Beijer-logo

Beijer GT-225F Digital Output Module

Beijer-GT-225F-Digital-Output-Module-product

Specifications

  • Channels: 16
  • Voltage: 24 VDC
  • Current: 0.3 A
  • Type: Sink
  • Terminal: Cage clamp, 18 pt removable

Product Usage Instructions

Installation

  1. Ensure power is off before installation.
  2. Connect the module to the appropriate power source.
  3. Securely fasten the module in place using the provided mounting hardware.

Setup

  1. Refer to the user manual for wiring diagrams specific to your application.
  2. Configure the module settings as needed for your system.

Usage

  1. Apply power to the module.
  2. Monitor the output using the provided software or interface.
  3. Ensure proper functioning of connected devices.

About This Manual

This manual contains information on the software and hardware features of the Beijer Electronics GT-225F Digital Output Module. It provides in-depth specifications, guidance on installation, setup, and usage of the product.

Symbols Used in This Manual
This publication includes Warning, Caution, Note, and Important icons where appropriate, to point out safety-related or other important information. The corresponding symbols should be interpreted as follows:

Beijer-GT-225F-Digital-Output-Module-fig- (1)

Safety

Before using this product, please read this manual and other relevant manuals carefully. Pay full attention to safety instructions!
In no event will Beijer Electronics be responsible or liable for damages resulting from the use of this product.
The images, examples, and diagrams in this manual are included for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Beijer Electronics cannot take responsibility or liability for actual use based on the examples and diagrams.

Product Certifications
The product has the following certifications.

Beijer-GT-225F-Digital-Output-Module-fig- (2)

General Safety Requirements

WARNING

  • Do not assemble the products and wires with power connected to the system. Doing so causes an “arc flash”, which can result in unexpected, dangerous events (burns, fire, flying objects, blast pressure, sound blast, heat).
  • Do not touch terminal blocks or IO modules when the system is running. Doing so may cause an electric shock, a short circuit, or a malfunction of the device.
  • Never let external metallic objects touch the product when the system is running. Doing so may cause an electric shock, a short circuit, or a malfunction of the device.
  • Do not place the product near flammable material. Doing so may cause a fire.
  • All wiring work should be performed by an electrical engineer.
  • When handling the modules, ensure that all persons, the workplace, and the packing are well grounded. Avoid touching the conductive component; the modules contain electronic components that may be destroyed by electrostatic discharge.

CAUTION

  • Never use the product in environments with temperatures over 60℃. Avoid placing the product in direct sunlight.
  • Never use the product in environments with over 90% humidity.
  • Always use the product in environments with pollution degrees 1 or 2.
  • Use standard cables for wiring.

About the G-series System

Beijer-GT-225F-Digital-Output-Module-fig- (3)

System overview

  • Network Adapter Module – The network adapter module forms the link between the field bus and the field devices with the expansion modules. The connection to different field bus systems can be established by each of the corresponding network adapter modules, e.g., for MODBUS TCP, Ethernet IP, EtherCAT, PROFINET, CC-Link IE Field, PROFIBUS, CANopen, DeviceNet, CC-Link, MODBUS/Serial, etc.
  • Expansion Module – Expansion module types: Digital IO, Analog IO, and Special modules.
  • Messaging – The system uses two types of messaging: Service messaging and IO messaging.

IO Process Data Mapping
An expansion module has three types of data: IO data, configuration parameters, and memory registers. The data exchange between the network adapter and the expansion modules is made via an IO process that images data using by internal protocol.

Beijer-GT-225F-Digital-Output-Module-fig- (4)

Data flow between the network adapter (63 slots) and the expansion modules

The input and output image data depend on the slot position and the data type of the expansion slot. The ordering of the input and output process image data is based on the expansion slot position. Calculations for this arrangement are included in the manuals for the network adapter and programmable IO modules.

Valid parameter data depends on the modules in use. For example, analog modules have settings
of either 0-20 mA or 4-20 mA, and temperature modules have settings such as PT100, PT200, and PT500. The documentation for each module describes the parameter data.

