Danfoss CSV 2, CSV 22 Solenoid Valve
Solenoid valve
- Types CSV 2 – CSV 22 (NC)
Refrigerants
- R22, R134a, R404A, R507, R407C, R513A, R452A, R600, R600a, R1234ze and R290.
- For other refrigerants, contact Danfoss.
Note: Please follow the specific selection criteria stated in the data sheet for these particular refrigerants.
- Max. working pressure: PS / MWP: 35 bar /508 psig
- Max. operation pressure differential (MOPD): Coil dependent
- Medium temperature: -40 – 105 °C / -40 – 221 °F
- Ambient temperature: -20 – 55 °C / -4 – 131 °F
- For CSV 3 and CSV 6 type valves, Danfoss recommends that a suitable filter or filter drier (max. size of 40 – 50 um) is installed ahead of each solenoid valve to keen scale. solder material and other foreian dirt and particles out of the valve
Mounting angle
Soldering
Flare
Warning
- Always disconnect power from the coil when dismounted from the valve.
- The coil may be damaged and there is a risk of injuries and burns.
- To ensure correct sealing between the coil and valve, mount the coil in the proper position and make sure that the coil is fully clicked on to the valve.
© Danfoss | DCS (sb) | 2020.10
AN34705422346901-000201 | 1 ugov.ua