Weintek eMT3070A1WK

MT8100iE Weintek 10.2" Graphic HMI User Manual

Model: eMT3070A1WK

1. Introduction

The Weintek MT8100iE is a 10.2-inch Human Machine Interface (HMI) designed for industrial automation applications. It features an 800 x 480 TFT industrial-grade LCD and is built to fully support major PLCs such as Rockwell, Siemens, Mitsubishi, and Omron. This manual provides essential information for the proper installation, operation, and maintenance of your MT8100iE HMI.

2. Safety Information

Please read and understand all safety instructions before operating the device. Failure to comply may result in injury or damage to the equipment.

  • Ensure the power supply is disconnected before performing any installation or maintenance.
  • Only qualified personnel should install and service this equipment.
  • Do not expose the device to excessive moisture, dust, or extreme temperatures.
  • Verify correct wiring and connections to prevent electrical hazards.
  • The front panel is NEMA4/IP65 compliant, but ensure proper sealing during installation to maintain this rating.

3. Package Contents

Verify that all items are present in the package:

  • MT8100iE HMI Unit
  • Mounting Brackets (4x)
  • Power Connector
  • User Manual (this document)
  • CD-ROM with EasyBuilder Pro Software (or download link)

4. Product Overview

Familiarize yourself with the components and interfaces of the MT8100iE HMI.

4.1 Front View

Front view of the Weintek MT8100iE HMI displaying an industrial boiler control system interface.

Figure 4.1: Front view of the MT8100iE HMI, showing the 10.2-inch TFT LCD touchscreen and the power indicator LED at the top left.

4.2 Side View

Side profile of the Weintek MT8100iE HMI, showing its slim design.

Figure 4.2: Side profile of the MT8100iE, illustrating its compact form factor suitable for panel mounting.

4.3 Rear View

Rear view of the Weintek MT8100iE HMI, showing mounting points, fuse holder, and reset button.

Figure 4.3: Rear view of the MT8100iE, highlighting the mounting holes for panel installation, the fuse holder for power protection, and the system reset button.

4.4 Communication Ports

Bottom view of the Weintek MT8100iE HMI showing USB, Ethernet, and serial communication ports.

Figure 4.4: Bottom view of the MT8100iE, detailing the various communication ports including USB, Ethernet, COM1 (RS-232), and COM2 (RS-485 2W/4W).

5. Setup

5.1 Panel Mounting

  1. Cut an opening in the control panel according to the dimensions provided in the installation guide (refer to the separate installation template for precise measurements).
  2. Insert the MT8100iE HMI into the cutout from the front.
  3. From the rear of the panel, insert the four mounting brackets into the slots on the HMI unit.
  4. Tighten the screws on the mounting brackets evenly until the HMI is securely fastened to the panel. Do not overtighten.

5.2 Power Connection

  • Connect a 24V DC power supply to the power input terminal block on the rear of the HMI.
  • Ensure correct polarity (+ and -).
  • Secure the connection firmly.

5.3 Communication Connections

  • Serial Ports: Use the COM1 (RS-232) and COM2 (RS-485 2W/4W) ports to connect to PLCs or other serial devices. Refer to your PLC's documentation for specific wiring diagrams.
  • Ethernet Port: Connect an Ethernet cable to the RJ45 port for network communication with PLCs or for remote access.
  • USB Ports: Use the USB host ports for connecting USB flash drives for project transfers or other peripherals.

6. Operating Instructions

6.1 Powering On

Once all connections are secure, apply power to the HMI. The power indicator LED will illuminate, and the HMI will boot up, displaying the configured project.

6.2 Project Download

To load a new project or update an existing one:

  1. Create or modify your HMI project using the EasyBuilder Pro software on a PC.
  2. Connect the PC to the HMI via Ethernet or USB.
  3. In EasyBuilder Pro, use the 'Download' function to transfer the project to the HMI.
  4. The HMI will restart with the new project loaded.

6.3 Touchscreen Operation

The MT8100iE features a resistive touchscreen. Use your finger or a non-sharp stylus to interact with the on-screen elements such as buttons, input fields, and displays.