Specifications

Environmental Specifications

Operating temperature -20°C – 60°C
UL temperature -20°C – 60°C
Storage temperature -40°C – 85°C
Relative humidity 5% – 90% non-condensing
Mounting DIN rail
Shock operating IEC 60068-2-27 (15 g)
Vibration resistance IEC 60068-2-6 (4 g)
Industrial emissions EN 61000-6-4: 2019
Industrial immunity EN 61000-6-2: 2019
Installation position Vertical and horizontal
Product certifications CE, FCC, UL, cUL

General Specifications

Power dissipation Max. 50 mA @ 5 VDC
Isolation I/O to Logic: Photocoupler isolation

Field power: Non-isolation

UL field power Supply voltage: 24 VDC nominal, Class 2
Field power Supply voltage: 24 VDC nominal Voltage range: 15-30 VDC

Power dissipation: 30 mA @ 24 VDC

Single wiring I/O cable max. 0.75 mm² (AWG 18)
Weight 63 g
Module size 12 mm x 109 mm x 70 mm

Dimensions

Beijer-GT-225F-Digital-Output-Module-fig- (5)

Output Specifications

Output per module 16 points sink type
Indicators 16 green output status
Output voltage range 24 VDC nominal

15 VDC – 30 VDC @ 70 °C

On-state voltage drop 0.3 VDC @ 25 °C

0.5 VDC @ 70 °C

On-state min. current Min. 1 mA
Off-state leakage current Max. 20 uA
Output signal delay OFF to ON: Max. 0.3 ms

ON to OFF: Max 0.5 ms

Output current rating Max. 0.3 A per channel / Max. 4.8 A per unit
Protection Over current limit: Min. 3.5 A @ 25 ℃ per channel Thermal shutdown: Min 3 A @ 25 ℃ per channel

Short circuit protection

Common type 16 points / 2 COM

Wiring Diagram

Beijer-GT-225F-Digital-Output-Module-fig- (6)

Pin no. Signal description
0 Output channel 0
1 Output channel 1
2 Output channel 2
3 Output channel 3
4 Output channel 4
5 Output channel 5
6 Output channel 6
7 Output channel 7
8 Output channel 8
9 Output channel 9
10 Output channel 10
11 Output channel 11
12 Output channel 12
13 Output channel 13
14 Output channel 14
15 Output channel 15
16 Common (Field power 24 V)
17 Common (Field power 24 V)

LED Indicator

Beijer-GT-225F-Digital-Output-Module-fig- (7)

LED no. LED function/description LED color
0 OUTPUT channel 0 Green
1 OUTPUT channel 1 Green
2 OUTPUT channel 2 Green
3 OUTPUT channel 3 Green
4 OUTPUT channel 4 Green
5 OUTPUT channel 5 Green
6 OUTPUT channel 6 Green
7 OUTPUT channel 7 Green
8 OUTPUT channel 8 Green
9 OUTPUT channel 9 Green
10 OUTPUT channel 10 Green
11 OUTPUT channel 11 Green
12 OUTPUT channel 12 Green
13 OUTPUT channel 13 Green
14 OUTPUT channel 14 Green
15 OUTPUT channel 15 Green

Channel Status

Status LED Indicates
Not signal Off Normal operation
On signal Green Normal operation

Mapping Data Into the Image Value

Output Image Value

Bit no. Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Byte 0 D7 D6 D5 D4 D3 D2 D1 D0
Byte 1 D15 D14 D13 D12 D11 D10 D9 D8

Beijer-GT-225F-Digital-Output-Module-fig- (8)

Output Module Data

D7 D6 D5 D4 D3 D2 D1 D0
D15 D14 D13 D12 D11 D10 D9 D8

Parameter Data

Valid parameter length: 4 Bytes

Bit no. Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Byte 0 Fault action (ch0-ch7)

0: Fault value, 1: Hold last state

Byte 1 Fault action (ch8-ch15)

0: Fault value, 1: Hold last state

Byte 2 Fault value (ch0-ch7)

0: Off, 1: On

Byte 3 Fault value (ch8-ch15)

0: Off, 1: On

Hardware Setup

CAUTION

  • Always read this section before installing the module!
  • Hot surface! The surface of the housing can become hot during operation. If the module is used in high ambient temperatures, always let it cool down before touching it.
  • Working on energized devices can damage the equipment! Always turn off the power supply before working on the module.

