Brainchild E62 PID Temperature Controller

Overview & Appearance

Keys and Displays
KEYPAD OPERATION
SCROLL KEY: ![]()
This key is used to select a parameter to be viewed or adjusted.
UP/Increase KEY:
This key is used to increase the value of the selected parameter.
DOWN/Decrease KEY: ![]()
This key is used to decrease the value of the selected parameter.
SHIFT KEY:
This key is used to:
- Move to the digit of the selected parameter and change the value by using up or down key to increase or decrease the value.
Scroll Up: ![]()
Two keys pressed synchronously are used to:
- Go to the previous parameter
RESET: + ![]()
Two keys pressed synchronously are used to:
- Revert the display to the home screen.
- Reset a latching alarm once the alarm condition is removed.
- Stop manual control mode, Auto-Tuning mode or calibration mode.
- Clear an Auto-Tuning or communication error message.
- Enter the manual control menu if a failure mode occurs.
Scroll Down: ![]()
Two keys pressed synchronously directly go to the Manual control mode
ENTER KEY: ![]()
Press
and hold for 5 seconds or longer to:
- Enter the Auto-Tuning mode.
The display will show. - Enter the manual control mode.
The display will show.
Enter the setup menu mode.
The display will show.
Perform calibration of a selected parameter during the calibration procedure. The display will show
Menu Flowchart
The Menu has been divided into 5 groups. They are as follows:
- User Menu
- Auto-Tuning Mode Menu
- Manual Mode Menu
- Setup Menu
- Calibration Mode Menu

- Press
for the next parameter ; Press
and
key to return to the previous parameter. - Press and hold
for 3.1 seconds, then let go to select auto tuning mode. - Press and hold
for 4.2 seconds, then let go, to select manual control mode. - Press and hold
for 5.3 seconds, then let go to select setup mode. - Press and hold
for 6.4 seconds, then let go to select calibration mode.
User Menu
Use
key to enter basic menu parameters, and press
again to select SP1, SEL1~SEL8.
Press ![]()
to return to the previous.

Auto-Tuning Mode
Press
key 5 seconds to activate Auto-Tuning Mode

Manual Mode Menu
Press
key 3 seconds to execute the selected default program

Enter Manual Control Mode; refer to Manual 6.1 & 6.8.2~6.8.4

Setup Menu
The setup menu has been categorized into eight categories.
They are listed as below.
- Basic Menu (bASE)
- Output Menu (oUT)
- Communication Menu (CoMM)
- User Select Menu (SEL)
Basic Menu (bASE)
Use
or
key to get bASE in the lower display then use
key to enter to basic menu parameters.

Output Menu (oUT)
Use
or
key to get oUT in the lower display then use
key to enter to output menu parameters.

Communication Menu (CoMM)
Use
or
key to get CoMM in the lower display then use
key to enter to communication menu parameters.
Please note that confirm A2FN set to CoMM when using communication.

User Select Menu (SEL)
Use
or
key get SEL in the lower display then use
key to enter to select the user menu parameters.

Calibration Mode

Press
key for 2 seconds or longer (not more than 3 seconds) ; then release it to enter calibration Mode.
Press
key for 5 seconds to perform calibration
- Please note that it is required to use specialized equipment to apply calibration, attempting to change will affect device accuracy
Note:
- Using Manual, Auto-Tuning, Calibration modes will break the control loop and change some of the previous setting data. Make sure that the system is allowable to apply these modes.
- The flow chart shows a complete list of all parameters. For actual application, the number of available parameters will vary depending on the setup and model of the controller and will be less than that shown in the flow chart.
- The user can select up to 8 parameters to put in the user select menu by using the SEL1~SEL8 parameters in the setup menu
Before you Start, Setup Input/Output
After power-up, press and hold
for 5.3 seconds, then let go to enter Setup Menu. Complete Parameter setting, INPT, UNIT, DP, O1TY, O1L and O1H.
- Enter the Setup Menu. Press
for 5 seconds to enter Basic Menu (bASE). Finish setting for INPT, UNIT and DP. Exit the level. - Return to the Setup Menu. Press
for 5 seconds to enter Output Menu (oUT). Finish setting for O1TY, O1L and O1H. Press and hold
and return to homepage.

