Danfoss CXH140 Scroll Compressors Instructions

CXH140 Scroll Compressors

Instructions
Danfoss scroll compressors
CXH

scroll

danfoss

A: Model number
B: Serial number
C: Refrigerant
D: Supply voltage, Starting current & Maximum operating current
E: Housing service pressure
F: Factory charged lubricant

Installation and servicing of the compressor by qualified personnel only. Follow
these instructions and sound refrigeration engineering practice relating to
installation, commissioning, maintenance and service.

details

overheating

The compressor must only be
used for its designed purpose(s)
and within its scope of application
(refer to «operating limits»).
Consult Application guidelines and
datasheet available from cc.danfoss.
com

Under all circumstances,
the EN378 (or other
applicable local safety
regulation) requirements
must be fulfilled.

fuseThe compressor is delivered under
nitrogen gas pressure (between
0.3 and 0.7 bar) and hence cannot
be connected as is refer to
the «assembly» section for further
details.

The compressor must be
handled with caution in the
vertical position (maximum
offset from the vertical: 15°)

1 – Introduction
These instructions pertain to the Danfoss scroll
compressors CXH used for air-conditioning
systems. They provide necessary information
regarding safety and proper usage of this
product.

2 – Handling and storage
• Handle the compressor with care. Use the
dedicated handles in the packaging. Use the
compressor lifting lug and use appropriate
and safe lifting equipment.
• Store and transport the compressor in an
upright position.
• Store the compressor between -35°C and 50°C.
• Don’t expose the compressor and the
packaging to rain or corrosive atmosphere.

3 – Safety measures before assembly
Never use the compressor in a flammable
atmosphere.
• The compressor ambient temperature may
not exceed 50°C during off-cycle.
• Mount the compressor on a horizontal flat
surface with less than 3° slope.
• Verify that the power supply corresponds to
the compressor motor characteristics (see
nameplate).

CXH140
These Danfoss scroll compressors are protected against overheating
and overloading by an internal safety motor protector. However, an external
manual reset overload protector is recommended for protecting
the circuit against over-current.

  • When installing CXH, use equipment
    specifically reserved for HFC refrigerants
    which was never used for CFC or HCFC
    refrigerants.
  • Use clean and dehydrated refrigeration-grade
    copper tubes and silver alloy brazing material.
  • Use clean and dehydrated system components.
  • The piping connected to the compressor must
    be flexible in 3 dimensions to dampen vibrations.

4 – Assembly

  • In parallel assemblies of CXH the compressor
    requires a rigid mounting on the rails. Use the
    rigid spacers from the tandem mounting kit
    or the rigid spacers delivered with dedicated
    tandem compressors.
  • Slowly release the nitrogen holding charge
    through the schrader port.
  • Remove the gaskets when brazing roto lock
    connectors.
  • Always use new gaskets for assembly.
  • Connect the compressor to the system as
    soon as possible to avoid oil contamination
    from ambient moisture.
  • Avoid material entering into the system while
    cutting tubes. Never drill holes where burrs
    cannot be removed.
  • Braze with great care using state-of-the-art
    technique and vent piping with nitrogen gas
    flow.
  • Connect the required safety and control
    devices. When the schrader port is used for
    this, remove the internal valve.

5 – Leak detection

Never pressurize the circuit with oxygen or
dry air. This could cause are or explosion.

  • Pressurize the system on HP side first and then
    on LP side. Never let the pressure on LP side
    exceed the pressure on HP side with more than
    5 bar. Such pressure difference could cause
    internal compressor damage.
  • Do not use dye for leak detection.
  • Perform a leak detection test on the complete
    system.
  • The test pressure must not exceed:
    Models LP side HP side
    CXH140 33.3 bar 45.5 bar
  • When a leak is discovered, repair the leak and
    repeat the leak detection.

6 – Vacuum dehydration

  • Never use the compressor to evacuate the
    system.
  • Connect a vacuum pump to both the LP & HP
    sides.
  • Pull down the system under a vacuum of 500
    μm Hg (0.67 mbar) absolute.
  • Do not use a megohmmeter nor apply power
    to the compressor while it is under vacuum as
    this may cause internal damage.

7 – Electrical connections

  • Switch off and isolate the main power supply.
    See overleaf for wiring details.
  • All electrical components must be selected as per
    local standards and compressor requirements.
  • Refer to page 2 for electrical connections details.
  • The Danfoss scroll compressors only
    works correctly in one rotation direction.
    Line phases L1, L2, L3 must absolutely be
    connected to compressor terminals T1, T2, T3
    to avoid reverse rotation.
  • Use ø 4.8 mm (3/16”) screws and ¼” ring
    terminals for the power connection. Fasten
    with 3 Nm torque.
  • The thermostat connection (if present) is a ¼”
    AMP-AWE spade connector.
  • The compressor must be connected to earth
    with the 5 mm earth terminal screw.

