL | 2018.10
Installation guide | ERC 214
DKRCE.PI.RL0.N4.02 | 4
Installation guide – ERC 214
8 – Technical Data
FEATURES Purpose of control Construction of control Power supply Rated power Inputs
Types of sensors allowed Sensors in “Kit Solution”
Precision
Type of action
Output
Display Operating Conditions Storage conditions Protection Environmental data Overvoltage category Heat and fire resistant EMC category
Certifications
DESCRIPTION Operating temperature sensing control suitable for incorporation into commercial airconditioning and refrigeration applications Incorporated control Low voltage, regulated, galvanically isolated, 115 V AC or 230 V AC, 50/60 Hz input
Less than 0.7 W
Sensor inputs, Digital inputs, Programming key Connected to SELV limited energy <15 W
NTC 5000 Ohms at 25 °C (beta = 3,980 at 25/100 °C – EKS 211 for example) NTC 10000 Ohms at 25 °C (beta = 3,435 at 25/85 °C – EKS 221 for example) PTC 990 Ohms at 25 °C (EKS 111 for example) Pt1000 (AKS 11, AKS 12, AKS 21 for example)
NTC 10000 Ohms at 25 °C, 1.5 m cable
Measuring range: -40 105 °C (-40 221 °F)
Regulator precision: +/-1 K below -35 °C, +/-0.5 K between -35 25 °C, +/-1 K above 25 °C
1B (relay)
Compressor relay DO1: 16 A, 16 (16) A, EN 60730-1 10 FLA / 60 LRA at 230 V, UL60730-1 16 FLA / 72 LRA at 115 V, UL60730-1
Defrosting relay DO2: 8 A, 2 FLA / 12 LRA, UL60730-1 8 A, 2 (2 A), EN60730-1
Fan relay DO3: 3 A, 2 FLA / 12 LRA, UL60730-1 3 A, 2 (2 A), EN60730-1
Alarm / light relay DO4: 2:00 AM
LED 3-figure display, decimal point and multifunction icons, °C + °F scale
-10 55 °C (14 131 °F), 90% Rh
-40 70 °C (-40 158 °F), 90% Rh
Front: IP65 (with seal) Rear: IP00
Pollution degree II, condensate free
II – 230 V supply version – (ENEC, UL recognized) III – 115 V supply version – (UL recognized)
Category D (UL94-V0) Temperature for ball pressure test statement “According to Annex G” (EN 60730-1)
Category I
UL acknowledgement (USA and Canada) (UL 60730-1) ENEC (EN 60730-1) CQC EC (LVD and EMC Directives) EAC (GHOST) NSF ROHS2.0 HACCP temperature monitoring in compliance with EN134785 Class I if used with sensor AKS 12
© Copyright Danfoss | Published by ADAP-KOOL | 2018.10
Installation guide | ERC 214
DKRCE.PI.RL0.N4.02 | 5
Installation guide – ERC 214
9 – Parameters
Parameter name – ERC 214
Code
Configuration
cFg
Main switch -1=service, 0=OFF, 1=ON
r12
Predefined applications AP0, AP1, AP2, AP3, AP4, AP5, AP6
o61
Sensor type selection
n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, o06
Pt1=Pt1000
DO4 configuration Lig=light, ALA=alarm
o36
Reference / thermostat
r–
Temperature setpoint
r00
Differential
r01
Min set point limitation
r02
Max set point limitation
r03
Offset display
(temperature correction shown on
r04
display)
Display units (°C / °F)
r05
Sair calibration (offset for air temperature calibration)
r09
Main switch -1=service, 0=OFF, 1=ON
r12
Night setback
(offset temperature during night
r13
mode)
Thermostat reference displacement (temperature offset)
r40
Pull-down duration
r96
Pull-down temperature limit
r97
Alarm
A–
Delay for temperature alarm during normal conditions
A03
Temperature alarm delay
pull-down / startup / defrosting
A12
duration
High temperature alarm limit (Cabinet / Ambient)
A13
Low temperature alarm limit
A14
DI1 delay (delay for selected function DI1)
A27
DI2 delay (delay for selected function DI2)
A28
Condenser high alarm limit
A37
Condenser high block limit
A54
Voltage protection enable
A72
Minimum cut-in voltage
A73
Minimum cut-out voltage
A74
Maximum voltage
A75
Defrost
d–
Defrosting method
no=no defrost, nAt=natural,
d01
EL=electric, gAS=hot gas
Defrost stop temperature
d02
Defrost interval
d03
N.B.: hidden parameters are greyed out
Min.
-1 AP0
n5
Lig
-100 0.1 -100 -100 -10 -C -20 -1
-50
-50 0 -100
0
0
-100 -100
0 0 0 0 no 0 0 0
no 0 0
Max.
1 AP6
Pt1
ALA
200 20 200 200 10 -F 20 1
50
50 960 200
240
240
200 200 240 240 200 200 yes 270 270 270
gAS 50 240
Unit
App. 0 (Def.)
