DEWIN Automatic Reclosing Residual Current Circuit Breaker (RCCB) with LED Display - 40A 30mA 2P AC230V Type A User Manual

1. Introduction

This manual provides detailed instructions for the installation, operation, and maintenance of your DEWIN Automatic Reclosing Residual Current Circuit Breaker (RCCB). Please read this manual thoroughly before installation and use to ensure safe and efficient operation. This device is designed to automatically reclose the circuit after an accidental trip, minimizing downtime and enhancing electrical safety.

2. Important Safety Information

3. Product Features

4. Technical Specifications

SpecificationValue
BrandDEWIN
Model NumberQDXCXDQDC-GS99306-02
Rated Current40 Ampere
Rated Residual Current30mA
Poles2P
Rated VoltageAC230V
TypeType A
Mounting TypeDIN Rail
Item Weight350 g
Package Dimensions12.4 x 11.7 x 8.9 cm
Working Frequency50/60Hz
Closing Action Time<1s
Opening Action Time<0.5s
Effective Control Signal Duration>400ms

Product Dimensions

DEWIN RCCB Product Dimensions and Circuit Diagram

Image Description: This image displays the physical dimensions of the DEWIN Automatic Reclosing RCCB, showing measurements for height (82mm), width (49mm), and depth (54mm). It also includes a basic electrical circuit diagram illustrating the connections for the device.

5. Installation and Wiring

Proper installation is crucial for the safe and correct operation of the DEWIN RCCB. Refer to the wiring diagram below and ensure all connections are secure and comply with local electrical standards.

Wiring Diagram

DEWIN RCCB Wiring Diagram

Image Description: This diagram illustrates the electrical connections for the DEWIN Automatic Reclosing RCCB. It shows the incoming Line (L) and Neutral (N) connections, the output to various loads, and the auxiliary control connections for external opening and closing buttons. Note that for automatic reclosing, an external button is not required, but for manual control, a normally open self-reset button is used.

Wiring Steps:

  1. Mount the RCCB securely on a 35mm DIN rail within your electrical panel.
  2. Connect the incoming Line (L) and Neutral (N) wires to the designated input terminals of the RCCB.
  3. Connect the load wires to the output terminals of the RCCB.
  4. For auxiliary control, connect external opening and closing buttons to the respective terminals (OPEN, CLOSE, COM). Ensure that for manual control, a normally open self-reset button is used.
  5. Verify all connections are tight and correct before restoring power.

Installation Demonstration Video

Video Description: This video demonstrates the physical installation and basic wiring of the DEWIN Automatic Reclosing Residual Current Circuit Breaker, showing how to connect the main power lines and load. It highlights the secure fastening of wires into the terminals.

Video Description: This video provides a visual guide to the installation process of the Automatic Reclosing Residual Current Circuit Breaker, including mounting on a DIN rail and connecting electrical wires. It shows the device in a typical electrical box setup.

6. Operating Instructions

The DEWIN RCCB offers both automatic and manual operating modes, indicated by the 'AUTO' and 'MANU' selector switch.

Operating Modes and LED Display

DEWIN RCCB Operating Modes and LED Display

Image Description: This diagram details the automatic and manual switching modes of the DEWIN RCCB, along with the corresponding LED digital display indicators. It explains that in AUTO mode, red flashing indicates opening and green flashing indicates closing, while in MANU mode, a yellow light is always on for manual operation. The display also shows trip count and reclosing recovery time.

Self-Locking Mode

DEWIN RCCB Self-Locking Mode and Waveform Definition

Image Description: This image illustrates the self-locking mechanism of the DEWIN RCCB. It shows the progressive reclosing delays after a circuit fault: 9 seconds for the first reclosure, 59 seconds for the second, and 299 seconds for the third. After the fourth fault, the device enters a self-locking mode, requiring manual intervention. The image also includes a table defining different waveform types (AC, A) and their action ranges.

To prevent continuous reclosing into a persistent fault, the device implements a self-locking mechanism:

  1. First Fault: The circuit automatically recloses after 9 seconds.
  2. Second Fault: The circuit automatically recloses after 59 seconds.
  3. Third Fault: The circuit automatically recloses after 299 seconds.
  4. Fourth Fault: The recloser enters a self-locking mode. Manual inspection of the circuit and a manual reset operation are required before the device can be reclosed.

Note: When the 'LOCK' mechanism is engaged (pulled up), the circuit breaker cannot be closed. This feature is designed to protect electrical safety and prevent accidental contact during inspection or maintenance.

7. Maintenance

Regular maintenance ensures the longevity and reliability of your DEWIN RCCB.

8. Troubleshooting

If you encounter issues with your DEWIN RCCB, refer to the following common problems and solutions:

If the problem persists after attempting these troubleshooting steps, contact a qualified electrician or DEWIN customer support for assistance.

9. Warranty and Support

Specific warranty details are not provided in the product information. For warranty claims, technical support, or service inquiries, please refer to the seller's return policy or contact DEWIN customer service directly through their official channels or the retailer where the product was purchased.

Related Documents - QDXCXDQDC-GS99306-02

Preview ABB 145 PM Series SF6 Power Circuit Breaker Installation and Maintenance Manual
Comprehensive installation and maintenance instructions for ABB's 145 PM series SF6 Single Pressure Outdoor Power Circuit Breakers, covering models like 121 PM40, 145 PM40, and 169 PM40. Details include pole unit, bushings, current transformers, and interrupter maintenance.
Preview Electrical Distribution Panel Wiring Diagram with Schneider Electric and ZUBR Components
Technical diagram illustrating the wiring of an electrical distribution panel, featuring Schneider Electric circuit breakers (IK60N C40A, C16A, C10A), an RCD (IID 63A 30mA), and a ZUBR 02-63 timer/control module. Includes main power input, busbar connections (L1, L2, L3, N, PE), and detailed wiring routes for phase, neutral, and earth conductors.
Preview CBI-electric ATS-385 Automatic Transfer Switch Operator's Manual
Operator's manual for the CBI-electric ATS-385 Automatic Transfer Switch Control Unit, detailing installation, operation, features, and specifications for reliable power transfer.
Preview Legrand АВДТ DX3 6000 A: Technical Specifications and Installation Guide
Detailed technical specifications, installation instructions, and performance characteristics for the Legrand АВДТ DX3 6000 A residual current circuit breaker with overcurrent protection (RCBO). Covers features, mounting, electrical data, and safety precautions.
Preview ABB VM1 Vacuum Circuit-Breaker Instruction Manual BA 504/02 E
Comprehensive instruction manual for the ABB VM1 series of vacuum circuit-breakers. Covers installation, operation, maintenance, technical specifications, safety guidelines, and diagrams for reliable electrical system protection.
Preview HVX 36-40.5-46kV Vacuum Circuit-Breaker Technical Instruction
Technical instruction manual for the Schneider Electric HVX 36-40.5-46kV vacuum circuit-breaker, covering technical data, variants, assembly, operation, servicing, and drawings. This document provides essential information for the safe and effective use of the HVX series medium voltage switching devices.