NJOY PWUP-OL300AP-AZ01B

NJOY Aten Pro 3000VA Uninterruptible Power Supply (UPS) User Manual

Model: PWUP-OL300AP-AZ01B

1. Introduction

The NJOY Aten Pro 3000VA Uninterruptible Power Supply (UPS) is designed to provide reliable power protection for sensitive electronic equipment. Featuring double conversion online technology and pure sine wave output, this UPS ensures continuous operation during power outages, voltage fluctuations, and spikes with zero transfer time. It is ideal for servers, data networks, and other critical systems requiring stable and clean power.

2. Safety Instructions

Please read and follow these safety instructions carefully before installing, operating, or maintaining the UPS. Failure to do so may result in injury or damage to the equipment.

  • Electrical Safety: Connect the UPS to a grounded AC power outlet. Do not remove the grounding prong.
  • Indoor Use Only: This UPS is intended for indoor use in a controlled environment. Avoid exposure to direct sunlight, heat sources, moisture, or corrosive substances.
  • Ventilation: Ensure adequate ventilation around the UPS. Do not block ventilation openings.
  • Battery Safety: Batteries contain hazardous energy. Do not open or mutilate batteries. Battery servicing should be performed or supervised by personnel knowledgeable about batteries and the required precautions.
  • Overload Protection: Do not overload the UPS. Ensure the total power consumption of connected devices does not exceed the UPS's rated capacity.
  • Emergency Shutdown: Familiarize yourself with the location of the ON/OFF button for emergency shutdown.

3. Product Overview

The NJOY Aten Pro 3000VA UPS features a robust design with an intuitive LCD display and essential connectivity ports.

Front view of the NJOY Aten Pro 3000VA UPS with LCD display and control buttons.

Figure 3.1: Front view of the NJOY Aten Pro 3000VA UPS, showing the LCD screen and control panel.

Rear view of the NJOY Aten Pro 3000VA UPS, highlighting RS232, USB, SNMP slot, Schuko outlets, circuit breaker, and AC input.

Figure 3.2: Rear panel of the NJOY Aten Pro 3000VA UPS, detailing the various connection ports and outlets.

3.1. Rear Panel Components

  1. RS232 Interface: For serial communication with a computer or network device.
  2. Schuko Outlets (x4): Power output sockets for connecting protected equipment.
  3. Circuit Breaker: Overload protection for the UPS.
  4. SNMP Slot: Optional slot for an SNMP card for network management.
  5. USB Interface: For USB communication with a computer.
  6. AC Input: Power input connection for the UPS.

4. Installation and Setup

4.1. Unpacking

Carefully unpack the UPS and inspect it for any shipping damage. Retain the original packaging for future use or transport.

4.2. Placement

Place the UPS in a clean, dry, and well-ventilated area. Ensure sufficient clearance around the unit for proper airflow. Avoid placing it near heat sources or in direct sunlight.

4.3. Connecting to Power

  1. Connect the UPS to a grounded AC power outlet using the provided power cord.
  2. Allow the UPS to charge for at least 4 hours before initial use to ensure optimal battery performance.

4.4. Connecting Equipment

Connect your critical electronic devices (e.g., computers, monitors, servers) to the Schuko output outlets on the rear panel of the UPS.

5. Operation

5.1. Turning On/Off

  • To Turn On: Press and hold the ON/MUTE button until you hear a beep. The UPS will perform a self-test and then enter AC mode.
  • To Turn Off: Press and hold the OFF/ENTER button until the UPS shuts down.

5.2. LCD Display

The LCD display provides real-time status information about the UPS, including:

  • Load Level
  • Battery Level
  • AC Mode
  • Battery Mode
  • Bypass Mode
  • Fault Indicators

5.3. Eco Mode

The Eco Mode feature helps reduce energy consumption. When the input voltage is within the acceptable range, the UPS will bypass the inverter to save energy, increasing overall efficiency.

6. Software Management

The NJOY Aten Pro 3000VA UPS includes management software for comprehensive monitoring and control. This software can be accessed via serial (RS232), USB, or an optional Ethernet (SNMP card) connection.

Screenshot of the UPS management software interface, showing system status, power flow, and configuration options.

Figure 6.1: Example of the UPS management software interface.

Key features of the management software include:

  • Real-time operational status visualization.
  • Scheduling for power on/off and battery tests.
  • Comprehensive UPS configuration options.
  • Safe shutdown of the operating system.

7. Maintenance

7.1. Battery Maintenance

The UPS uses sealed, maintenance-free lead-acid batteries. While these batteries do not require liquid top-ups, regular checks are recommended:

  • Perform a battery self-test periodically using the management software or UPS controls.
  • Replace batteries when their capacity significantly diminishes. Battery replacement should be performed by qualified personnel.

