This document describes the protocol detail of Modbus for V-PR100

✓ Hardware interface

  • The interface on the sensor is RS-232
  • Hardware named RX, TX, GND

✓ RS-232 Slave Address, Baud rate, Data format

  • Slave Address : 1~247
  • Baud rate : 9600, 19200, 38400, 57600, 115200
  • Parity : None, Even
  • Data length : 8 bit
  • Stop bit : 1 bit
  • Default Address = 28, Data format = 115200, N81

✓ About Modbus (ref PI-MBUS-300)

  • Support RTU mode
  • Bit addressable items (i.e. Coils and Discrete inputs) will not be implemented
  • Measurement Values are represented in IEEE 754 single-precision 32-bit floating point type
  • Modbus protocol structure :
    • 1st byte : Address (1~247)
    • 2nd byte : Function code (1 byte)
    • 3~Nth bytes : Data bytes
    • N+1th ~ N+2th byte : CRC (16 bits), LSB first

Outline

Using purpose : It is used to measure the height of internal storage such as factory, farm water tank, swimming pool, industrial water, grain warehouse, silo, etc. The sensor emits electromagnetic waves to analyze reflected waves and travel time to measure the height of the stored object (an object made of water, liquid, grain, powder, etc.).

How to use : Fix the product to the ceiling, and Power supply to the product. Use the Modbus-RTU serial communication method to know the height of the reservoir, the distance to the reservoir, and the strength of the reflected signal. The same information can be found in images visualized through the BLE Android App via wireless communication.

ATTACHMENT POSITION : Assemble the V-PR100 to the casing and screw it into a tank, silo, or outdoor ceiling structure. Installation must be at least 200mm apart from the wall.

Instrument Holding Registers for application engineering

(ex: ModScan) 

Item

No.

Address Address HEX Parameter Point Type Data Type Value
1 0017 0011H Update rate HOLDING REGISTER Unsigned

integer

second
2 0018 0012H Threshold HOLDING REGISTER Unsigned

integer

3 0019 0013H Cutoff meter HOLDING REGISTER Floating Pt. meter
4 0021 0015H Bottom HOLDING REGISTER Floating Pt. meter
5 0023 0017H Distance HOLDING REGISTER Floating Pt. meter
6 0025 0019H Level HOLDING REGISTER Floating Pt. meter
7 0028 001CH Amplitude HOLDING REGISTER Unsigned

integer

Instrument Holding Registers for software engineering

 Item No. StartingAddress  Parameter  R/W  Data Bytes  Point Type  Data Type  Value
Hibyte Lobyte
Information
1 00 00-03 FirmwareVersion R 8bytes HOLDINGREGISTER ASCII
 2  00  04-0B  Serial Number  R  16bytes  HOLDING REGISTER  ASCII
RS-XXX Slave Address, Baudrate, Data format
 3  00  0C  Slave Address  R/W  1byte  HOLDING REGISTER  unsigned integer  1-247
 4  00  0D  Baud rate  R/W  1byte  HOLDING REGISTER  unsigned integer 0 : 96001 : 192002 : 384003 : 576004 : 115200
 5  00  0E  Data type  R/W  1byte  HOLDING REGISTER  unsigned integer  0 : N811 : E81
Measurement value, Setting range
 6  00  0F  Measure_set  R/W  1byte  HOLDING REGISTER  unsigned integer  0  : OFF1  : ON
 7  00  11  Update_rate  R/W  1byte  HOLDING REGISTER  unsigned integer  1~60(second)
 8  00  12  Threshold  R/W  2bytes  HOLDING REGISTER  unsigned integer  50~60000

 