App. 1
App. 2
App. 3
App. 4
App. 5
App. 6
1
1
1
1
1
1
1
AP0 AP1 AP2 AP3 AP4 AP5 AP6
n10 n10 n10 n10 n10 n10 n10
Lig Lig Lig Lig Lig Lig Lig
C/F 2
4
K
2
2
C/F -35 2
C/F 50
6
2
-24
2
-24
2
2
2
2
2
2
0
-26
0
-26 -35
4
-20
4
-20 50
K
0
0
0
0
0
0
0
-C
-C
-C
-C
-C
-C
-C
K
0
0
0
0
0
0
–
1
1
1
1
1
1
–
K
0
0
0
0
0
0
0
K
0
0
0
0
0
0
–
min. 0
0
0
0
0
0
–
C/F 0
0
0
0
0
0
–
min 30 45 30 30 30 30 30
min 60 90 60 60 60 60 60
C/F 8
10
8
-15
8
-15
8
C/F -30 0
-2 -30 -2 -30 -30
min 30 30 30 30 30 30 30
min 30 30 30 30 30 30 30
C/F 80 80 80 80 80 80
–
C/F 85 85 85 85 85 85
–
no no no no no no no
V
0
0
0
0
0
0
0
V
0
0
0
0
0
0
0
V 270 270 270 270 270 270 270
EL nAt EL
EL
EL
EL
EL
C/F 6
–
–
–
6
6
6
hours 8
6
8
12
8
12
8
© Copyright Danfoss | Published by ADAP-KOOL | 2018.10
Installation guide | ERC 214
DKRCE.PI.RL0.N4.02 | 6
Installation guide – ERC 214
Parameter name – ERC 214
Code
Max. defrost time
d04
Defrost delay at power up (or DI signal)
d05
Drip delay
d06
Fan delay after defrost
d07
Fan start temperature after defrost d08
Fan during defrost
d09
Defrost stop sensor non=timed, Air=Sair (air temperature), d10 dEF=S5 (defrost sensor)
Compressor accumulated
runtime to start defrost
d18
0=OFF
Defrost on demand 20.0=OFF
d19
Defrost delay after pull-down 0=OFF
d30
Fan control
F–
Fan at compressor cutout
FFc=fan follow compressor, FAo=fan always ON,
F01
FPL= fan pulsation
Fan stop evaporator temperature 50.0=OFF
F04
Fan cycle ON
F07
Fan cycle OFF
F08
Compressor
c–
Compressor minimum ON time
C01
Compressor minimum OFF time
C02
Compressor OFF delay with door open
C04
Zero crossing selection
C70
Others
o–
Delay of outputs at startup
o01
DI1 configuration
oFF=not used,
Sdc=status display output,
doo=door alarm with resumption,
doA=door alarm without resumption,
SCH = main switch, nig=day / night mode,
o02
rFd=reference displacement,
EAL=external alarm,
dEF=defrost,
Pud=pull-down,
Sc=condenser sensor
Serial address
o03
Password
o05
Select sensor type
n5=NTC 5 K, n10=NTC 10 K,
o06
Ptc=PTC, Pt1=Pt1000
Display resolution
0.1=steps of 0.1 °C, 0.5=steps of 0.5 °C,
o15
1.0=steps of 1.0 °C
Relay 1 counter (1 count = 100 operating cycles)
o23
N.B.: hidden parameters are greyed out
Min. 0 0 0 0 -50 oFF
non
0 0 0
FFc
-50 0 0 0 0 0 no 0
oFF
0 no n5
0.1
0
Max. 480 240.0 60 60 0 on dEF
96 20 960
FPL
50 15 15 30 30 15 yes 600
Sc
247 999 Pt1
1
999
Unit
App. 0 (Def.)
