PR750LCD3C Smart App Sinewave UPS
“
Specifications
- Model: PR750LCD3C
- Brand: CyberPower
- Features: PowerButton/PowerOnIndicator, OnlineIndicator,
OnBatteryIndicator, FaultIndicator, BatteryFaultIndicator,
LCDModuleOperationButtons, CloudMonitoring(EthernetPort),
EPO(EmergencyPowerOff)Port, Serial/USBPorts to PC, TVSS Screw,
SNMP/HTTP Network Slot, Circuit Breaker, AC Input Power Cord,
Battery and Surge Protected Outlets
Product Information
Your ultimate ally in power, the Intelligent UPS Series
PR750LCD3C is designed to provide unsurpassed power protection,
operation, and performance. It features various indicators,
operation buttons, ports for connectivity, and outlets for battery
and surge protection.
For product registration and warranty benefits, visit CyberPowerSystems.com/registration.
Ensure to follow all safety warnings and instructions provided
in the manual for the safe installation and operation of the
UPS.
Usage Instructions
1. Installation:
– Install the UPS in a temperature and humidity controlled
indoor area free of conductive contaminants.
– Connect the UPS to an AC power outlet with fuse or circuit
breaker protection.
– Ensure proper grounding of the outlet.
2. Maintenance:
– Do not remove the cover except to service the battery. Turn
off and unplug the unit before servicing the batteries.
– The UPS must be easily accessible for maintenance
purposes.
3. Safety Precautions:
– Do not use the UPS for medical or life support equipment.
– Do not use near aquariums to prevent the risk of fire or
electric shock.
– Do not use the UPS on any transportation such as airplanes or
ships.
FAQ
Q: Where can I register my product for warranty benefits?
A: You can register your product at
www.CyberPowerSystems.com/registration to receive warranty
benefits.
Q: What should I do before servicing the batteries?
A: Turn off and unplug the unit from the AC power source before
servicing the batteries.
Q: Can I use the UPS near aquariums?
A: No, it is not recommended to use the UPS near aquariums to
prevent the risk of shorting out due to condensation.
“`
YOUR ULTIMATE ALLY IN POWER
INTELLIGENT UPS SERIES
PR750LCD3C
USER MANUAL
2
1
4
8
9
3
10
5
7
6
Menu Esc
Enter
14
UNINTERRUPTIBLE POWER SUPPLY E187679 6G48
11 12 13
FEATURES
1. PowerButton/PowerOnIndicator 2. OnlineIndicator 3. OnBatteryIndicator 4. FaultIndicator 5. BatteryFaultIndicator 6. LCDModuleOperationButtons 7. CloudMonitoring(EthernetPort)
8. EPO(EmergencyPowerOff)Port 9. Serial/USBPortstoPC 10. TVSSScrew 11. SNMP/HTTPNetworkSlot 12. CircuitBreaker 13. ACInputPowerCord 14. BatteryandSurgeProtectedOutlets
PRODUCT REGISTRATION
ThankyouforpurchasingaCyberPowerproduct.ThisUPSisdesignedtoprovideunsurpassedpower protection,operation,andperformanceduringthelifetimeoftheproduct.Pleasetakeafewminutesto registeryourproductat:www.CyberPowerSystems.com/registration. Registrationcertifiesyourproduct’swarranty,confirmsyourownershipintheeventofaproductlossortheft, andentitlesyoutofreetechnicalsupport.RegisteryourproductnowtoreceivethebenefitsofCyberPower ownership.
Cyber Power Systems (USA), Inc. 424112thAvenueEast,Suite400|Shakopee,MN55379|CyberPowerSystems.com
IMPORTANT SAFETY WARNINGS (SAVETHESEINSTRUCTIONS)
Thismanualcontainsimportantinstructionsthatshouldbefollowedduringinstallationandmaintenanceofthe UPSandbatteries.Pleasereadandfollowallinstructionscarefullyduringinstallationandoperationoftheunit. Readthismanualthoroughlybeforeattemptingtounpack,install,oroperateyourUPS.
CAUTION! Topreventtheriskoffireor electricshock,installinatemperatureandhumidity controlledindoorareafreeof conductivecontaminants.(Pleasesee specificationsforacceptabletemperature andhumidityrange).
