Danfoss CN0101 BeaCon Actuator Actuator Dynamic Balancing Valve

Danfoss-CN0101-BeaCon-Actuator-Actuator-Dynamic-Balancing-Valve-PRODUCT

Product Specifications

  • Product Name: BeaCon Actuator
  • Dynamic Balancing Valve (AB-QM) (DN15-32)
  • Control Valve (RA-G) (DN20-32)
  • Power Supply: 24V
  • Communication: M-BUS

Product Usage Instructions

Installation

  1. Install with a Dynamic balancing valve (AB-QM) via M30x1.5 thread.
  2. Install with a Dynamic balancing valve (AB-QM) via RA connector.

Manual Operation

  • Press the up and down buttons together for 4 seconds until the power light flashes to enter manual operation mode.
  • Press the up or down button for 4 seconds. The actuator spindle will move accordingly with the respective light flashing.
  • Press the reset button shortly for calibration or long-press for 5 seconds to reset the actuator.

Safety Note

  • Read and observe all instructions before assembly and commissioning to avoid injury and damage.
  • All assembly, start-up, and maintenance work should be carried out by qualified personnel.
  • Switch off the power line before wiring the actuator.

Additional Information

  • Connect via a safety isolating transformer.
  • Dismantle the product for recycling or disposal following local regulations.

BeaCon Actuator

Danfoss-CN0101-BeaCon-Actuator-Actuator-Dynamic-Balancing-Valve-FIG-1

Installation Guide

Danfoss-CN0101-BeaCon-Actuator-Actuator-Dynamic-Balancing-Valve-FIG-2

  • A: Install with a Dynamic balancing valve (AB-QM) via M30x1.5 threadDanfoss-CN0101-BeaCon-Actuator-Actuator-Dynamic-Balancing-Valve-FIG-3
  • B: Install with a Dynamic balancing valve (AB-QM) via RA connectorDanfoss-CN0101-BeaCon-Actuator-Actuator-Dynamic-Balancing-Valve-FIG-4
  • Black: Power:24V
  • Red: Communication: M-bus
    • Yellow
    • WhiteDanfoss-CN0101-BeaCon-Actuator-Actuator-Dynamic-Balancing-Valve-FIG-5
  • Address ID laser on the side of the actuator, which can be removed from the actuator for recording or saving.Danfoss-CN0101-BeaCon-Actuator-Actuator-Dynamic-Balancing-Valve-FIG-6

 Manual operation

  • Press the up and down buttons together 4 times until the power light flashes to enter manual operation mode.
  • Press the up(down) button 4s. The actuator spindle will move up (down). Up(down) light flashing during the spindle movement.
  • Press the reset button short time. The actuator performs calibration.
  • Press the reset button long time, 5s. Actuator reset. All lights flashing together one time.
  • The spindle of the actuator moves to the top and stops for 1 min. Then, perform calibration automatically.Danfoss-CN0101-BeaCon-Actuator-Actuator-Dynamic-Balancing-Valve-FIG-7

Indicator explanation

Indicator Long bright off Slow blink fast blink
Power M-BUS control Power off/Alarm Manual operation
Up Fully open position of valve Middle position of the valve Moving up
Down Fully close the position of the valve Moving down
M-BUS Receiving the data package within 10 minutes M-BUS disconnect No data package within 10 min
Alarm normal Fault diagnosis

Safety Note

  • Danfoss-CN0101-BeaCon-Actuator-Actuator-Dynamic-Balancing-Valve-FIG-8To avoid injury and damage to persons and devices, these instructions must be carefully read and observed before assembly and commissioning.
  • Necessary assembly, start-up, and maintenance work must be performed only by qualified, trained, and authorised personnel. Switch off the power line before wiring the actuator.
  • Danfoss-CN0101-BeaCon-Actuator-Actuator-Dynamic-Balancing-Valve-FIG-8Connect via a safety isolating transformer.
  • Galvanic separations shall be provided for segments crossing buildings.
  • Danfoss-CN0101-BeaCon-Actuator-Actuator-Dynamic-Balancing-Valve-FIG-9This product should be dismantled, and its components sorted, if possible, into various groups before recycling or disposal. Always follow the local disposal regulations.

CUSTOMER SERVICE

Frequently Asked Questions

  • Q: How do I perform a factory reset on the actuator?
    • A: Press the reset button for 5 seconds to reset the actuator.
    • All lights will flash together once, and the spindle will move to the top and stop for 1 minute before automatic calibration.
  • Q: What should I do if the M-BUS connection is lost?
    • A: If there is no data package received within 10 minutes, the M-BUS indicator will blink fast, indicating a loss of connection.
    • Check the connections and restart if necessary.