App. 1
App. 2
App. 3
App. 4
App. 5
App. 6
min 30 45 15 15 30 30 30
min 0
0
0
0
0
0
–
min 0
0
0
0
0
0
5
min 0
0
0
0
0
0
5
C/F -5
–
–
–
-5
-5
–
on on on on on on on
non non non non dEF dEF non
hours 0
0
0
0
0
0
–
K
20
–
–
–
20 20
–
min 0
0
0
0
0
0
–
FAo FAo FAo FAo FAo FAo FAo
C/F 50
–
–
–
50 50
–
min 2
2
2
2
2
2
2
min 2
2
2
2
2
2
2
min 0
0
0
0
0
0
0
min 2
2
2
2
2
2
2
min 0
0
0
0
0
0
1
yes yes yes yes yes yes yes
min 5
5
5
5
5
5
5
oFF oFF oFF oFF oFF oFF oFF
0
0
0
0
0
0
–
no no no no no no
0
n10 n10 n10 n10 n10 n10 –
0.1 0.1 0.1 0.1 0.1 0.1 0.1
0
0
0
0
0
0
–
© Copyright Danfoss | Published by ADAP-KOOL | 2018.10
Installation guide | ERC 214
DKRCE.PI.RL0.N4.02 | 7
Installation guide – ERC 214
Parameter name – ERC 214
Code
Relay 2 counter (1 count = 100 operating cycles)
o24
Relay 3 counter (1 count = 100 operating cycles)
o25
Relay 4 counter (1 count = 100 operating cycles)
o26
DO4 configuration ALA=alarm, Lig=light
o36
DI2 configuration
oFF=not used, Sdc=status display output,
doo=door alarm with resumption,
doA=door alarm without resumption, SCH=main switch, nig=day / night mode,
o37
rFd=reference displacement,
EAL=external alarm, dEF=defrost,
Pud=pull-down
Lights control
on=always on, dAn=day / night,
o38
doo=on basis of door action
Predefined applications
o61
Save settings as default WARNING: previous default settings o67 will be overwritten
Display at defrost
Air=effective air temperature, FrE=freezing temperature,
o91
-d-=”-d-” is displayed
Polarity
P–
DI1 input polarity
nc=normally closed,
P73
no=normally open
DI2 input polarity
nc=normally closed,
P74
no=normally open
Invert alarm relay 0=normal, 1=relay action inversion
P75
Keyboard lock enable
P76
Readouts
u–
Controller status
S0=cooling ON/Heating ON,
S2=wait for compressor ON time to elapse,
S3=wait for compressor OFF time to
elapse-restart time, S4=drip OFF
delay after defrost, S10=cooling stop,
S11=cooling stopped by thermostat / heating OFF, S14=defrosting state,
u00
S15=fan delay state after defrost,
S17=door open (DI input),
S20=emergency cooling, S25=manual
control of outputs, S30=continous
cycle/Pull-down, S32=delay of outputs
at power up
Air temperature (Sair)
U01
Read the present regulation reference
u02
Defrost temperature (S5)
u09
N.B.: hidden parameters are greyed out
Min. 0 0 0
ALA
oFF
on AP0 no Air
nc nc 0 no
S0
-100 -100 -100
Max. 999 999 999 Lig
Pud
doo AP6 yes -d-
no no 1 yes
S32
200 200 200
Unit
App. 0 (Def.)
App. 1
App. 2
App. 3
App. 4
App. 5
App. 6
0
0
0
0
0
0
–
0
0
0
0
0
0
–
0
0
0
0
0
0
–
Lig Lig Lig Lig Lig Lig
–
oFF oFF oFF oFF oFF oFF oFF
on on on on on on on
AP0 AP1 AP2 AP3 AP4 AP5
–
no no no no no no
–
-d- -d- -d- -d- -d- -d- -d-
no no no no no no no
no no no no no no no
0
0
0
0
0
0
–
no no no no no no
–
—
C/F —
C/F —
C/F —
–
–
–
© Copyright Danfoss | Published by ADAP-KOOL | 2018.10
Installation guide | ERC 214
DKRCE.PI.RL0.N4.02 | 8
Installation guide – ERC 214
Parameter name – ERC 214
Code
DI1 input
u10
Status of night operation
u13
DI2 input
u37
Condenser temperature (Sc)
U09
Compressor relay status
u58
Fan relay status
u59
Defrost relay status
u60
Alarm relay status
u62
Light relay status
u63
Firmware version readout
u80
Alarm status
Sair air temperature sensor error
E29
S5 defrost sensor error
E27
Sc condenser sensor error
E30
High temperature alarm
A01
Low temperature alarm
A02
High voltage alarm
A99
Low voltage alarm
AA1
Condenser alarm
A61
Door alarm
A04
Standby alarm
A45
DI external alarm
A15
N.B.: hidden parameters are greyed out
Min.
oFF oFF oFF -100 oFF oFF oFF oFF oFF 0
Max.
on on on 200 on on on on on 999
Unit
App. 0 (Def.)
App. 1
App. 2
App. 3
App. 4
App. 5
App. 6
—
—
—
C/F —
—
—
—
—
—
—
Safety standards
Check the input voltage is correct before connecting the instrument. Do not expose to water or damp: only use the regulator within the design operating limits, avoiding sudden temperature changes with high atmospheric humidity to prevent condensate forming.
Product disposal
The device (or product) must be disposed of in compliance with local waste disposal legislation.
EU design registration
002566703-0001
Contact info.: www.danfoss.com/erc
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice.This also applies to products
already on order provided that such alterations can be made without subsequential changes being necessary
eady agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
© Copyright Danfoss | Published by ADAP-KOOL | 2018.10
Installation guide | ERC 214
DKRCE.PI.RL0.N4.02 | 9
Documents / Resources
![]() |
Danfoss ERC 214 Digital Regulator [pdf] Installation Guide 80G8101.01, 80G8102.01, 80G8103.02, ERC 214 Digital Regulator, ERC 214, Digital Regulator, Regulator |