CAUTION!Toreducetheriskofelectricshock,do notremovethecoverexcepttoservicethebattery. Turnoffandunplugtheunitbefore servicingthebatteries.Therearenouserserviceable partsinsideexceptforthebattery.
CAUTION!Hazardouslivepartsinsidecanbe energizedbythebatteryevenwhentheACinput powerisdisconnected.
CAUTION!TheUPSmustbeconnectedtoanAC poweroutletwithfuseorcircuitbreakerprotection. Donotplugintoanoutletthatisnotgrounded.If youneedtodeenergizethisequipment,turnoffand unplugtheunit.
CAUTION!Toavoidelectricshock,turnofftheunit andunplugitfromtheACpowersourcebefore servicingthebatteryorinstallingacomputer component.
CAUTION!Toreducetheriskoffire,connectonlyto acircuitprovidedwith20amperesmaximumbranch circuitovercurrentprotectioninaccordancewith theNationalElectricCode,ANSI/NFPA70.
CAUTION!Notforuseinacomputerroomas definedintheStandardfortheProtectionof ElectronicComputer/DataProcessingEquipment, ANSI/NFPA75.
CAUTION!Donotdisposeofbatteriesinafire.The batteriesmayexplode.
CAUTION! TheUPSshouldbeneartheconnected equipmentandeasilyaccessible.
DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! CyberPowerSystemsdoesnotsellproductsforlife supportormedicalapplications.DONOTuseinany circumstancethatwouldaffectoperationandsafety oflifesupportequipment,anymedicalapplications orpatientcare.
DO NOT USE WITH OR NEAR AQUARIUMS! Toreducetheriskoffireorelectricshock,donotuse withornearanaquarium.Condensationfromthe aquariumcancausetheunittoshortout.
DO NOT USE THE UPS ON ANY TRANSPORTATION! Toreducetheriskoffireorelectricshock,donotuse theunitonanytransportationsuchasairplanesor ships.Theeffectofshockorvibrationcausedduring transitandthedampenvironmentcancausetheunit toshortout.
INSTALLING YOUR UPS SYSTEM
UNPACKING InspecttheUPSuponreceipt. Theboxshouldcontainthefollowing: (a)UPSunit (b)User’smanual (c)Emergencypoweroffcable(gray) (d)USBA+Btypecable (e)Functionsetupguide
PowerPanel®Businesssoftwareisavailableonour website.Pleasevisitwww.cyberpowersystems.com andgototheSoftwareSectionforafreedownload. OVERVIEW ThePR750LCD3Cprovidescompletepower protectionfromutilitypowerthatisnotalways consistent.
ThePR750LCD3Cfeatures1030Joulesofsurge protectionagainstpowersurgesandmaintenance freebatteriesforlonglastingbatterybackupduring poweroutages.Inadditiontoensuringconsistent powertoyourcomputersystem,thePR750LCD3C alsoincludessoftwarethatwillautomaticallysave youropenfilesandshutdownyourcomputersystem duringautilitypowerloss.
AUTOMATIC VOLTAGE REGULATOR
ThePR750LCD3Cstabilizesinconsistentutilitypower tonominallevelsthataresafeforequipment.Unstable utilitypowercanbedamagingtoimportantdataand hardware.WithAutomaticVoltageRegulation(AVR), damagingvoltagelevelsarecorrectedtosafelevels. AVRautomaticallyincreaseslowutilitypowertoa consistentandsafe110/120volts.
INSTALLING YOUR UPS SYSTEM
DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT
1. EnsurethattheequipmentpluggedintotheUPS doesnotexceedtheUPSunit’sratedcapacity.If theratedcapacitiesoftheunitareexceeded,an overloadconditionmayoccurandcausetheUPS unittoshutdownorthecircuitbreakertotrip.
2. Therearemanyfactorsthatcanaffectthe amountofpowerthatyourelectronicequipment willrequire.Foroptimalsystemperformancekeep theloadbelow80%oftheunit’sratedcapacity.