OP1L/ OP1H Table
| Range | OP1L | OP1H | |
| OM9A-3 | 4-20 | 20.0 | 100.0 |
| OM9A-3 | 0-20 | 0.0 | 100.0 |
| OM9A-5 | 0-5V | 0.0 | 50.0 |
| OM9A-5 | 1-5V | 10.0 | 50.0 |
| OM9A-5 | 0-10 | 0.0 | 100.0 |
* When O1TY as DC.MA or DC. Vo, set the value based on usage requirement
Terminal Connection

Parameter Notation
User Menu Parameter
| Modbus | Parameter | Description | Range | Default | Access | |
| 0 | SP1 | Set Point 1 | Low: SP1L
High: SP1H |
25.0 °C | R/W | |
| 64 | PV | Process value | Low: -19999
High: 45536 |
(77.0 °F) | R | |
| 65 | SV | Current set point value | Low: SP1L
High: SP1H |
—— | R | |
| 44 |
SEL1 |
Select 1st parameter for user menu | 0 NONE
1 A1SP 2 A2SP 3 LOCK 4 INPT 5 PB 6 TI |
7 TD
8 SHIF 9 OFST 10 O1HY 11 A1HY 12 A2HY 13 ADDR |
—— | R/W |
| 45 | SEL2 | Select 2nd parameter | Select 2nd parameter for user manual. Same as the SEL1 | 0 | R/W | |
| 46 | SEL3 | Select 3rd parameter | Select 3rd parameter for user manual. Same as the SEL1 | 0 | R/W | |
| 47 | SEL4 | Select 4th parameter | Select 4th parameter for user manual. Same as the SEL1 | 0 | R/W | |
| 48 | SEL5 | Select 5th parameter | Select 5th parameter for user manual. Same as the SEL1 | 0 | R/W | |
| 49 | SEL6 | Select 6th parameter | Select 6th parameter for user manual. Same as the SEL1 | 0 | R/W | |
| 50 | SEL7 | Select 7th parameter | Select 7th parameter for user manual. Same as the SEL1 | 0 | R/W | |
| 51 | SEL8 | Select 8th parameter | Select 8th parameter for user manual. Same as the SEL1 | 0 | R/W | |
Manual Mode Parameter
| Modbus | Parameter | Description | Range | Default | Access |
| 66 | MV1 | Output 1 %Value | Low: 0.00
High: 100.00 % |
—– | R (R/W,
Manual) |
Basic (bASE) Parameter
| Modbus | Parameter | Description | Range | Default | Access |
| 3 | LOCK | Select parameters to be locked | 0 None: No parameter is locked
1 SEt: Setup data are locked 2 uSEr: Setup data and user data are locked. SetPoint are unlocked. 3 ALL: All data are locked |
0 | R/W |
| 4 | INPT | Input sensor selec- tion | 0 J_tC: J type Thermocouple
1 K_tC: K type Thermocouple 2 t_tC: T type Thermocouple 3 R_tC: R type Thermocouple 4 S_tC: S type Thermocouple 5 Pt. dN: PT 100 DIN 6 Pt.JS: PT 100 JIS |
1 | R/W |
| 5 | UNIT | Input unit selection | 0 oC: °C unit
1 oF: °F unit |
0 | R/W |
| 6 | DP | Decimal point selec- tion | 0 No.dP: no decimal point
1 1-dP: 1 decimal point |
1 |
R/W |
|
9 |
SP1L |
Low limit of set point value | Low:
J_TC: -120.0°C (-184.0°F) K_TC: -200.0°C (-328.0°F) T_TC: -250.0°C (-418.0°F) R_TC: 0.0°C ( 32.0°F) S_TC: 0.0°C ( 32.0°F) PTDN: -200.0°C (-328.0°F) PTJS: -200.0°C (-328.0°F) High: SP1H |
-17.8 °C
(0.0 °F) |
R/W |
| 10 |
SP1H |
High limit of set point value | Low: SP1L
High: J_TC: 1000.0°C (1828.0°F) K_TC: 1370.0°C (2498.0°F) T_TC: 400.0°C ( 752.0°F) R_TC: 1767.7°C (3214.0°F) S_TC: 1767.7°C (3214.0°F) PTDN: 850.0°C (1562.0°F) PTJS: 600.0°C (1112.0°F) |
537.8 °C
(1000.0 °F) |
R/W |
| 12 | FILT |
Filter damping time constant of PV |
0 0: 0 sec time constant
1 0.2: 0.2 sec time constant 2 0.5: 0.5 sec time constant 3 1: 1 sec time constant 4 2: 2 sec time constant 5 15: 5 sec time constant 6 10: 10 sec time constant 7 20: 20 sec time constant 8 30: 30 sec time constant 9 60: 60 sec time constant |
2 | R/W |
| 14 | PB | Proportional band
value |
Low: 0.0
High: 500.0°C (900.0°F) |
10.0 °C
(18.0 °F) |
R/W |
| 15 | TI | Integral time value | Low: 0, High: 3600 sec | 60 | R/W |
