1. Introduction
This manual provides detailed instructions for the installation, operation, and maintenance of the MOBYAT DDS5188 Single Phase KWH Energy Meter. This device is designed for measuring active energy consumption in single-phase AC circuits. Please read this manual thoroughly before installation and use to ensure safe and correct operation.
2. Safety Information
Warning: Installation and maintenance should only be performed by qualified electricians. Failure to follow these instructions may result in electric shock, fire, or damage to the device.
- Ensure the power supply is disconnected before any installation or wiring.
- Do not operate the meter if it is damaged or shows signs of malfunction.
- Observe all local and national electrical codes and regulations.
- Avoid exposing the meter to direct sunlight, high temperatures, or excessive humidity.
3. Package Contents
Verify that all items are present and undamaged upon unpacking:
- 1 x MOBYAT DDS5188 Single Phase KWH Energy Meter
- 1 x User Manual (this document)
4. Product Overview
The MOBYAT DDS5188 is a compact Din Rail mountable energy meter featuring an LCD display for clear readings.

Figure 4.1: Front view of the MOBYAT DDS5188 KWH Energy Meter. This image shows the main body of the meter, including the LCD display which indicates KWH consumption, and the model number DDS5188 printed on the front. The meter is white with black text and features screw terminals for wiring.

Figure 4.2: Angled front view of the MOBYAT DDS5188 KWH Energy Meter. This perspective highlights the compact design suitable for Din rail mounting, showing the LCD display and the side profile with terminal connections.
5. Specifications
| Parameter | Value |
|---|---|
| Model | DDS5188 |
| Rated Voltage | AC220V |
| Operating Voltage Range | 176~276V AC |
| Base Current (Ib) | 5A |
| Maximum Current (Imax) | 20A / 32A (depending on variant) |
| Frequency | 50/60Hz (±10%) |
| Accuracy Class | Class 1 IEC62053-21 |
| Data Display Mode | 5+1 digits LCD display |
| Installation Method | Din Rail |
| Humidity | 20-80% |
| Weight | Approximately 120g |
6. Installation
The DDS5188 energy meter is designed for Din rail mounting. Follow these steps for proper installation:
- Preparation: Ensure the main power supply to the circuit where the meter will be installed is completely disconnected. Use appropriate safety equipment.
- Mounting: Clip the meter onto a standard 35mm Din rail in a suitable electrical enclosure. Ensure it is securely fastened.
- Wiring: Refer to the wiring diagram below for correct connections.

Figure 6.1: Back view of the MOBYAT DDS5188 KWH Energy Meter showing the wiring diagram. This diagram illustrates the connection points for the single-phase AC input (L and N) and the load, along with pulse output terminals (SO). The diagram also includes product identifiers like "2204242768".
- Connect the incoming live wire (L) to terminal 1.
- Connect the outgoing live wire (L) to the load from terminal 3.
- Connect the incoming neutral wire (N) to terminal 4.
- Connect the outgoing neutral wire (N) to the load from terminal 6.
- Optional: Connect pulse output (SO) terminals 20 and 21 for remote monitoring, if applicable.
- Verification: Double-check all connections for tightness and correctness. Ensure no bare wires are exposed.
- Power On: Restore power to the circuit. The LCD display should illuminate and begin showing energy consumption.
7. Operating Instructions
The DDS5188 meter operates automatically once correctly installed and powered. It continuously measures and displays the total active energy consumption.
- LCD Display: The 5+1 digit LCD display shows the total accumulated energy consumption in kilowatt-hours (KWH). The last digit (after the decimal point) represents tenths of a KWH.
- Pulse Indicator: A red LED indicator (often labeled "IMP" or similar) will flash proportionally to the energy consumption, indicating active measurement.
- No User Interaction: This meter is designed for direct measurement and does not typically feature user-configurable settings or buttons for resetting readings. The total KWH reading is cumulative.
8. Maintenance
The MOBYAT DDS5188 energy meter requires minimal maintenance.
- Cleaning: Use a soft, dry cloth to clean the exterior of the meter. Do not use abrasive cleaners or solvents.
- Inspection: Periodically inspect the wiring connections to ensure they remain tight and free from corrosion.
- Environmental Conditions: Ensure the operating environment remains within the specified humidity (20-80%) and temperature ranges to prolong the meter's lifespan.
- No User Serviceable Parts: Do not attempt to open or repair the meter. Refer any issues to qualified personnel.
9. Troubleshooting
If you encounter issues with your DDS5188 energy meter, refer to the following common problems and solutions:
| Problem | Possible Cause | Solution |
|---|---|---|
| Display is blank | No power supply; Incorrect wiring; Faulty meter |
|
| Meter not counting KWH | No load connected; Incorrect wiring; Faulty meter |
|
| Inaccurate readings | Incorrect wiring; Overload; External interference |
|
If problems persist after attempting these solutions, contact qualified technical support.
10. Warranty and Support
MOBYAT products are manufactured to high-quality standards. For specific warranty terms and conditions, please refer to the documentation provided at the time of purchase or contact your retailer. For technical support, please reach out to your product supplier or the manufacturer's customer service channels.