HARDWARE INSTALLATION GUIDE
1. YournewUPSmaybeusedimmediately uponreceipt.However,toensurethebattery’s maximumchargecapacity,itisrecommended thatyouchargethebatteryforatleast8hours. YourUPSisequippedwithanautocharge feature.WhentheUPSispluggedintoanAC outlet,thebatterywillautomaticallycharge whethertheUPSisturnedonoroff.Note:This UPSisdesignedwithasafetyfeaturetokeepthe systemfrombeingturnedonduringshipment. ThefirsttimeyouturntheUPSon,youwillneed tohaveitconnectedtoACpoweroritwillnot powerup.
2. WiththeUPSunitturnedoffandunplugged, connectyourcomputer,monitor,andanyother peripheralsrequiringbatterybackupintothe batterypowersuppliedoutlets.DO NOT plug a laser printer, paper shredder, copier, space heater, vacuum, sump pump or other large electrical devices into the “Battery and Surge Protected Outlets”. The power demands of these devices may overload and damage the unit.
PLUG IN
3. PlugtheUPSintoa2pole,3wiregrounded receptacle(walloutlet).Makesurethewall branchoutletisprotectedbyafuseorcircuit breakeranddoesnotserviceequipmentwith largeelectricaldemands(e.g.,airconditioner, copier,etc…).Thewarrantyprohibitstheuseof extensioncords,outletstrips,andsurgestrips.
4. Pressthepowerbuttonandtheenterbuttonto turntheuniton.ThePowerOnindicatorlightwill illuminate.Ifanoverloadisdetected,anaudible alarmwillsoundandtheunitwillemitonelong beep.Tocorrectthis,turntheUPSoffandunplug atleastonepieceofequipmentfromthebattery powersuppliedoutlets.Makesurethecircuit breakerisdepressedandthenturntheUPSon.
5. Tomaintainoptimalbatterycharge,leavetheUPS pluggedintoanACoutletatalltimes.
6. TostoretheUPSforanextendedperiod,coverit andstorewiththebatteryfullycharged.Whilein storage,rechargethebatteryeverythreemonths toensurebatterylife.
7. EnsurethewalloutletandUPSarelocated neartheequipmentbeingattachedfor properaccessibility.
SYSTEM FUNCTION BLOCK DIAGRAM
Input
EMI Filter
Surge Suppressor
Normal Mode Battery Mode
Charger AC / DC
AVR
Output Inverter
Battery
BASIC OPERATION
1. Power Button / Power On Indicator Usedasthemasteron/offswitchforequipment connectedtothebatterypowersuppliedoutlets.
2. Online Indicator ThisLEDisilluminatedwhentheutilitypoweris normalandtheUPSoutletsareprovidingpower, freeofsurgesandspikes.
3. On Battery Indicator Duringaseverebrownoutorblackout,thisLED isilluminatedandanalarmsounds(twoshort beepsfollowedbyapause)toindicatetheUPSis operatingfromitsinternalbatteries.
4. Fault Indicator ThisLEDisilluminatedifthereisaproblemwith theUPS.
5. Battery Fault Indicator ThisLEDisilluminatedifthereisabatteryissue withtheUPS.
6. LCD Module Operation Buttons Foradditionalinformationonhowtocustomizethe UPS’soperation,pleaserefertotheLCDSetting Guidesectionbelow.
7. Cloud Monitoring (Ethernet Port) ThecardconnectsaUPStoPowerPanelCloudto provideuserstheabilitytomonitortheoperationof theirUPS.Foradditionalinformation,pleaserefer tohttps://www.cyberpowersystems.com/products/ software/powerpanelcloud. *REMINDER:NOTFORTELECOMMUNICATION (TELEPHONE)NETWORK.
8. EPO (Emergency Power Off) Port TheEPO/ROOinterfaceisanIEC60950safety extralowvoltage(SELV)circuit.Thiscircuitmust beseparatedfromhazardousvoltagecircuitsby reinforcedinsulation.Followtheappropriatecircuit diagrambelowtowiretheprovidedgrayEPOcable toyourEPO/ROOconfiguration.Connectisolated drycontacts(ratedtohandle60Vdc,30VacRMS and20mAmaximum)anduseONLYlatching switch.