 9  00  13  Cutoff_meter  R/W  4bytes  HOLDING REGISTER  float 0.0 ~ 12.7(meter)
 10  00  14  Bottom  R/W  4bytes  HOLDING REGISTER  float 0.0 ~ 12.7(meter)
 11  00  16  Distance  R  4bytes  HOLDING REGISTER  float 0.0 ~ 12.7(meter)
 12  00  18  Level  R  4bytes  HOLDING REGISTER  float 0.0 ~ 12.7(meter)
 13  00  1A  Detect  R/W  1byte  HOLDING REGISTER  unsigned integer 0  : Default1  : Detect2  : Write
 14  00  1B  Amplitude  R  2bytes  HOLDING REGISTER  unsigned integer  0~60000

 

Item No. Address  Parameter  R/W Data Bytes Point Type Data Type  Value
ADDRDEC ADDRHEX
Information
1 40001 0001H Firmware Version R 8bytes HOLDINGREGISTER ASCII
 2  40005  0005H  Serial Number  R  16bytes  HOLDING REGISTER  ASCII
RS-XXX Slave Address, Baudrate, Data format
 3  40013  000DH  Slave Address  R/W  1byte  HOLDING REGISTER  unsigned integer  1-247
  4   40014   000EH   Baud rate   R/W   1byte  HOLDING REGISTER  unsigned integer 0 : 96001 : 192002 : 384003 : 576004 : 115200
 5  40015  000FH  Data type  R/W  1byte  HOLDING REGISTER  unsigned integer  0 : N811 : E81
Measurement value, Setting range
 6  40016  0010H  Measure_set  R/W  1byte  HOLDING REGISTER  unsigned integer  0  : OFF1  : ON
 7  40017  0011H  Update_rate  R/W  1byte  HOLDING REGISTER  unsigned integer  1~60(second)
 8  40018  0012H  Threshold  R/W  2bytes  HOLDING REGISTER  unsigned integer  50~60000

 

 9  40019  0013H  Cutoff_meter  R/W  4bytes  HOLDING REGISTER  float 0.0 ~ 12.7(meter)
 10  40021  0015H  Bottom  R/W  4bytes  HOLDING REGISTER  float  0.0 ~ 12.7(meter)
 11  40023  0017H  Distance  R  4bytes  HOLDING REGISTER  float  0.0 ~ 12.7(meter)
 12  40025  0019H  Level  R  4bytes  HOLDING REGISTER  float  0.0 ~ 12.7(meter)
13  40027  001BH  Detect  R/W  1byte  HOLDING REGISTER  unsigned integer 0  : Default1  : Detect2  : Write
14 40028 001CH Amplitude R 2bytes HOLDING REGISTER unsigned integer 0~60000

Data format

ASCII format, Item No. 1-2

1st Word 2nd Word 3rd Word 4th Word 5th Word 6th Word 7th Word 8th Word
Hi

byte

Lo

Byte

Hi

byte

Lo

Byte

Hi

byte

Lo

Byte

Hi

byte

Lo

Byte

Hi

byte

Lo

Byte

Hi

byte

Lo

Byte

Hi

byte

Lo

Byte

Hi

byte

Lo

Byte

“ABCDEF0123456789” is represented as

<41><42><43><44><45><46><30><31><32><33><34><35><36><37><38><39>

IEEE754 format, Item No. 9-12

Data Hi Word, Hi Byte Data Hi Word, Lo Byte Data Lo Word, Hi Byte Data Lo Word, Lo Byte
SEEE EEEE EMMM MMMM MMMM MMMM MMMM MMMM

Where

S represents the sign bit where 1 is negative and 0 is positive.
E is the two’s complement exponent with an offset of 127 i.e. an exponent of zero is
represented by 127, an exponent of 1 by 128 etc.
M is the 23-bit normal mantissa. The highest bit is always 1 and, therefore, is not stored

Using the above format the floating point number 12.7 is represented as <41><4B><33><33>:

Data Hi Word, Hi Byte Data Hi Word, Lo Byte Data Lo Word, Hi Byte Data Lo Word, Lo Byte
0x41 0x4B 0x33 0x33