Space Requirements

The following drawings show the space requirements when installing the G-series modules. The spacing creates space for ventilation and prevents conducted electromagnetic interference from influencing the operation. The installation position is valid vertically and horizontally. The drawings are illustrative and may be out of proportion.

CAUTION
Not following the space requirements may result in damaging the product.

Beijer-GT-225F-Digital-Output-Module-fig- (9)

Mount Module to DIN Rail
The following chapters describe how to mount the module to the DIN rail.

CAUTION
The module must be fixed to the DIN rail with the locking levers.

Mount GL-9XXX or GT-XXXX Module
The following instructions apply to these module types:

  • GL-9XXX
  • GT-1XXX
  • GT-2XXX
  • GT-3XXX
  • GT-4XXX
  • GT-5XXX
  • GT-7XXX

GN-9XXX modules have three locking levers, one at the bottom and two on the side. For mounting instructions, refer to Mount GN-9XXX Module.

Beijer-GT-225F-Digital-Output-Module-fig- (10)

Mount GN-9XXX Module
To mount or dismount a network adapter or programmable IO module with the product name GN-9XXX, for example, GN-9251 or GN-9371, see the following instructions:

Beijer-GT-225F-Digital-Output-Module-fig- (11)

Mount Removable Terminal Block
To mount or dismount a removable terminal block (RTB), see the instructions below.

Beijer-GT-225F-Digital-Output-Module-fig- (12)

Connect Cables to Removable Terminal Block
To connect/disconnect cables to/from the removable terminal block (RTB), see the instructions below.

WARNING
Always use the recommended supply voltage and frequency to prevent damage to the equipment and ensure optimal performance.

Beijer-GT-225F-Digital-Output-Module-fig- (13)

Field Power and Data Pins
Communication between the G-series network adapter and the expansion module, as well as system /field power supply of the bus module, is carried out via the internal bus. It is comprised of 2 Field Power Pins and 6 Data Pins.

WARNING
Do not touch the data and field power pins! Touching can result in soiling and damage from ESD noise.

Beijer-GT-225F-Digital-Output-Module-fig- (14)

Pin no. Name Description
P1 System VCC System supply voltage (5 VDC)
P2 System GND System ground
P3 Token output Token output port of the processor module
P4 Serial output Transmitter output port of the processor module
P5 Serial input The receiver input port of the processor module
P6 Reserved Reserved for bypass token
P7 Field GND Field ground
P8 Field VCC Field supply voltage (24 VDC)

Copyright © 2025 Beijer Electronics AB. All rights reserved.

The information in this document is subject to change without notice and is provided as available at the time of printing. Beijer Electronics AB reserves the right to change any information without updating this publication. Beijer Electronics AB assumes no responsibility for any errors that may appear in this document. All examples in this document are only intended to improve understanding of the functionality and handling of the equipment. Beijer Electronics AB cannot assume any liability if these examples are used in real applications.

In view of the wide range of applications for this software, users must acquire sufficient knowledge themselves in order to ensure that it is correctly used in their specific application. Persons responsible for the application and the equipment must themselves ensure that each application complies with all relevant requirements, standards, and legislation in respect to configuration and safety.

Beijer Electronics AB will accept no liability for any damage incurred during the installation or use of the equipment mentioned in this document. Beijer Electronics AB prohibits all modifications, changeconversionsnsn of the equipment.

Head Office

FAQs

What should I do if the module is not working?

Check the power supply and wiring connections. Ensure that the module is properly configured for your application.

Can I use this module with other G-series components?

Yes, this module is designed to work seamlessly with other G-series components. Refer to the user manual for compatibility details.

Documents / Resources

Beijer GT-225F Digital Output Module [pdf] User Manual
GT-225F, GT-225F Digital Output Module, Digital Output Module, Output Module, Module

References

Leave a comment

Your email address will not be published. Required fields are marked *