OPTION 1: USER SUPPLIED NORMALLY OPEN SWITCH
(RECOMMENDED)
1
ROO SWITCH
2
3
4 N.O.EPO SWITCH
OPTION 2: USER SUPPLIED NORMALLY CLOSED SWITCH
1
ROO SWITCH
2
N.C.EPO SWITCH
3
4 3-4 JUMPER
*REMINDER:NOTFORTELECOMMUNICATION (TELEPHONE)NETWORK.
9. Serial/USB Ports to PC TheSerialandUSBportsallowconnectionand communicationbetweenthecomputerandtheUPS unit.Note:Onlyoneportcanbeusedatatime.
10. TVSS Screw UsetheTransientVoltageSurgeSuppressionScrew togroundtheUPS.
11. SNMP/HTTP Network Slot Removethecoverpaneltoinstallanoptional RMCARDtoremotelymonitorandmanageyour UPSoveranetwork.
12. Circuit Breaker LocatedonthebackoftheUPS,thecircuitbreaker providesoverloadandfaultprotection.
13. AC Input Power Cord Heavydutypowercord.
14. Battery and Surge Protected Outlets Theunithassixbatterypowered/surgesuppression outletsforconnectedequipmenttoensure temporaryuninterruptedoperationofyour equipmentduringapowerfailure.(DONOTpluga laserprinter,papershredder,copier,spaceheater, vacuum,sumppumporotherlargeelectrical devicesintothe”BatteryandSurgeProtected Outlets”.Thepowerdemandsofthesedevicesmay overloadanddamagetheunit.)
REPLACING THE BATTERY
ReplacementofbatterieslocatedinanOPERATOR ACCESSAREA.PleasereadandfollowtheSafety Instructionsbeforeservicingthebattery.
CAUTION!RISKOFEXPLOSIONIFBATTERYIS REPLACEDBYANINCORRECTTYPE.DISPOSE OFUSEDBATTERIESACCORDINGTOLOCAL REGULATIONS.
CAUTION!Whenreplacingbatteries,replacewith thesamenumber,manufacturerandmodelname ofthebatteries:CyberPower/RB1270X2Ffor PR750LCD3C.ContactCyberPowerSystemsoryour dealerformoreinformationaboutreplacement batteries.
CAUTION! Riskofenergyhazard,24V,maximum 7AmperehourbatteryforPR750LCD3C;.Before
replacingbatteries,removeconductivejewelrysuch aschains,wristwatches,andrings.Highenergy throughconductivematerialscouldcausesevere burns.
CAUTION! Batteriesareconsideredhazardouswaste andmustbedisposedofproperly.Contactyour localgovernmentformoreinformationaboutproper disposalandrecyclingofbatteries.Donotdisposeof batteriesinafire.Thebatteriesmayexplode.
CAUTION! Donotopenormutilatebatteries. Releasedmaterialisharmfultotheskinandeyes.It maybetoxic.
CAUTION!Toavoidelectricshock,turnofftheunit andunplugitfromtheACpowersourcesbefore servicingthebattery.
REPLACING THE BATTERY – continued
CAUTION!Onlyusetoolswithinsulatedhandles.Do notlaytoolsormetalpartsontopofUPSorbattery terminals.
BATTERY REPLACEMENT PROCEDURE:
PR750LCD3C
1. Turnoffandunplugallconnectedequipment.
2. TurntheUPSoffandunplugitfromtheAC powersource.
3. Pushthebuckleandremovethefrontpanelof theUPS.
4. Loosenthescrewandremovethebattery compartmentplate.
5. Removethebatteriesfromthecompartment.
6. Disconnectthebatterywiresfromthebatteries.
7. Installthereplacementbatteriesbyconnecting thewirebundle(composedofoneredwire andoneblackwire)totheconnectorfromthe batterypack.
8. Putthebatteriesbackintothecompartment.
9. Reinstallthebatterycompartmentplateand tightenthescrewbackintoplace.
10.PutthefrontpanelbackontheUPS.
