Danfoss 042R0151 Solenoid Coil For Control In Potentially Explosive Areas
Specifications
- Nominal voltage: 24V DC, 110V, 230V, 240V
- Frequency: 50/60 Hz
- Nominal current: 0.46A – 0.053A
- Weight: 1.0 kg
- Protection degree: IP67 (Evaluated by Danfoss)
- Pollution degree: 3 (EN60730-1)
- Overvoltage category: II (2.5 kV)
- Mode of operation: Type 1 action (EN60730-1)
Installation
Connection
Connect the solenoid coil according to the provided wiring diagram.
Identification
- Green/Yellow cord for earthing
- Week and date of manufacturing
- External earth terminal
- Code number
- Voltage
- Approval/Certificate number
- Frequency
- Ambient temperature range
- Country of manufacturing
- Approval logos
EX Certifications
- Ex mb IIC T4 Gb
- IECEx ULD 21.0024X
- UL 21 ATEX 2606X
- UL21UKEX2374X
The coil may only be installed with the following valve combinations
Valves work with A
- EVM-EVRF-EVRP-EVRB
- AKV, AKVA
- EVR 2, 3, 6
- EVRS(T) 3
- EV210BW, EV210B
- ICLX
- VDH, VDHT EAM, VDHT
- VPH
- EVRA 3, EVRA(T) 3
Valves work with B
- EV220B 6, 10, 12, 14, 18, 22
- EV221BW
- EV251B
- EVRS(T) 10-20
- ICF
- EV227B
- EVRA 10, 15, 20 (Before 1996)
- EVRA(T) 10, 15, 20 (Before 1996)
Valves woworkith both
- EVR 10, 15, 20, 22, 25, 32, 40
- EV220B 15, 20, 25, 32, 40, 50
- EV220BW
- EV220B 65, 80, 100
- EV250BW, EV250B
- VDH 30 EC
- EV222B
- EV224B
- EVRA 10, 15, 20, 25, 32, 40 (After 1996)
- EVRA(T) 10, 15, 20 (After 1996)
Application and specification
Nominal
voltage |
Frequency | Nominal current | Code no wth cover and bottom | Code no with cover and frame | ||
[V] | [Hz] | [A] | 5m cable | 10m cable | 5m cable | 10m cable |
24 | DC | 0.46 | 018Z8589 | 018Z8569 | 018Z8596 | 018Z8575 |
24 | 50/60 | 0.48 | 018Z8588 | 018Z8568 | 018Z8595 | 018Z8574 |
110 | 50/60 | 0.102 | 018Z8587 | 018Z8567 | 018Z8593 | 018Z8573 |
230 | 50/60 | 0.053 | 018Z8586 | 018Z8566 | 018Z8592 | 018Z8572 |
240 | 50/60 | 0.047 | 018Z8585 | 018Z8565 | 018Z8591 | 018Z8571 |
Ambient temp. -40 °C ≤ Tambient ≤ +40 °C Protection degree IP67(Evaluated by Danfoss)
Media -40 °C < Tmedia < +90 °C Polution degree 3 (EN60730-1) Humidity 0 – 97 % Over voltage category II (2.5 kV) Voltage +6 / -10 % Mode of operation Type 1 action (EN60730-1) Connection 3-Wire cable 3 x 0.75mm² External earth wire Minimum wire gauge > 4mm² |
Safety instruction
All national safety regulations must be complied with in connection with the installation, start-up, and operation of the Danfoss solenoid valve. Furthermore, the requirements of the declaration of conformity and national regulations for installation in an explosion area. Disregarding such regulations involves a risk of serious personal injury or extensive material damage. Work in connection with the solenoid valve mentioned must be performed only by suitable, qualified persons. Safety requirements for use in explosive atmospheres are fulfilled through compliance certificates
- Ex mb IIC T4 Gb
- IECEx ULD 21.0024X
- UL 21 ATEX 2606X
- UL21UKEX2374X
Specific Condition of Safe Use
- The solenoid coil shall be protected against impact during use
- Protect the coil against direct sunlight and other ultraviolet sources
- Disconnect the power before dismounting the coil
- Install the coil and cable according to IEC/EN/ EN BS 60079-14
- The cable supplied with the solenoids must not be handled or flexed, and shall be protected against impact if the ambient temperature is below 0 °C
- The coils must be installed in the orientation shown on page 1
- The permitted process medium temperature range is -40 °C to +90 °C
- The capacitance of exposed, isolated, metallic parts is 7pF
- The cable is only for fixed installation, and the minimum bending diameter for fixed installation: r ≥ 35 mm ( 2 )
- The cable jacket material is PVC
- The cable operating temperature range is -40 – 90 °C
- The product is provided with a yellow/green PE Conductor as well as an external earth terminal. These shall not be used simultaneously.
If the external earth connection is connected to earth or bonding system, the PE Conductor must be cut off, isolated, and not connected. If the PE Conductor is connected to earth, the external earth terminal must be left without any connection. For the external earth terminal, the size of the earth core shall be e minimum of 4 mm², and the installer shall use a suitable method,e.g., crimp terminal, to ensure the security of the external earth connection. The screw for external PE shall be mounted with 1.2 Nm ± 0.2. The external earth conductors shall be physically secured close to the coil connection to ensure that the conductors cannot be readily loosened or twisted - The end user must ensure the earthing of the coil is maintained
- The non-detachable cords method of Z repairing is not allowed. If the coil failed, it must be replaced with a new coil
UK-CA contact address
Danfoss Ltd. 22 Wycombe End, HP9 1NB, GB
CE contact address
Danfoss A/S DK-6430 Nordborg Denmark
FAQs
Q: What should I do if the solenoid coil is not functioning properly?
A: Check the wiring connections, ensure the voltage input matches the specifications, and consult a qualified technician.
Q: Can the solenoid coil be used in explosive atmospheres?
A: Ycompliance certificates fulfill es, the safety requirements for use in explosive atmospheres. Ensure that you follow all safety instructions.
Documents / Resources
![]() |
Danfoss 042R0151 Solenoid Coil For Control In Potentially Explosive Areas [pdf] Installation Guide 018Z8589, 018Z8569, 018Z8588, 018Z8568, 018Z8587, 018Z8567, 018Z8586, 018Z8566, 018Z8585, 018Z8565, 042R0151 Solenoid Coil For Control In Potentially Explosive Areas, 042R0151, Solenoid Coil For Control In Potentially Explosive Areas, Control In Potentially Explosive Areas, Potentially Explosive Areas, Explosive Areas |