| 16 | TD | Derivative time value | Low: 0, High: 360.0 sec | 30.0 | R/W |
| 11 | SHIF | PV shift (offset)
value |
Low: -200.0°C (-360.0°F) High: 200.0°C (360.0°F) | 0.0 °C
(0.0 °F) |
R/W |
| 68 | CICF | CIC filter switch | 0 OFF
1 ON |
0 | R |
Output (oUT) Parameter
| Modbus | Parameter | Description | Range | Default | Access |
| 17 | OUT1 | Output 1 function | 0 REVR: Reverse (heating) control action
1 dIRt: Direct (cooling) control action |
0 | R/W |
| 21 | CYC1 | Output 1 cycle time | Low: 0.1;
High: 90.0 sec. |
18.0 | R/W |
| 18 | O1TY | Output 1 signal type | 0 RELY: Relay output
1 SSrd: Solid state relay drive output 2 DC.MA: DC current 3 DC.Vo: DC voltage |
0 | R/W |
| 7 | OP1L | OP1 linear output low limit value | 0.0 ~ OP1H | 0.0 | R/W |
| 8 | OP1H | OP1 linear output
high limit value |
OP1L ~ 110.0 % | 100.0 | R/W |
| 19 | O1FT | Output 1 failure transfer mode | 0~1000: 0.0 ~ 100.0 % to continue output 1
control function if the sensor fails, or select OFF (0) or ON (1) for ON-OFF control |
0.0 | R/W |
| 22 | OFST | Offset value for P
control |
Low: 0
High: 100.0 % |
25.0 | R/W |
| 20 | O1HY | Output 1 ON-OFF
control hysteresis |
Low: 0.1
High: 50.0 °C (90.0°F) |
0.5 °C
(0.9 °F) |
R/W |
| 23 | PL1L | MV1 power value
limit low |
Low: 0
High: 50 % or PL1H |
0 | R/W |
| 24 | PL1H | MV2 power value limit high | Low: PL1L
High: 100 % |
100 |
R/W |
| 25 | A1FN | Alarm 1 function for alarm 1 output | 0 NoNE: No alarm function
1 dE.HI: Deviation high alarm 2 dE.Lo: Deviation low alarm 3 db.HI: Deviation band out of band alarm 4 db.Lo: Deviation band in band alarm 5 PV.HI: Process value high alarm 6 PV.Lo: Process value low alarm |
1 |
R/W |
| Modbus | Parameter | Description | Range | Default | Access |
|
26 |
A1MD |
Alarm 1 operation mode |
0 NoRM: Normal alarm action
1 LtCH: Latching alarm action 2 HoLd: Hold alarm action 3 Lt.Ho: Latching & Hold action |
0 | R/W |
| 29 | A1HY | Alarm 1 Hysteresis control | Low: 0.1
High: 50.0°C (90.0°F) |
0.1 °C
(0.2 °F) |
R/W |
| 34 | A1DL | Alarm 1 delay | Low: 0; High: 5999 sec | 0 | R/W |
| 28 | A1FT | Alarm 1 failure trans- fer mode | 0 oFF: OFF if sensor fails
1 oN: ON if sensor fails |
1 | R/W |
| 1 | A1SP | Alarm 1 set point | A1FN=PVHI/PVLO
Low: SP1L High: SP1H |
100.0 °C
(212.0 °F) |
R/W |
| 13 | A1DV | Alarm 1 deviation value | A1FN=DEHI/DELO/DBHI/DBLO
Low: 0.0 High: 500.0°C (900.0°F) |
10.0 °C
(18.0 °F) |
R/W |
| 33 |
A2FN |
Alarm 2 function for alarm 2 output |
0 NoNE: No alarm function
1 dE.HI: Deviation high alarm 2 dE.Lo: Deviation low alarm 3 db.HI: Deviation band out of band alarm 4 db.Lo: Deviation band in band alarm 5 PV.HI: Process value high alarm 6 PV.Lo: Process value low alarm 7 COMM: RS485 |
2 |
R/W |
|
35 |
A2MD |
Alarm 2 operation mode |
0 NoRM: Normal alarm action
1 LtCH: Latching alarm action 2 HoLd: Hold alarm action 3 Lt.Ho: Latching & Hold action |
0 |
R/W |
| 36 | A2HY | Hysteresis control of alarm 2 | Low: 0.1°C
High: 50.0°C (90.0°F) |
0.1 °C
(0.2 °F) |
R/W |
| 38 | A2DL | Alarm 2 delay | Low: 0; High: 5999 sec | 0 | R/W |
| 37 | A2FT | Alarm 2 failure forced transfer mode | 0 oFF: Alarm output OFF if sensor fails
1 oN: Alarm output ON if sensor fails |
1 | R/W |
| 2 | A2SP | Alarm 2 set point | A2FN=PVHI/PVLO
Low: SP1L High: SP1H |
100.0 °C
(212.0 °F) |
R/W |
| 43 | A2DV | Alarm 2 deviation value | A2FN=DEHI/DELO/DBHI/DBLO
Low: 0.0 High: 500.0°C (900.0°F) |
10.0 °C
(18.0 °F) |
R/W |