11. ConnecttoACpowerandchargethenew batteriesforupto8hourstoinsureafullcharge.
PUSH
LCD SETTING GUIDE
PressMenuButtontoenterSetupMenuanduseUp/Down Buttontoscrollthroughmenus.PressEnterButtontogointo theselectedmenuandusetheUp/DownButtonandEnter Buttontoselectthesettingitemandtocompletethesetting. EscButtonispressedtoexitthesubmenuandgobackto previouspage.
Formoreinformationaboutfunctionssetup,pleasereferto theFunctionSetupGuide.
Menu Esc
Enter
Menu BasicSetup
AmbientSetup OutletControl Test Logs
About
UtilityQuality Sensitivity
Item
ECOOn/Off LEDBrightness
UPSConfiguration
SelfTest
Event110
UPSModelName UPSSerialNumber LastBatteryChangeDate NextBatteryChangeDate
LCDHibernation CyclingDisplay
AlarmTest
UPSFirmwareVersion IPAddress MACID
AudibleAlarm ServicePortnumber
LCD SETTING GUIDE – continued
Menu
Item
AdvancedSetup
OutputVoltage MinimumOutputVoltage MaximumOutputVoltage LowBatteryThreshold
BatteryChangeDate ScheduleTest DateandTime PowerMeterRest IPAccess IPAddress
SubnetMask Gateway WiringFault FirmwareUpdate** BacktoDefault
**Onlydisplayedinstandby mode
TROUBLESHOOTING
Problem
Possible Cause
Solution
Circuitbreakerbuttonis projectingfromthebackofthe unit.
TheUPSdoesnotperform expectedruntime.
Circuitbreakerhastrippeddueto anoverload.
TurntheUPSoffandunplugat leastonepieceofequipment. Wait10seconds,resetthecircuit breakerbypressingthebuttonin, andthenturntheUPSon.
Batteriesarenotfullycharged.
Rechargethebatterybyleaving theUPSpluggedin.
Batteriesarewornout.
ContactCyberPowerSystems aboutreplacementbatteries.
Thepowerbuttonisdesigned topreventdamagefromrapidly turningitoffandon.
TurntheUPSoff.Wait10seconds andthenturntheUPSon.
TheUPSwillnotturnon.
TheunitisnotconnectedtoanAC Theunitmustbeconnectedtoa
outlet.
120V50/60Hzoutlet.
Batteriesarewornout.
ContactCyberPowerSystems aboutreplacementbatteries.
Mechanicalproblem.
ContactCyberPowerSystemsfor repair.
PowerPanel®Businessisinactive.
TheUSB/serialcableisnot connected.
TheUSB/serialcableisconnected tothewrongport.
ConnecttheUSB/serialcableto theUPSunitandanopenUSB/ serialportonthebackofthe computer.
Checkthebackofthecomputer foranadditionalUSB/serialport. Movethecabletothisport.
Overload
Removeexcessiveloadandrestart theUPS.
TheFaultLEDisilluminated.
OutputShort BatteryOvercharge
ContactCyberPowerSystems. ContactCyberPowerSystems.
OverTemperature
ContactCyberPowerSystems.
Additionaltroubleshootinginformationcanbefoundatwww.cyberpowersystems.com/support.
