Dinuy terminal micro 5

Dinuy Terminal Micro 5 Digital Time Switch User Manual

Model: Terminal Micro 5

Brand: Dinuy

1. Introduction

This manual provides comprehensive instructions for the installation, operation, and maintenance of your Dinuy Terminal Micro 5 Digital Time Switch. Please read this manual carefully before using the device to ensure safe and efficient operation. This device is designed to control electrical circuits based on programmed time schedules.

2. Important Safety Information

  • Electrical Hazard: Installation and maintenance should only be performed by a qualified electrician in accordance with all local and national electrical codes.
  • Disconnect power at the main circuit breaker before installing or servicing the device.
  • Do not expose the device to moisture, extreme temperatures, or corrosive environments.
  • Ensure all connections are secure and properly insulated to prevent short circuits.
  • Do not exceed the maximum load capacity specified for the device.

3. Product Overview

The Dinuy Terminal Micro 5 is a compact digital time switch designed for DIN rail mounting. It features a clear LCD display for time and program status, along with intuitive buttons for easy programming.

Dinuy Terminal Micro 5 digital time switch, front view showing display, buttons, and wiring terminals.

Figure 1: Dinuy Terminal Micro 5 Digital Time Switch

This image displays the Dinuy Terminal Micro 5 digital time switch. The device is white, designed for DIN rail mounting. The top section shows terminals labeled '1' and '2' for power input. Below this, there are terminals '1', '2', '3' for the switched output, with a rating of 'μ16(6)A 250V~'. The central part features a digital LCD screen displaying 'DINUY', '18.06.18', 'LUNES' (Monday), 'On', and '9:28.00'. Below the screen are four blue buttons: 'M' (Mode), 'OK', '-' (Minus/Left arrow), and '+' (Plus/Right arrow). The bottom section shows terminals 'N' (Neutral) and 'L' (Live) for the main power supply, with '230V/50-60Hz' indicated.

3.1. Components

  • LCD Display: Shows current time, day, program status, and programming menus.
  • 'M' Button (Mode): Used to navigate through different modes (e.g., time setting, program setting).
  • 'OK' Button: Confirms selections and settings.
  • '-' Button (Minus/Left Arrow): Decreases values or moves left in menus.
  • '+' Button (Plus/Right Arrow): Increases values or moves right in menus.
  • Terminals L & N: Main power supply input (230V/50-60Hz).
  • Terminals 1, 2, 3: Switched output contacts (μ16(6)A 250V~).

4. Installation and Setup

4.1. Mounting

The Dinuy Terminal Micro 5 is designed for DIN rail mounting. Snap the device onto a standard 35mm DIN rail in your electrical panel.

4.2. Wiring Diagram

WARNING: Ensure power is disconnected before wiring.

  1. Connect the main Live (L) wire to the 'L' terminal at the bottom of the device.
  2. Connect the main Neutral (N) wire to the 'N' terminal at the bottom of the device.
  3. For the switched output, connect the load's Live wire to terminal '1' or '3' (depending on desired contact type, typically '1' for normally open).
  4. Connect the incoming Live wire for the load to terminal '2'.
  5. Refer to the markings on the device for precise terminal identification: Input power (L, N) and Switched output (1, 2, 3).

4.3. Initial Power-Up

After wiring, restore power. The display should illuminate. If the display is blank, check power connections. The device may require initial time and date setting.

5. Operating Instructions

5.1. Setting Current Time and Day

  1. Press the 'M' button repeatedly until the time setting mode is displayed (e.g., flashing hours).
  2. Use the '+' and '-' buttons to adjust the hour. Press 'OK' to confirm.
  3. Repeat for minutes, then for the current day of the week.
  4. Press 'OK' to save and exit the time setting mode.

5.2. Programming ON/OFF Schedules

The device allows setting multiple ON/OFF programs for different days or groups of days.

  1. Press the 'M' button until 'PROG' or a similar indicator appears.
  2. Use '+' or '-' to select a program number (e.g., '1 ON'). Press 'OK'.
  3. Set the desired ON time (hour and minute) using '+' and '-' and confirming with 'OK'.
  4. Select the days for this program (e.g., Mon-Fri, daily, specific days) using '+' and '-' and confirming with 'OK'.
  5. Repeat for the corresponding OFF time ('1 OFF').
  6. Continue for additional programs as needed.
  7. Press 'M' to exit programming mode and return to normal operation.

5.3. Manual Override

To temporarily override the programmed schedule, press the 'M' button briefly during normal operation. This will cycle through 'ON', 'OFF', and 'AUTO' modes. Select 'AUTO' to resume programmed operation.

6. Maintenance

The Dinuy Terminal Micro 5 requires minimal maintenance. Ensure the device is kept clean and free from dust. Use a soft, dry cloth for cleaning. Do not use abrasive cleaners or solvents.

7. Troubleshooting

  • Device not powering on: Check main power supply and wiring connections (L and N terminals). Ensure the circuit breaker is on.
  • Load not switching: Verify that the program is correctly set and the device is in 'AUTO' mode. Check the load's wiring and functionality. Ensure the load does not exceed the device's maximum switching capacity.
  • Incorrect time display: Reset the current time and day as per section 5.1.
  • Programs not executing: Ensure the device is in 'AUTO' mode. Recheck program settings for correct ON/OFF times and selected days.

8. Technical Specifications

FeatureSpecification
ManufacturerDinuy
Manufacturer Product IDIH TER MC5
Model Numberterminal micro 5
Input Voltage230V AC, 50-60Hz
Switching Capacityμ16(6)A 250V~
Mounting TypeDIN Rail
Package Dimensions11.2 x 6.8 x 5 cm
Product Weight100 g

9. Warranty Information

This product is covered by the manufacturer's standard warranty. Please refer to the warranty card included with your purchase or contact Dinuy customer support for detailed warranty terms and conditions. Keep your proof of purchase for warranty claims.

10. Customer Support

For technical assistance, troubleshooting not covered in this manual, or warranty inquiries, please contact your local Dinuy distributor or visit the official Dinuy website for contact information.

Related Documents - terminal micro 5

Preview Manual de Interruptores Horarios Modulares Digitales DINUY IH TER MC/TEB MC
Manual de usuario completo para los interruptores horarios modulares digitales DINUY IH TER MC0, IH TEB MC0, IH TER MC2 e IH TEB MC2, cubriendo instalación, programación y características vía NFC.
Preview DINUY IHEMT 1328 Timer Switch User Manual
User manual for the DINUY IHEMT 1328 timer switch, providing operating instructions, installation guidelines, and connection diagrams in multiple languages.
Preview DINUY Temporized Tactile Pushbutton - Installation and User Manual
Comprehensive manual for DINUY's Temporized Tactile Pushbutton, covering installation, technical specifications, and operation for models like PT EMP EL4, PT SUP EL4, and PT GAR EL1.
Preview DINUY Laüka Dot KNX Capacitive Switch with Temperature and Luminosity Sensors + Thermostat Function Manual
Instructions and technical specifications for the DINUY Laüka Dot KNX capacitive switch, featuring 2, 4, 6, or 8 buttons, integrated temperature and luminosity sensors, and a thermostat function. Includes installation and commissioning guidance.
Preview DINUY Electrical Device Installation Guide
Step-by-step installation instructions for DINUY electrical devices, covering mounting and wiring. Includes model numbers and connection details.
Preview Declaración de Conformidad CE DINUY IH TER BT2 Terminal Bluetooth
Declaración oficial de conformidad CE para el Terminal Bluetooth DINUY IH TER BT2, confirmando el cumplimiento de las directivas y normas de la UE aplicables.