GeeekPi 10-inch 2U Rack Mount Fan Unit (Model DR-0006) Instruction Manual

Model: DR-0006

1. Product Overview

The GeeekPi 10-inch 2U Rack Mount Fan Unit is designed to provide active cooling for 10-inch rack systems, specifically compatible with DeskPi RackMate T0/T1/T2/TL1 series. This unit features dual 70mm axial fans and an intelligent control circuit with an NTC temperature sensor to manage airflow and reduce equipment temperatures, enhancing system stability.

It supports both Automatic and Manual fan control modes, allowing dynamic adjustment of fan speeds based on real-time operating temperatures or a fixed speed setting. The integrated 0.96-inch OLED display provides real-time temperature and operational status.

GeeekPi 10-inch 2U Rack Mount Fan Unit front view

Figure 1.1: Front view of the GeeekPi 10-inch 2U Rack Mount Fan Unit, showing the dual fans and control panel.

Product dimensions of the GeeekPi 10-inch 2U Rack Mount Fan Unit

Figure 1.2: Detailed dimensions of the fan unit and individual 70mm fans. The unit measures 250mm (9.84 inches) in length, 88mm (3.46 inches) in height, and 20mm (0.78 inches) in depth. Each fan is 70mm (2.75 inches) square with a 15mm (0.59 inches) thickness.

2. Setup Instructions

2.1 Unpacking and Inspection

Carefully unpack the fan unit and its accessories. Verify that all components listed in the accessory list are present and undamaged.

Accessory list for the GeeekPi 10-inch 2U Rack Mount Fan Unit

Figure 2.1: Included accessories: one temperature sensor and four #10-32 screws (5/16 inch).

2.2 Power Supply Connection

The fan unit requires a DC 12V / 2A power supply, which is not included with the product. Ensure you use a compatible power adapter with an outer diameter of 5.5mm and an inner diameter of 2.1-2.5mm. Connect the power supply to the 'Power' port on the rear panel of the unit.

Rear panel of the fan unit showing power input and NTC probe connection

Figure 2.2: Rear panel connections, including the DC 12V / 2A power input and the NTC probe port. The image also shows the internal 2x70mm cooling fans.

2.3 NTC Temperature Sensor Placement

Connect the provided NTC temperature sensor to the designated port on the rear panel. For accurate temperature feedback, place the probe close to the primary heat source within your rack or equipment cabinet. This ensures the fan unit can effectively monitor and respond to temperature changes.

Placement of the NTC temperature sensor within a server rack

Figure 2.3: Example of NTC sensor placement near a heat-generating device in a rack for optimal temperature monitoring.

2.4 Rack Mounting

Mount the 2U fan unit into your 10-inch server rack using the provided #10-32 screws. Ensure the unit is securely fastened to prevent vibration and maintain proper airflow.

3. Operating Instructions

3.1 Control Panel and Display

The fan unit features a 0.96-inch OLED display and four control buttons: On/Off, Menu, and +/-. These allow you to configure and monitor the unit's operation.

Detailed view of the temperature control board and its interfaces

Figure 3.1: The temperature control board showing the 0.96-inch OLED display, On/Off button, Menu button, and +/- buttons. It also highlights the Power Interface, NTC Interface, and Fan Interfaces.

3.2 Power On/Off and Factory Reset

  • Power On: Short press the 'On/Off' button (less than 0.8 seconds).
  • Power Off / Restore Factory Settings: Long press the 'On/Off' button (more than 0.8 seconds).

3.3 Fan Control Modes

The unit supports two primary fan control modes:

  • Automatic Mode: Fan speeds adjust dynamically based on the temperature detected by the NTC sensor. This mode ensures efficient cooling when needed and energy savings when temperatures are low.
  • Manual Mode: Allows you to set a fixed fan speed level (0-10) regardless of the temperature.

Use the 'Menu' button to switch between parameter settings and operating modes. Use the '+/-' buttons to adjust fan speed levels in Manual mode or temperature threshold values in Automatic mode.

OLED display showing current temperature and fan speed grade

Figure 3.2: The 0.96-inch OLED display showing real-time temperature (e.g., 19°C), fan speed grade (e.g., Grade: 5), and current mode (e.g., Manual).

3.4 Fan Operation Logic (Automatic Mode)

The system's fan operation logic in Automatic mode is as follows:

  • Below Close Temp: Fans stop.
  • Between Close Temp and Warn Temp: Fan speed is automatically regulated, increasing as the temperature rises.
  • Above Warn Temp: Fans run at maximum speed, and the display will flash to indicate an alarm condition.

3.5 Product Operation Video

Video 3.1: An official product video demonstrating the operation and features of the GeeekPi 2U Rack Mount Fan Panel for DeskPi RackMate. This video provides a visual guide to the unit's functionality and control interface.

4. Maintenance

To ensure optimal performance and longevity of your GeeekPi Rack Mount Fan Unit, regular maintenance is recommended:

  • Cleaning: Periodically clean the fan grilles and blades to prevent dust accumulation, which can impede airflow and reduce cooling efficiency. Use a soft brush or compressed air. Ensure the unit is powered off before cleaning.
  • Cable Inspection: Check all cable connections, including the power supply and NTC sensor, for secure fit and any signs of wear or damage.
  • Environmental Conditions: Ensure the operating environment is within recommended temperature and humidity ranges to prevent premature component failure.

5. Troubleshooting

If you encounter issues with your fan unit, refer to the following troubleshooting guide:

ProblemPossible CauseSolution
Fan unit does not power onNo power supply connected or incompatible power supply.Ensure a DC 12V / 2A power supply is correctly connected. Verify power outlet functionality.
Fans not spinning in Automatic modeTemperature is below the 'Close Temp' threshold.This is normal operation. If cooling is desired at lower temperatures, switch to Manual mode or adjust 'Close Temp' settings.
Fans running at maximum speed constantlyTemperature is above the 'Warn Temp' threshold.Check for excessive heat sources in the rack. Ensure proper ventilation. Verify NTC sensor placement.
Inaccurate temperature readingsNTC sensor improperly placed or disconnected.Ensure the NTC sensor is securely connected and positioned near the main heat source.
Fans blowing air in the wrong directionFans are installed to pull air rather than push, or vice-versa, depending on desired airflow.The fans can be reversed if needed. Consult the product's internal design for fan orientation adjustment.

6. Specifications

FeatureDetail
ModelDR-0006
BrandGeeekPi
Product Dimensions (L x W x H)10" x 10" x 10" (Note: This appears to be packaging dimensions. Actual unit dimensions are 250mm x 88mm x 20mm as per Figure 1.2)
Cooling MethodForced Air (Dual 70mm axial fans)
Power Connector Type2-pin 2.00 mm PH connector (for control board), Barrel Jack (for external power supply)
Input VoltageDC 12V / 2A (Power supply not included)
Display0.96-inch OLED
Temperature SensorNTC (10 kΩ @25 °C, B value 3950 K, ±1%)
Compatible DevicesSBC (Single Board Computers), DeskPi RackMate T0/T1/T2/TL1 series

7. Warranty Information

This GeeekPi 10-inch 2U Rack Mount Fan Unit (Model DR-0006) comes with a 6-month warranty from the date of purchase. This warranty covers manufacturing defects and malfunctions under normal use. Please retain your proof of purchase for warranty claims.

8. Customer Support

For technical assistance, troubleshooting, or warranty inquiries, please contact GeeekPi customer support through the retailer where the product was purchased or visit the official GeeekPi website for contact information.