TECHNICAL SPECIFICATIONS
MODEL Capacity(VA) Capacity(Watts) INPUT NominalInputVoltage InputFrequencyRange InputPlugType OUTPUT OutputReceptacles
OnBatteryOutputVoltage
OnBatteryOutputFrequency TransferTime(Typical) OverloadProtection SURGE PROTECTION AND FILTERING Lightning/SurgeProtection BATTERY ReplaceableBatteryPack SealedMaintenanceFree RechargeTime(Typical) WARNING DIAGNOSTICS Indicators AudibleAlarms ENVIRONMENTAL OperatingTemperature OperatingRelativeHumidity StorageTemperature StorageRelativeHumidity MANAGEMENT ConnectivityPorts RemoteMonitoring Software SNMP/HTTPNetworking Software PHYSICAL Dimensions(WxHxD)(in/mm) Weight(lb/kg) SAFETY ConformanceApprovals
PR750LCD3C 750 750
100Vac125Vac 50/60Hz+/3HzAutosensing
NEMA515P
(6)NEMA515R 120Vac+/5% (Underatestloadoflessthan60%.Whentheloadexceeds60%, theoutputvoltagerangemayexceed5%.) 50/60Hz+/1% Typical4ms(Atnormalsensitivity) InternalCurrentLimiting
Yes(1,350J)
RB1270X2F Yes
8hoursto90%(Recoverto90%afterfullloaddischarge)
LCDDisplay,LEDIndicators(PowerOn,Online,OnBattery,UPSFault,BatteryFault) OnBattery,BatteryLow,Overload,UPSFault,ReplaceBattery
32°Fto104°F(0°Cto40°C) 0to95%Noncondensing
5°Fto113°F(15°Cto45°C) 0to95%Noncondensing
(1)USBPort,(1)SerialPort BuiltinCloudcard PowerPanelCloud
Yes,withoptionalRMCARD205/400 PowerPanel®Business
138x162x360(mm)/5.43×6.37×14.17(in) 11.8kg/26.01lbs
UL1778,CSAC22.2No.107.3,andFCCClassB
NETWORK OPERATION
Local Monitoring ConnecteithertheUSBcableorSerialcabletothecorrespondingportontheUPSandonthecomputerwith PowerPanelBusinesssoftwareinstalled.PowerPanelBusinesssoftwareisavailableonourwebsite.Pleasego towww.cyberpowersystems.com/products/software/powerpanelbusinessforthefreedownload. Note:USBandSerialportcannotbeusedsimultaneously.SerialportwillbedisablediftheUSBportisused.
Remote Monitoring
ThisproductisequippedwithaSNMP/HTTPnetworkslot.IfyouwouldliketocontroltheUPSfromaremote location,especiallyunderaprivatenetwork,aCyberPowerRemoteManagementCard(RMCARD)isrequired. Formoreinformation,visitwww.cyberpowersystems.com.
Cloud Monitoring
ThisproductfeaturesanEthernetportforCloudConnection,whichmakesiteasytomonitorCyberPower UPSsystemsfromanywhere.FollowbelowstepstogetyourUPSonCloud.
1. Hardwareinstallation:ConnecttheCloudMonitoring(EthernetPort)ontheUPSrearpaneltoawalljack ornetworkswitchusingasuitableEthernetcable.
LED Indicators
Conditions
Link
Off
TheUPSisnotconntectedtothenetwork
On(Yellow) TheUPSisconnectedtothenetwork.
Off
TheCloudMonitoring(EthernetPort)isnotpowered.
Tx/Rx On(Green) TheCloudMonitoring(EthernetPort)ispowered.
Flashing
Receivingortransmittingdatapacket.
2. Applicationinstallation:InstallPowerPanelCloudApponyoursmartphoneandthenlaunchthe application.PowerPanelCloudAppisavailablefordownloadontheAppleAppStoreorGooglePlay.
iOS
Android
3. Signupandlogin.
NETWORK OPERATION – continued
4. AddadeviceinthePowerPanelCloudApp. (a) Click”+”intheupperrightcornerofthehomepage.
(b) Locatethe”AddDevicebyQRCode”toaddyourCloudUPS. (c) ScantheQRCodeonthetopsideoftheUPS.IftheQRCodescanwassuccessful,click”Add”
andnamethedeviceyouaremonitoring. (d) Afterthesetupiscompleted,youwillseeyourdeviceonthehomepage.
(e) WaittilltheUPSissuccessfullyconfigured.
5. StartmonitoringyourUPS! InadditiontotheMobileApp,youcanaccessthePowerPanelCloudaccountviaawebbrowser: https://powerpanel.cyberpower.com.Formoreinformation,pleaserefertothePowerPanelCloudUser’sManual.