7.2. General Cleaning

Keep the UPS clean and free from dust. Use a dry cloth to wipe the exterior. Do not use liquid cleaners or solvents.

8. Troubleshooting

This section addresses common issues you might encounter with your NJOY Aten Pro 3000VA UPS.

ProblemPossible CauseSolution
UPS does not turn onNo AC input power; Battery dischargedCheck power cord connection and wall outlet; Allow UPS to charge for several hours.
UPS beeps continuouslyOverload; Battery low/faultReduce connected load; Check battery status via LCD or software.
Short backup timeBattery not fully charged; Battery end-of-lifeCharge UPS for at least 4 hours; Consider battery replacement.
UPS in Bypass modeInternal fault; OverloadContact technical support if fault persists; Reduce connected load.

9. Specifications

Detailed technical specifications for the NJOY Aten Pro 3000VA UPS.

FeatureSpecification
BrandNJOY
Model NumberPWUP-OL300AP-AZ01B
Power Rating3000 VA / 2700 W
UPS TypeOnline Double Conversion
Output WaveformPure Sine Wave
Nominal Input Voltage230 Vac
Nominal Output Voltage200, 208, 220, 230, 240 Vac
Accepted Input Voltage Range110-300 VAC ± 5% (50% load), 160-300 VAC ± 5% (100% load)
Frequency50 Hz ~ 60 Hz
Output Sockets4 x Schuko
Transfer Time (AC-DC)Zero
Transfer Time (Inverter to Bypass)4 ms
Communication PortsUSB, RS232 (Optional: Smart SNMP card)
Operating Temperature0 ~ 40 °C
EfficiencyUp to 90%
Battery TypeSealed Lead-Acid (Maintenance-Free)
Battery Configuration6 x 12V/9Ah
Compatible DevicesDVR, surveillance systems, Wi-Fi modem, monitor, printer, TV, desktop, gaming computer
Item Weight27.6 Kilograms
Form FactorTower

10. Warranty and Support

NJOY offers a comprehensive warranty and dedicated customer support for the Aten Pro series.

  • Warranty: The NJOY Aten Pro UPS comes with a 3-year warranty. Batteries are covered by a 1-year warranty.
  • Customer Support: For assistance before, during, or after your purchase, please contact our professional customer service team.

Related Documents - PWUP-OL300AP-AZ01B

Preview nJoy Horus Plus Series UPS User Manual - Installation, Operation, and Safety
Comprehensive user manual for the nJoy Horus Plus Series Uninterruptible Power Supply (UPS). Includes installation guides, operational instructions, technical specifications, safety warnings, and troubleshooting for models PWUP-LI060H1-AZ01B through PWUP-LI200H1-AZ01B.
Preview nJoy Aten PRO Series UPS User Manual
User manual for the nJoy Aten PRO Series UPS, covering models PWUP-OL300AP-AZ01B, PWUP-OL200AP-AZ01B, PWUP-OL100AP-AZ01B, Aten PRO 1000, Aten PRO 2000, and Aten PRO 3000. Provides installation, operation, safety, and troubleshooting information for these Uninterruptible Power Supply units.
Preview nJoy Aster 6/10KT Black/White User Manual - Reliable Power Protection
Comprehensive user manual for the nJoy Aster 6/10KT Black/White Uninterruptible Power Supply (UPS). Learn about installation, operation, features like double-conversion technology, and troubleshooting for essential power continuity.
Preview nJoy Aira Series UPS User Manual (600/1200VA)
User manual for the nJoy Aira Series UPS models UPCSTLP860TAICP01B and UPCSTLP812HAICP01B. Provides setup, operation, safety, and troubleshooting information for these uninterruptible power supply units.
Preview nJoy Token Series UPS User Manual - UPCSBLS660TTOAZ01B, UPCSBLS680TTOAZ01B
User manual for the nJoy Token Series UPS models UPCSBLS660TTOAZ01B and UPCSBLS680TTOAZ01B. Learn about installation, operation, safety, troubleshooting, and specifications for these power protection devices.
Preview nJoy Cadu Series UPS User Manual - UPCMTLS665TCAAZ01B, UPCMTLS685TCAAZ01B, UPCMTLS610HCAAZ01B, UPCMTLS615HCAAZ01B, UPCMTLS620HCAAZ01B
Comprehensive user manual for the nJoy Cadu Series UPS, including installation, operation, safety warnings, troubleshooting, and disposal information for models UPCMTLS665TCAAZ01B through UPCMTLS620HCAAZ01B.