Communication Examples

Read Distance Measurement Value

Request the host (PC or PLC) to polling the data of V-PR300
Field Name Value Type Byte
Slave Address 1~247 Byte 1
Read Holding registers 03 Byte 1
Starting Address Hi 00 Byte 1
Starting Address Lo 16 Byte 1
No. of registers Hi 00 Byte 1
No. of registers Lo 02 Byte 1
CRC Lo CRC Lo Byte 1
CRC Hi CRC Hi Byte 1

*Registers of Distance are 0x0016 ~ 0x0017

Response V-PR300 response data to the host (PC or PLC)
Field Name Value Type Byte
Slave Address 1~247 Byte 1
Read Holding registers 03 Byte 1
Byte Count 04 Byte 1
IEEE 754 Data Lo Word, Hi Byte 0xDD Byte 1
IEEE 754 Data Lo Word, Lo Byte 0x2F Byte 1
IEEE 754 Data Hi Word, Hi Byte 0x40 Byte 1
IEEE 754 Data Hi Word, Lo Byte 0x64 Byte 1
CRC Lo CRC Lo Byte 1
CRC Hi CRC Hi Byte 1

*the floating point number 3.576 is represented as <40><64><2F>

Read Level Measurement Value 

Request the host (PC or PLC) to polling the data of V-PR300
Field Name Value Type Byte
Slave Address 1~247 Byte 1
Read Holding registers 03 Byte 1
Starting Address Hi 00 Byte 1
Starting Address Lo 18 Byte 1
No. of registers Hi 00 Byte 1
No. of registers Lo 02 Byte 1
CRC Lo CRC Lo Byte 1
CRC Hi CRC Hi Byte 1

*Registers of Level are 0x0018 ~ 0019

Response V-PR300 response data to the host (PC or PLC)
Field Name Value Type Byte
Slave Address 1~247 Byte 1
Read Holding registers 03 Byte 1
Byte Count 04 Byte 1
IEEE 754 Data Lo Word, Hi Byte 0xC8 Byte 1
IEEE 754 Data Lo Word, Lo Byte 0xB4 Byte 1
IEEE 754 Data Hi Word, Hi Byte 0x41 Byte 1
IEEE 754 Data Hi Word, Lo Byte 0x26 Byte 1
CRC Lo CRC Lo Byte 1
CRC Hi CRC Hi Byte 1

*the floating point number 10.424 is represented as <41><26>

Read Serial No.

Request the host (PC or PLC) to polling the data of V-PR300
Field Name Value Type Byte
Slave Address 1~247 Byte 1
Read Holding registers 03 Byte 1
Starting Address Hi 00 Byte 1
Starting Address Lo 04 Byte 1
No. of registers Hi 00 Byte 1
No. of registers Lo 08 Byte 1
CRC Lo CRC Lo Byte 1
CRC Hi CRC Hi Byte 1

*Registers of Serial No. are 0x0004 ~ 0x000B

Response V-PR300 response data to the host (PC or PLC)
Field Name Value Type Byte
Slave Address 1~247 Byte 1
Read Holding registers 03 Byte 1
Byte Count 10 Byte 1
1st Word, Lo byte 0x36 Byte 1
1st Word, Hi byte 0x30 Byte 1
2nd Word, Lo byte 0x50 Byte 1
2nd Word, Hi byte 0x30 Byte 1
3rd Word, Lo byte 0x4B Byte 1
3rd Word, Hi byte 0x52 Byte 1
4th Word, Lo byte 0x36 Byte 1
4th Word, Hi byte 0x42 Byte 1
5th Word, Lo byte 0x30 Byte 1
5th Word, Hi byte 0x31 Byte 1
6th Word, Lo byte 0x30 Byte 1
6th Word, Hi byte 0x30 Byte 1
7th Word, Lo byte 0x00 Byte 1
7th Word, Hi byte 0x44 Byte 1
8th Word, Lo byte 0x00 Byte 1
8th Word, Hi byte 0x00 Byte 1
CRC Lo CRC Lo Byte 1
CRC Hi CRC Hi Byte 1

*example of Serial No. is “060PRKB61000D”