CYBERPOWER GREENPOWER UPSTM TECHNOLOGY
Advanced Energy-Saving Patented Bypass Technology
CyberPower’spatentedGreenPowerUPSTMwithBypassTechnologyreducesUPSenergy
costsbyupto75%comparedtoconventionalUPSmodels.Evenwhenutilitypoweris
normal,conventionalUPSmodelsconstantlypasspowerthroughatransformer.Bycon trast,undernormalconditionstheadvancedcircuitryofaGreenPowerUPSTMbypasses thetransformer.Asaresult,thepowerefficiencyissignificantlyincreasedwhilede
GREENPOWER UPSTM
EnergySavingTechnology
creasingwasteheat,usinglessenergy,andreducingenergycosts.Whenanabnormal
powerconditionoccurs,theGreenPowerUPSTMautomaticallyrunspowerthroughitstransformertoregulate
voltageandprovide”safe”power.Sinceutilitypowerisnormalover88%ofthe
time,theGreenPowerUPSTMoperatesprimarilyinitsefficientbypassmode.TheGreenPowerUPSTMisalso
manufacturedinaccordancewiththeRestrictiononHazardousSubstances(RoHS)directivemakingitone
ofthemostenvironmentallyfriendlyonthemarkettoday.
FCC COMPLIANCE STATEMENT
Thisdevicecomplieswithpart15oftheFCCrules.Operationissubjecttothefollowingtwoconditions: (1)thisdevicemaynotcauseharmfulinterference,and(2)thisdevicemustacceptanyinterference received,includinginterferencethatmaycauseundesiredoperation. Note:ThisequipmenthasbeentestedandfoundtocomplywiththelimitsforaClassBdigitaldevice,pursuantto part15oftheFCCRules.Theselimitsaredesignedtoprovidereasonableprotectionagainstharmfulinterferenceina residentialinstallation.Thisequipmentgenerates,uses,andcanradiateradiofrequencyenergyand,ifnotinstalledand usedinaccordancewiththeinstructions,maycauseharmfulinterferencetoradiocommunications.However,thereis noguaranteethatinterferencewillnotoccurinaparticular installation.Ifthisequipmentdoescauseharmfulinterferencetoradioortelevisionreception,whichcanbedetermined byturningtheequipmentoffandon,theuserisencouragedtotrytocorrecttheinterferencebyoneormoreofthe followingmeasures: Reorientorrelocatethereceivingantenna. Increasetheseparationbetweentheequipmentandreceiver. Connecttheequipmenttoanoutletonacircuitdifferentfromthattowhichthereceiverisconnected. Consultthedealeroranexperiencedradio/TVtechnicianforhelp. Warning:Changesormodificationsnotexpresslyapprovedbythepartyresponsibleforcompliancecouldvoidthe user’sauthoritytooperatetheequipment.
Canadian Compliance Statement CANICES3(B)/NMB3(B)
LIMITED WARRANTY AND CONNECTED EQUIPMENT GUARANTEE
Pleasevisitwww.CyberPowerSystems.comforacopyoftheLimitedWarrantyandConnectedEquipment Guarantee.
Where Can I Get More Information?
TheapplicationoftheUnitedNationsConventionofContractsfortheInternationalSaleof Goodsisexpresslyexcluded.CyberPoweristhewarrantorunderthisLimitedWarranty. ForfurtherinformationpleasefeelfreetocontactCyberPowerat: CyberPowerSystems(USA),Inc.424112thAveE.,STE400,Shakopee,MN55379; callusat(877) 297-6937;orsubmitawebticketonlineatcyberpowersystems.com/support.
CyberPowerSystems(USA),Inc.encouragesenvironmentallysoundmethodsfordisposal andrecyclingofitsUPSproducts.Pleasedisposeand/orrecycleyourUPSandbatteriesin accordancetothelocalregulationsofyourstate.
WARNING:ThisproductcanexposeyoutochemicalsincludingbisphenolA(BPA)andstyrene,whichisknowntothe StateofCaliforniatocausereproductiveharmandcancer.Formoreinformation,gotowww.P65Warnings.ca.gov.
©2024CyberPowerSystems(USA),Inc.PowerPanel®isaregisteredtrademarksofCyberPowerSystems(USA),Inc. Allrightsreserved.Allothertrademarksusedarepropertyoftheirrespectiveowners.
K01000099102
Documents / Resources
![]() |
CyberPower PR750LCD3C Smart App Sinewave UPS [pdf] User Manual PR750LCD3C, PR750LCD3C Smart App Sinewave UPS, PR750LCD3C, Smart App Sinewave UPS, App Sinewave UPS, Sinewave UPS |