1. Introduction
This manual provides detailed instructions for the safe and efficient use of the BEMKO A31-BL01A-MID A30-BM030-L 3-Phase 5(80)A Electric Meter. This device is designed for measuring active energy consumption in three-phase electrical systems. Please read this manual thoroughly before installation and operation to ensure proper function and safety.
The BEMKO A30-BM030-L is a certified (CE) energy monitor suitable for DIN rail mounting, offering reliable measurement with a clear LCD display.
2. Important Safety Information
- Electrical Hazard: Installation and maintenance should only be performed by qualified personnel. Ensure power is disconnected before any work on the meter or associated wiring.
- Proper Use: Use this device only for its intended purpose of measuring electrical energy. Do not use it for purposes other than specified.
- Environmental Conditions: Do not expose the meter to extreme temperatures, humidity, or corrosive environments beyond its specified operating range (-10 °C to +45 °C, IP20).
- Damage: Do not install or operate the meter if it appears damaged. Contact the supplier for assistance.
- Modifications: Do not attempt to open, modify, or repair the meter. This will void the warranty and may pose a safety risk.
3. Product Overview
The BEMKO A30-BM030-L is a compact 3-phase electric meter designed for easy integration into electrical panels. It features a digital LCD display for energy readings and is built for durability and accuracy.

Figure 3.1: Front view of the BEMKO A30-BM030-L 3-Phase Electric Meter, showing the LCD display and branding.
3.1 Key Components
- LCD Display: Shows energy consumption in kWh (6+2 digits).
- Pulse Output Indicator: An LED that flashes to indicate energy pulses (1000 imp/kWh).
- Terminals: Input (IN) and Output (OUT) terminals for connecting the three phases (L1, L2, L3) and neutral (N).
- DIN Rail Clip: For secure mounting on a 35mm DIN rail.
4. Technical Specifications
| Parameter | Value |
|---|---|
| Model Number | A30-BM030-L |
| Rated Voltage | 3 x 230 / 400 V |
| Current (Base/Max) | 5 A / 80 A |
| Accuracy Class | 1.0 |
| Frequency | 50/60 Hz |
| Standby Consumption | ≤ 2 W, 10 VA |
| Pulse Output | 1000 imp/kWh (inactive) |
| Display Type | LCD, 6 + 2 digits |
| Mounting | 35 mm DIN rail (6P modules) |
| Operating Temperature | -10 °C to +45 °C |
| IP Class | IP20 |
| Material | Plastic |
| Certification | CE |
| Dimensions (L x W x H) | 11.65 x 7.6 x 6.5 cm |
| Weight | 50 grams |

Figure 4.1: Dimensional drawing of the BEMKO A30-BM030-L electric meter, showing length (116.5 mm), width (76.0 mm), and depth (65 mm).

Figure 4.2: Side profile of the BEMKO A30-BM030-L electric meter, highlighting the DIN rail mounting mechanism and a depth of 36.0 mm from the mounting surface.
5. Installation Instructions
The BEMKO A30-BM030-L electric meter is designed for installation on a standard 35mm DIN rail. Ensure all safety precautions are followed before beginning installation.
5.1 Mounting
- Disconnect Power: Ensure the main power supply to the installation area is completely disconnected and locked out.
- Select Location: Choose a dry, well-ventilated location within the specified operating temperature range (-10 °C to +45 °C) and IP20 protection.
- Mount on DIN Rail: Clip the meter onto a standard 35mm DIN rail. Ensure it is securely fastened.
5.2 Wiring
Refer to the wiring diagram below for correct connection of the three-phase and neutral lines. Incorrect wiring can damage the meter or pose a safety hazard.

Figure 5.1: Wiring diagram for the BEMKO A30-BM030-L 3-Phase Electric Meter. Terminals 1, 3, 5, 7 are for input (IN) L1, L2, L3, N respectively. Terminals 2, 4, 6, 8 are for output (OUT) L1, L2, L3, N respectively.

Figure 5.2: Close-up view of the terminal blocks on the BEMKO A30-BM030-L electric meter, showing connections for phases and neutral.
- Connect the incoming Phase 1 (L1) to terminal 1.
- Connect the outgoing Phase 1 (L1) to terminal 2.
- Connect the incoming Phase 2 (L2) to terminal 3.
- Connect the outgoing Phase 2 (L2) to terminal 4.
- Connect the incoming Phase 3 (L3) to terminal 5.
- Connect the outgoing Phase 3 (L3) to terminal 6.
- Connect the incoming Neutral (N) to terminal 7.
- Connect the outgoing Neutral (N) to terminal 8.
- Ensure all connections are tight and secure to prevent loose contacts and overheating.
- After wiring, double-check all connections against the diagram before restoring power.
6. Operating Instructions
Once properly installed and powered, the BEMKO A30-BM030-L electric meter will automatically begin measuring energy consumption.

Figure 6.1: Close-up of the BEMKO A30-BM030-L LCD display, showing the 6+2 digit energy reading in kWh.
6.1 Reading the Display
- The LCD displays the total active energy consumed in kilowatt-hours (kWh).
- The display format is 6+2 digits, meaning six digits for whole kWh and two digits for decimal kWh (e.g., 000000.01 kWh).
6.2 Pulse Output
- The meter features an LED indicator that flashes at a rate of 1000 pulses per kWh (1000 imp/kWh). This provides a visual indication of energy consumption.
- The pulse output is inactive, meaning it is for visual indication only and not for external connection to other systems.
7. Maintenance
The BEMKO A30-BM030-L electric meter is designed for maintenance-free operation. No internal user-serviceable parts are present.
- Cleaning: If necessary, gently wipe the exterior of the meter with a soft, dry cloth. Do not use abrasive cleaners, solvents, or liquids directly on the device.
- Inspection: Periodically inspect the wiring connections to ensure they remain secure.
- Environmental: Ensure the operating environment remains within the specified temperature and humidity limits.
8. Troubleshooting
If you encounter issues with your BEMKO A30-BM030-L electric meter, refer to the following common troubleshooting steps:
| Problem | Possible Cause | Solution |
|---|---|---|
| Display is blank or off. | No power supply to the meter. | Check the main power supply and all wiring connections. Ensure power is restored. |
| Meter not registering consumption. | Incorrect wiring or no load connected. | Verify wiring against the diagram (Figure 5.1). Ensure there is an active electrical load connected downstream of the meter. |
| Pulse LED not flashing. | No energy consumption or meter malfunction. | Confirm that there is an active load drawing power. If the display shows consumption but the LED does not flash, contact support. |
| Meter appears damaged. | Physical damage. | Do not operate. Disconnect power immediately and contact the supplier for replacement or repair. |
If the problem persists after following these steps, please contact your supplier or a qualified electrician.
9. Warranty and Support
Specific warranty details for the BEMKO A31-BL01A-MID A30-BM030-L electric meter are not provided within this document. For warranty claims or technical support, please refer to the purchase documentation or contact your point of sale or the manufacturer, BEMKO SP. Z O.O., directly.
When contacting support, please have your product model number (A30-BM030-L) and purchase date available.