APC AP4430

APC Rack ATS AP4430 Automatic Transfer Switch Instruction Manual

Model: AP4430 - 200-208V, 20A, L6-20 Input, (8) C13, (1) C19 Output

1. Introduction

This manual provides essential instructions for the installation, operation, and maintenance of your APC Rack Automatic Transfer Switch (ATS) Model AP4430. The AP4430 is designed to provide redundant power to single-corded equipment by automatically transferring the load to a secondary power source if the primary source fails. This ensures continuous power availability for critical devices in rack environments.

Key Features:

  • Automatic transfer between two AC power sources.
  • Advanced load monitoring capabilities.
  • Remote on/off switching control of individual outlets.
  • Power cycling, delayed power sequencing, and outlet use management.

2. Safety Information

Before installing or operating the APC Rack ATS, read and understand all safety instructions. Failure to follow these instructions may result in equipment damage, personal injury, or death.

  • Ensure proper grounding for all connected equipment.
  • Do not operate the unit in environments with excessive moisture or extreme temperatures.
  • Disconnect all power sources before performing any maintenance or installation procedures.
  • Only qualified personnel should perform installation and service.

3. Setup and Installation

The APC Rack ATS AP4430 is designed for rack-mounting. Follow these steps for proper installation and connection.

3.1 Package Contents

Verify that all components are present:

  • APC Rack ATS AP4430 unit
  • Rack-mounting hardware
  • Installation guide

3.2 Physical Installation

  1. Mount the AP4430 unit into a standard 19-inch equipment rack using the provided rack-mounting hardware. Ensure secure fastening.
  2. Allow adequate airflow around the unit for proper cooling.

3.3 Power Connections

The AP4430 requires two independent power sources for redundant operation. Each input cable is equipped with an L6-20 plug.

  1. Connect the Source A input power cord to a reliable 200-208V, 20A power source.
  2. Connect the Source B input power cord to a separate, independent 200-208V, 20A power source.
  3. Ensure both power sources are active and stable.
Rear view of APC Rack ATS AP4430 showing dual L6-20 power inputs and multiple C13 and C19 output receptacles.

Figure 1: Rear panel of the APC Rack ATS AP4430, illustrating the dual power inputs and output receptacles.

3.4 Equipment Connections

The AP4430 provides (8) C13 and (1) C19 output receptacles for connecting your equipment.

  1. Connect your single-corded equipment to the available C13 and C19 output receptacles on the AP4430.
  2. Ensure that the total load connected to the ATS does not exceed its maximum rated capacity of 20A.
Front view of APC Rack ATS AP4430 with LED indicators and control buttons.

Figure 2: Front panel of the APC Rack ATS AP4430, showing the power flow indicators and control interface.

4. Operating Instructions

Once installed and connected, the AP4430 operates automatically to provide redundant power.

4.1 Automatic Transfer Function

The ATS continuously monitors the voltage and frequency of both Source A and Source B. If the primary source (typically Source A) falls outside acceptable parameters, the ATS will automatically transfer the connected load to the secondary source (Source B) within milliseconds, ensuring uninterrupted power to your equipment.

4.2 LED Indicators

The front panel features LED indicators that display the status of the power sources and the current load path:

  • Source A/B Status LEDs: Indicate the availability and quality of each input power source.
  • Load Path LEDs: Show which source is currently supplying power to the connected equipment.
  • Output Status LEDs: Provide information on individual outlet status (if applicable for switched models).

4.3 Remote Management (if configured)

The AP4430 supports remote management via network connection. Refer to the separate network management card manual for detailed configuration and operation of features such as:

  • Remote monitoring of power consumption and environmental conditions.
  • Individual outlet switching (on/off, reboot).
  • Scheduled power cycling and sequencing.
  • Event logging and alarm notifications.

5. Maintenance

The APC Rack ATS AP4430 is designed for reliable operation with minimal maintenance. However, periodic checks are recommended.

  • Visual Inspection: Periodically inspect the unit and cables for any signs of damage, wear, or loose connections.
  • Cleaning: Keep the unit free from dust and debris. Use a dry, soft cloth for cleaning. Do not use liquid cleaners or solvents.
  • Firmware Updates: Check the APC website periodically for available firmware updates to ensure optimal performance and security. Follow the instructions provided with the firmware update package.

6. Troubleshooting

This section addresses common issues you might encounter with the AP4430.

6.1 No Power to Connected Equipment

  • Check Input Power: Verify that both Source A and Source B are supplying power and that their respective status LEDs on the ATS front panel are illuminated.
  • Check Circuit Breakers: Ensure that the circuit breakers for both input power sources are not tripped.
  • Check Output Connections: Confirm that equipment power cords are securely plugged into the ATS output receptacles.

6.2 ATS Not Transferring

  • Verify Source Availability: Ensure both Source A and Source B are available and within acceptable voltage/frequency ranges. The ATS will only transfer if one source fails and the other is healthy.
  • Check Load: Ensure the connected load does not exceed the ATS capacity, which could prevent proper transfer.

6.3 Communication Issues (Remote Management)

  • Network Connection: Verify the network cable is securely connected and network settings are correct.
  • IP Address: Confirm the ATS has a valid IP address and is reachable on the network.
  • Firmware: Ensure the network management card firmware is up to date.

If issues persist, contact APC Technical Support for assistance.

7. Specifications

Detailed technical specifications for the APC Rack ATS AP4430.

AttributeValue
Model NumberAP4430
Input Voltage200-208V
Input Current Rating20 Amps
Input Connector TypeNEMA L6-20
Output Receptacles(8) C13, (1) C19
Form FactorRackmount
Product Dimensions (L x W x H)23.63 x 4.5 x 14 inches
Item Weight10.6 pounds
Cooling MethodAir
Date First AvailableSeptember 6, 2017

8. Warranty Information

APC products are backed by a manufacturer's warranty. For specific warranty terms and conditions applicable to your AP4430 unit, please refer to the warranty card included with your product or visit the official APC website. Keep your proof of purchase for warranty claims.

9. Technical Support

For technical assistance, product inquiries, or troubleshooting beyond the scope of this manual, please contact APC Technical Support:

  • Visit the official APC website for support resources, FAQs, and contact information.
  • Refer to the contact details provided in your product documentation.

© 2023 APC by Schneider Electric. All rights reserved.