8 – Filling the system

  • Keep the compressor switched off.
  • Fill the refrigerant in liquid phase into the
    condenser or liquid receiver. The charge must
    be as close as possible to the nominal system
    charge to avoid low pressure operation and
    excessive superheat. Never let the pressure
    on LP side exceed the pressure on HP side
    with more than 5 bar. Such pressure dierence
    could cause internal compressor damage.
  • Keep the refrigerant charge below the
    indicated charge limits if possible. Above
    this limit; protect the compressor against
    liquid flood-back with a pump-down cycle or
    suction line accumulator.
  • Never leave the fulling cylinder connected to
    the circuit.
    Compressor models Refrigerant charge
    limit (kg)

CXH140 7.9

9 – Verification before commissioning

Use safety devices such as safety pressure
switch and mechanical relief valve in compliance
with both generally and locally applicable
regulations and safety standards. Ensure that
they are operational and properly set.
Check that the settings of high-pressure
switches and relief valves don’t exceed the
maximum service pressure of any system
component.

  • A low-pressure switch is recommended to
    avoid vacuum operation. Minimum setting
    for CXH: 1.5 bar g.
  • Verify that all electrical connections are
    properly fastened and in compliance with
    local regulations.
  • When a crankcase heater is required, it must be
    energized at least 6 hours before initial startup
    and start-up after prolonged shutdown for
    sump heaters.

10 – Start-up

  • Never start the compressor when no
    refrigerant is charged.
  • All service valves must be in the open position.
  • Balance the HP/LP pressure.
  • Energize the compressor. It must start
    promptly. If the compressor does not start,
    check wiring conformity and voltage on
    terminals.
  • Eventual reverse rotation can be detected
    by following phenomena; the compressor
    doesn’t build up pressure, it has abnormally
    high sound level and abnormally low power
    consumption. In such case, shut down the
    compressor immediately and connect the
    phases to their proper terminals. CXH140
    has no internal reverse rotation protection.
    Prolonged reverse rotation will damage the
    compressors.
  • If the internal overload protector trips out it
    must cool down to 60°C to reset. Depending
    on ambient temperature, this may take up to
    several hours.

11 – Check with running compressor

  • Check current draw and voltage.
  • Check suction superheat to reduce risk of
    slugging.
  • Observe the oil level in the sight glass (if
    provided) for about 60 minutes to ensure
    proper oil return to the compressor.
  • Respect the operating limits.
  • Check all tubes for abnormal vibration.
    Movements in excess of 1.5 mm require
    corrective measures such as tube brackets.
  • When needed, additional refrigerant in liquid
    phase may be added in the low-pressure side
    as far as possible from the compressor. The
    compressor must be operating during this
    process.
  • Do not overcharge the system.
  • Never release refrigerant to atmosphere.
  • Before leaving the installation site, carry out
    a general installation inspection regarding
    cleanliness, noise and leak detection.
  • Record type and amount of refrigerant charge
    as well as operating conditions as a reference
    for future inspections.

12 – Maintenance

Internal pressure and surface temperature
are dangerous and may cause permanent injury.
Maintenance operators and installers require
appropriate skills and tools. Tubing temperature
may exceed 100°C and can cause severe burns.
Ensure that periodic service inspections to
ensure system reliability and as required by local
regulations are performed.

To prevent system related compressor problems,
following periodic maintenance is recommended:

  • Verify that safety devices are operational and
    properly set.
  • Ensure that the system is leak tight.
  • Check the compressor current draw.
  • Confirm that the system is operating in a
    way consistent with previous maintenance
    records and ambient conditions.
  • Check that all electrical connections are still
    adequately fastened.
  • Keep the compressor clean and verify
    the absence of rust and oxidation on the
    compressor shell, tubes and electrical
    connections.

13 – Warranty

Always transmit the model number and serial number
with any claim filed regarding this product.
The product warranty may be void in following cases:

  • Absence of nameplate.
  • External modifications; in particular, drilling,
    welding, broken feet and shock marks.
  • Compressor opened or returned unsealed.
  • Rust, water or leak detection dye inside the compressor.
  • Use of a refrigerant or lubricant not approved by Danfoss.
  • Any deviation from recommended instructions pertaining to installation, application or maintenance.
  • Use in mobile applications.
  • Use in explosive atmospheric environment.
  • No model number or serial number transmitted with the warranty claim.

14 – Disposal

Danfoss recommends that compres
sors and compressor oil should be
recycled by a suitable company at its
site.

Danfoss A/S, 6430 Nordborg, Denmark

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Documents / Resources

Danfoss CXH140 Scroll Compressors [pdf] Instructions
CXH140, CXH140 Scroll Compressors, CXH140, Scroll Compressors, Compressors

References

Leave a comment

Your email address will not be published. Required fields are marked *