Read Firmware Version

Request the host (PC or PLC) to polling the data of V-PR300
Field Name Value Type Byte
Slave Address 1~247 Byte 1
Read Holding registers 03 Byte 1
Starting Address Hi 00 Byte 1
Starting Address Lo 00 Byte 1
No. of registers Hi 00 Byte 1
No. of registers Lo 04 Byte 1
CRC Lo CRC Lo Byte 1
CRC Hi CRC Hi Byte 1

*Registers of Firmware Version are 0x0000 ~ 0x0003

Response V-PR300 response data to the host (PC or PLC)
Field Name Value Type Byte
Slave Address 1~247 Byte 1
Read Holding registers 03 Byte 1
Byte Count 08 Byte 1
1st Word, Lo byte 0x30 Byte 1
1st Word, Hi byte 0x56 Byte 1
2nd Word, Lo byte 0x30 Byte 1
2nd Word, Hi byte 0x30 Byte 1
3rd Word, Lo byte 0x2E Byte 1
3rd Word, Hi byte 0x31 Byte 1
4th Word, Lo byte 0x30 Byte 1
4th Word, Hi byte 0x30 Byte 1
CRC Lo CRC Lo Byte 1
CRC Hi CRC Hi Byte 1

*example of Firmware Version is “V0001.00”

Activation methods

Default Communication setting

Default Address = 28, Baudrate : 115200, N81
Measure set : 0 (0 : Not measure, 1 : Measure)
Update rate : 1 sec (distance, level, amplitude value out rate)
Threshold : 100 (Radar measure minimum value set)
Cutoff meter : 0.3 meter (Range that doesn’t matter if you don’t measure it)
Bottom Level : 12.4 meter (12.7 – cutoff meter)
Detect : 0 (1 : Bottom distance detect, 2 : Write Bottom distance)

Activation methods
[Fig 1. Distance level differentiation]

Measurement value explanation

Cutoff meter : Range that doesn’t matter if you don’t measure it. (@Fig 1 – d1)
Bottom : The distance from V-PR300 model’s antenna to floor. (@ Fig 1 – d5)
Distance : The distance from V-PR300 model’s antenna to object target. (@ Fig 1 – d2)
Level : The distance from the object to floor. (@ Fig 1 – d3)
Amplitude : The radar’s signal intensity. (high value is high signal intensity)
Threshold : Set the radar’s minimum signal intensity. (To detect the object target except for noise signals)

  • Bottom value (d5) = d6 – d1(cutoff meter)
  • Distance value (d2) = d4 – d1(cutoff meter)

Methods activation (know the distance to floor or not)

  1. When know the distance to the floor
    1. Set the parameter “detect(starting address : 001A)” value ‘2’ to write bottom value.
    2. Write the floor distance value ‘X.XXX’(IEEE 754 floating pt. ex. 10.8, the unit is ‘meter’) value to parameter “bottom(starting address : 0014)”.
    3. Write the cutoff meter value ‘X.XXX’(IEEE 754 floating pt. ex. 1.0, the unit is ‘meter’) value to parameter “Cutoff_meter(starting address : 0013)”.
    4. When the setting is done, set the parameter “Measure_set(starting address : 000F)” value ‘1’ to radar activation.
  2. If Need to measure the distance to the floor
    1. Please empty the contents inside the tank(or silo) to detect floor distance exactly.
    2. Write the cutoff meter value ‘X.XXX’(IEEE 754 floating pt. ex. 1.0, the unit is ‘meter’) value to parameter “Cutoff_meter(starting address : 0013)”.
    3. Set the parameter “detect(starting address : 001A)” value ‘1’ to detect floor distance.
    4. During detect floor distance, do not communicate to V-PR300, there be required few seconds.
    5. After detect floor distance, the ‘Bottom’ distance value would be change(starting address : 0014)” automatically.
    6. Also set the parameter “Measure_set(starting address : 000F)” value ‘1’ automatically.