6.4 PLC Communication

The HMI is designed to communicate with various PLCs. Ensure the communication settings (protocol, baud rate, station ID, etc.) configured in your EasyBuilder Pro project match those of your connected PLC.

7. Maintenance

Regular maintenance ensures optimal performance and longevity of your HMI.

  • Cleaning: Use a soft, damp cloth to clean the screen and casing. Do not use abrasive cleaners or solvents. Ensure no liquid enters the device.
  • Firmware Updates: Periodically check the Weintek website for firmware updates to ensure your HMI has the latest features and bug fixes.
  • Fuse Replacement: If the HMI does not power on, check the fuse located on the rear panel. Replace it with a fuse of the same type and rating if necessary. Always disconnect power before replacing the fuse.
  • Environmental Conditions: Ensure the operating environment remains within the specified temperature and humidity ranges to prevent damage.

8. Troubleshooting

This section provides solutions to common issues you might encounter.

ProblemPossible CauseSolution
HMI does not power on.No power supply, incorrect wiring, blown fuse.Check power connection, verify wiring polarity, replace fuse if blown.
Touchscreen is unresponsive.Screen calibration issue, hardware fault.Perform screen calibration (refer to EasyBuilder Pro documentation), contact support if issue persists.
Cannot communicate with PLC.Incorrect communication settings, wrong cable, PLC offline.Verify communication protocol, baud rate, and station ID in EasyBuilder Pro. Check cable connections. Ensure PLC is powered on and running.
Project download fails.Network issue, incorrect IP address, firewall blocking.Check network cable, verify HMI and PC IP addresses are in the same subnet. Temporarily disable firewalls for testing.

9. Specifications

FeatureDescription
Model NumbereMT3070A1WK
Screen Size10.2 Inches
Resolution800 x 480
Aspect Ratio1.66:1
Screen SurfaceGlossy
MemoryBuilt-in 128 MB Flash Memory
Real-Time Clock (RTC)Yes
Front Panel RatingNEMA4/IP65 Compliant
Serial PortsCOM1 RS-232 / COM2 RS-485 (2W/4W)
Email NotificationStatus e-Mail notification feature

10. Warranty and Support

Weintek products are manufactured to high quality standards. For warranty information and technical support, please refer to the official Weintek website or contact your authorized distributor. Keep your purchase receipt as proof of purchase for warranty claims.

For software downloads, drivers, and additional resources, visit the official Weintek support portal.

Related Documents - eMT3070A1WK

Preview WEINTEK cMT3106XM Handheld HMI Datasheet | Specifications & Features
Detailed datasheet for the WEINTEK cMT3106XM 10.1-inch WVA Handheld HMI. Explore features, technical specifications, environmental ratings, and ordering information.
Preview Weintek cMT2108X2 10.1-inch TFT HMI - Datasheet and Specifications
Detailed datasheet for the Weintek cMT2108X2, a 10.1-inch TFT HMI with 1024x600 resolution, 4GB flash memory, and industrial-grade features. Includes specifications, dimensions, and ordering information.
Preview WEINTEK MODBUS RTU, RTU over TCP PLC Connection Guide
Technical guide from WEINTEK detailing the configuration and connection of HMIs using MODBUS RTU and RTU over TCP protocols. Covers HMI and PLC settings, device addressing, wiring diagrams, and Modbus RTU function codes for industrial automation.
Preview Weintek cMT-G02X Series HMI Installation Instructions
Detailed installation instructions for the Weintek cMT-G02X Series HMI, covering environment setup, power and communication connections, software configuration, safety precautions, and warranty information.
Preview Weintek cMT-CTRL01 Series HMI Installation Guide
Installation instructions for the Weintek cMT-CTRL01 Series HMI. This guide covers environmental setup, unpacking, physical installation, power and communication connections, system settings, LED indicators, reset procedures, battery replacement, and warranty information. Designed for industrial automation professionals.
Preview cMT-G05X Series Installation Instructions | Weintek HMI
Official installation instructions for the Weintek cMT-G05X Series HMI. Covers setup, environment, power connections, system settings, communication, software, and warranty.