Blauberg-logo

Blauberg Turbo EC 200 Mixed Flow Inline Fans

Blauberg-Turbo-EC-200-Mixed-Flow-inline-Fans-product

Product Specifications

  Unit of measurement  

Turbo EC 200

Connected air duct size mm 200
Speed 1
Phases 1
Minimum supply voltage V 230
Maximum supply voltage V 230
Power supply frequency Hz 50/60
Rated power W 123
Unit current A 1.02
Maximum airflow m3/h 1040
Rotation speed at 50Hz  
Sound pressure level LpA at 3 m dB(A) 49
Weight kg 3.95
Transported air temperature (max) °С 55
Transported air temperature (min) °С -25
Ingress protection rating IPX4

Mixed-flow inline fans with EC-motors

  • Sound pressure level LpA at 3 m: 49
  • Motor type: EC
  • Impeller type: Mixed-flow
  • Casing material: Plastik
  • Installation in any positionBlauberg-Turbo-EC-200-Mixed-Flow-inline-Fans-FIG- (1)Blauberg-Turbo-EC-200-Mixed-Flow-inline-Fans-FIG- (2)

Product Dimensions

ØD B H L ØD1
198 239 277.5 295.5 209

Blauberg-Turbo-EC-200-Mixed-Flow-inline-Fans-FIG- (3)

Ecodesign

Trademark Blauberg
Model Turbo EC 200
 

Specific energy consumption (SEC) (kWh/(m2/a))

Cold Average Warm
54.1 A+ 27.1 B 11.6 E
Type of ventilation unit Unidirectional
Type of drive installed Variable speed
Type of heat recovery system None
Maximum flow rate (m3/h) 910
Electric power input (W) 123
Reference flow rate (m3/s) 0.177
Reference pressure difference (Pa) 50
Specific power input (SPI) (W/(m3/h)) 0.094
Control typology Local demand control
Maximum external leakage rates (%) 2.7
Declared typology RVU UVU
Sound power level (dB(A)) 69
 

The annual electricity consumption (AEC) (kWh/a)

Cold Average Warm
50 50 50
 

The annual heating saved (AHS) (kWh/a)

Cold Average Warm
5536 2830 1280

Installation

  1. Ensure the connected air duct size matches the unit size.
  2. Provide proper electrical connections within the specified voltage range.
  3. Securely mount the unit in a suitable location for optimal airflow.

Operation

  1. Turn on the power supply and select the desired speed setting.
  2. Monitor the airflow and adjust as needed for ventilation requirements.

Maintenance

  1. Regularly clean the unit and the air ducts to ensure efficient operation.
  2. Check for any unusual sounds or performance issues and consult the user manual for troubleshooting.

FAQs

What is the maximum airflow of the Turbo EC 200?

The maximum airflow of the Turbo EC 200 is 1040m3 h.

What is the weight of the Turbo EC 200?

The weight of the Turbo EC 200 is 3.95kg.

Documents / Resources

Blauberg Turbo EC 200 Mixed Flow Inline Fans [pdf] User Guide
200, Turbo EC 200 Mixed Flow Inline Fans, Turbo EC 200, Mixed Flow Inline Fans, Inline Fans, Fans

References

Leave a comment

Your email address will not be published. Required fields are marked *