Exception error code

*Exception code is 36(decimal), 0x24(HEX). 

*If it is out of the range the system setting value, the corresponding exception] code(0x24) is place to Function code.
e.g. cutoff meter set the range between 0.3 to bottom value. if cutoff meter set to ‘0.2’ is out of the range, the result is <24><00 <00>.

FCC Approval

This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:

  1. This device may not cause harmful interference, and
  2. this device must accept any interference received, including interference that may cause undesired operation.

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

  • Reorient or relocate the receiving antenna.
  • Increase the separation between the equipment and receiver.
  • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
  • Consult the dealer or an experienced radio/TV technician for help.

Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate this equipment.

This device should be installed and operated with minimum 20Cm between the radiator and your body

INTEGRATION INSTRUCTIONS

List of applicable FCC rules
This module complies with Part 15.247, 15.255 of the FCC rules.

Summarize the specific operational use conditions
This module contains the 60GHz Object detection Sensor.
15.255(a) Operation under the provisions of this section is not permitted for the following products:

  1. Equipment used on satellites.
  2. Field disturbance sensors, including vehicle radar systems, unless the field disturbance sensors are employed for fixed operation, or used as short-range devices for interactive motion sensing. For the purposes of this section, the reference to fixed operation includes field disturbance sensors installed in fixed equipment, even if the sensor itself moves within the equipment.

The module is limited to installation in fixed applications only.

Limited module procedures
Not applicable

Trace antenna designs
Not applicable

RF exposure considerations
This module complies with FCC RF radiation exposure limits set forth for an uncontrolled environment. This device should be installed and operated with minimum 20Cm between the radiator and your body. The host manual shall include the RF exposure statements.
If RF exposure statements and use conditions are not provided, then the host product manufacturer is required to take responsibility of the module through a change in FCC ID (new application).

Antennas
The chip antenna is permanently attached internal PCB.

Label and compliance information
The module is labeled with its own FCC. If the FCC ID is not visible when the module is installed inside another device, then the outside of the device into which the module is installed must also display a label referring to the enclosed module. In that case, the final end product must be labeled in a visible area with the following: “Contains FCC ID: 2A8FDVPR100”
The host manual shall include the following regulatory statement:
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:

  1. This device may not cause harmful interference, and
  2. this device must accept any interference received, including interference that may cause undesired operation.

Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate this equipment.
This device should be installed and operated with minimum 20Cm between the radiator and your body.

Information on test modes and additional testing requirements
Testing of the host product with all the transmitters installed – referred to as the composite investigation test- is recommended, to verify that the host product meets all the applicable FCC rules. The host manufacturer can use the software to control the RF signal during test.
For more information, please contact us.

Additional testing, Part 15 Subpart B disclaimer
The modular transmitter is only FCC authorized for the specific rule parts (i.e., FCC transmitter rules) listed on the grant, and that the host product manufacturer is responsible for compliance to any other FCC rules that apply to the host not covered by the modular transmitter grant of certification.
The host product may need to be evaluated against the FCC Part 15B criteria for unintentional radiators in order to be properly authorized for operation as a Part 15 digital device.

Note EMI Considerations
Note that a host manufacture is recommended to use D04 Module Integration Guide recommending as “best practice” RF design engineering testing and evaluation in case non-linear interactions generate additional non-compliant limits due to module placement to host components or properties.

How to make changes
only Grantees are permitted to make permissive changes.
For more information, please contact us.

Additional testing, Part 15 Subpart B disclaimer
The modular transmitter is only FCC authorized for the specific rule parts (i.e., FCC transmitter rules) listed on the grant, and that the host product manufacturer is responsible for compliance to any other FCC rules that apply to the host not covered by the modular transmitter grant of certification.
The host product may need to be evaluated against the FCC Part 15B criteria for unintentional radiators in order to be properly authorized for operation as a Part 15 digital device.

Revision History

  • V1 2022. 09. 30 Initial
  • V1.1 2022. 11. 29 First Revision FCC rules attached