Communication (CoMM) Parameter
| Modbus | Parameter | Description | Range | Default | Access |
| 39 | ADDR | Address assignment of digital communication |
Low: 1
High: 255 |
1 | R/W |
| 40 | BAUD | Baud rate of digital communication | 0 2.4: 2.4 Kbits/s baud rate
1 4.8: 4.8 Kbits/s baud rate 2 9.6: 9.6 Kbits/s baud rate 3 14.4: 14.4 Kbits/s baud rate 4 19.2: 19.2 Kbits/s baud rate 5 28.8: 28.8 Kbits/s baud rate 6 38.4: 38.4 Kbits/s baud rate 7 57.6: 57.6 Kbits/s baud rate 8 115.2: 115.2 Kbits/s baud rate |
2 | R/W |
| 41 | DATA | Data bit count of dig- ital communication | 0 7bIt: 7 bit
1 8bIt: 8 bit |
1 | R/W |
| 42 | PARI | The parity bit of digi- tal communication | 0 EVEN: Even parity
1 odd: Odd parity 2 NoNE: No parity bit |
0 |
R/W |
Calibration Mode Parameter
| Modbus | Parameter | Description | Range | Default | Access |
| 52 | ADLO | mV calibration low
coefficient |
Low: -1999
High: 1999 |
—– |
R/W |
| 53 | ADHI | mV calibration high
coefficient |
Low: -1999
High: 1999 |
—– |
R/W |
| 54 | RTDL | RTD calibration low
coefficient |
Low: -1999
High: 1999 |
—– |
R/W |
| 55 | RTDH | RTD calibration high coefficient | Low: -1999
High: 1999 |
—– |
R/W |
| 56 | CJLO | Cold junction calibra-
tion low coefficient |
Low: -5.00
High: 40.00 |
—– |
R/W |
Other Parameter
| Modbus | Parameter | Description | Range | Default | Access |
| 57 | CJCT | Cold Junction Temperature | Low: -4000
High: 9000 |
—– | R |
| 58 | DATE | Date | Low: 0;
High: 65535 |
—– | R |
| 59 | SRNO | Serial Number | Low: 0;
High: 65535 |
—– | R |
| 63 | CJCL | Cold junction low calibration
voltage |
Low: 0
High: 7552 |
—– | R |
| 69 | EROR | Error code | Low: 0; High: 65535 | —– | R |
| 70 | MODE | Operation mode & alarm status | Low: 0
High: 65535 |
—– | R |
| 71 | PROG | Device version, firmware version | 67.XX | —– | R |
| 72 | CMND | Command code | Low: 0; High: 65535 | —– | R/W |
| 73 | JOB1 | Job code | Low: 0; High: 65535 | —– | R/W |
Error Code
| Error Code | Display
Symbol |
Description & Reason |
Corrective Action |
| 10 | ER10 | Communication error: bad function code | Correct the communication software to meet the protocol
requirements |
| 11 | ER11 | Communication error: register address out of range | Do not issue an over-range address of the register to the slave |
| 14 | ER14 | Communication error: attempt to write a
read-only data |
Do not write read-only data or protected data to the slave |
| 15 | ER15 | Communication error: write a value which is out of range to a register | Do not write an over-range data to the slave register |
| 26 | ATER | Auto-Tuning Error: Failed to perform Auto-Tuning function |
|
| 29 | EEPR | EEPROM can’t be written correctly | Return to manufacturer for repair. |
| 30 | CJER | Cold junction compensation for
Thermocouple malfunction |
Return to manufacturer for repair. |
| 39 | SBER | Input sensor break | Replace the input sensor |
| 40 | ADER | A to D converter or related component(s) malfunction | Return to the original manufacturer for repair. |
FAQ
How do I access the User Menu?
How do I activate Auto-Tuning Mode?
How do I enter Manual Control Mode? To enter Manual Control Mode, press the designated key for 3 seconds. How do I perform calibration? To calibrate a parameter, press and hold the ENTER key for 5 seconds during the calibration procedure.
How do I perform calibration?
Documents / Resources
![]() | E62 PID Temperature Controller |
References